background image

Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07

13

A. Install the Outside Air Kit

This 

fi

 replace will operate correctly only if adequate ventila-

tion is provided to allow proper draft to the 

fi

 replace system. 

See Section 2.

The outside air kit is supplied with this 

fi

 replace.

 

Using an 

outside air kit is highly recommended to minimize the effects 
of negative pressure within the structure. We recommend 
you utilize the shortest duct run to optimize the performance 
of the outside air kit. Cold air 

fl

 ow can be minimized by put-

ting a small dip in the duct creating a cold air trap. This trap 
can also help prevent heat build-up and exhausting out the 
intake due to the stack effect. The outside air kit inlet should 
be positioned in a manner that will not allow snow, leaves, 
etc. to block the inlet. In some installations the air duct 
may need to be run vertically. In such an installation, a 3 ft 
(.914 m) height difference must be maintained from the top 
of the uppermost chimney section to the outside combustion 
air inlet. See Figure 4.2.

See Figure 4.3 for proper placement of outside air inlet.

Risk of Smoke Spillage

Outside air inlet must be located to prevent blockage 
from:
 • 

Leaves

 • 

Snow/ice

 • 

Other 

debris

Blockage may cause combustion air starvation.

CAUTION

Sharp Edges

•  Wear protective gloves and safety glasses 

during installation.

CAUTION

Installation of Fireplace 

Fire Risk
Asphyxiation Risk

Do not draw outside combustion air from:
• Wall, 

fl

 oor or ceiling cavity.

•  Enclosed space such as an attic or 

garage.

•  Close proximity to exhaust vents or 

chimneys.

Fumes or odor may result.

WARNING

Outside Air

Shield

Outside Air

Plate

Assembly

2 Wire Ties

Flexible Duct

(not supplied)

Figure 4.1  Outside Air Installation

The outside air kit is installed on the right side (PIER-40) 
or  open end (BAY-40) of the 

fi

 replace. See Figure 4.4 for 

handle location/operation.

Remove the cover plate from the side (PIER-40) or bottom 
(BAY-40) of the 

fi

 replace assembly where the air kit is to be 

installed.

Содержание BAY-40

Страница 1: ...ly a fire may result causing property damage personal injury or death Do not store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance Do not overfire Overfiring will void your warranty Comply with all minimum clearances to combustibles as specified Failure to comply may cause house fire WARNING Fire Risk For use with solid wood fuel or decorative ...

Страница 2: ...bel Information Location The model information regarding your specific fireplace can be found on the rating plate located on the smoke shield of the fireplace Congratulations FIREPLACE NO MODEL NO MODEL NO MFG DATE WARNING RISK OF FIRE DAMAGE REPLACE GRATE WITH HEARTH HOME TECHNOLOGIES INC FIRECHAMBER INTENDED FOR USE WITH HEARTH HOME TECHNOLOGIES INC LISTED FIREPLACE PARTS SEE INSTALLATION AND OP...

Страница 3: ...the Chimney 21 6 Complete the Enclosure 22 A Chimney Termination 22 B Chase Top 24 C Install the Termination Cap 24 7 Accessories 26 A Gas Log Lighter Provisions 26 8 Finishing 27 A Hearth Extension 27 B Finishing Material 28 C Mantel 29 D Sidewalls Surrounds 29 E Glass Doors 29 9 Operating Instructions 30 A General Information 30 B Outside Air 31 C Clear Space Near the Fireplace 31 D Flue Damper ...

Страница 4: ...ed as a decorative fire place It should not be factored as a primary heat source in residential heating calculations Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to the owner s information manual provided with this fireplace For assistance or additional information consult a qualified installer service agency or your dealer WARNING Fi...

Страница 5: ...icinity of the fireplace Avoid installing the fireplace near doors walkways or small isolated spaces Recessed lighting should be a sealed can design attic hatches weather stripped or sealed attic mounted duct work and air handler joints and seams taped or sealed Basement installations should be avoided due to stack effect Stack effect creates negative pressure in lower levels Hearth Home Technolog...

Страница 6: ...fire Penetrate the highest part of the roof This minimizes the effects of wind turbulence Be located away from trees adjacent structures uneven roof lines and other obstructions Offsets can restrict draft so their use should be minimized Consider the fireplace location relative to floor and ceiling and attic joists Recommended Location Marginal Location Location Not Recommended Recommended Locatio...

Страница 7: ...Support straps on rafter supports chimney not shown Termination cap Chimney penetrates roof preferably without affecting roof rafters Offset Return with hanger straps Framing headed off in ceiling joists Enclosed space above and around fireplace Mantel and surround Decorative facing and trim Hearth extension Factory built fireplace Protective metal hearth strip s Outside combustion air Combustible...

Страница 8: ...ause odors CAUTION E Inspect Fireplace and Components Carefully remove the fireplace and components from the packaging The vent system components and doors are shipped in separate packages Report to your dealer any parts damaged in shipment Read all the instructions before starting the installation Follow these instructions carefully during the installation to ensure maximum safety and benefit Fir...

Страница 9: ...in 1575 mm 16 in 406 mm 56 in 1422 mm 64 in 1626 mm 64 in 1626 mm 16 in 406 mm 26 in 660 mm to front of fireplace opening Figure 3 1 Fireplace Locations Fire Risk Provide adequate clearances Around air openings To combustibles For service access Locate fireplace away from traffic areas WARNING Note Illustrations and photos reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustration...

Страница 10: ...pliance 2 in 51 mm min 2 in min 51 mm Must have 2 in 51 mm minimum clearance to header 0 in to floor 2 in 51 mm min 2 in 51 mm min 2 in 51 mm min 2 in 51 mm min Figure 3 2 Clearances to Combustible Materials Fire Risk Comply with all minimum clearances to combustibles as specified Framing or finishing material used on the front of or in front of the appliance closer than the minimums listed must b...

Страница 11: ...mm HEARTH EXTENSION shaded HEARTH EXTENSION shaded 1 2 in min distance from fireplace to combustible materials Note In addition to these framing dimensions also reference the following sections Clearances Section 3 B Mantel Projections Section 8 C Fireplace Dimensions Section 12 A Note 6 in 152 mm 12 in 305 mm from opening of fireplace 62 in 1575 mm 16 in 406 mm 56 in 1422 mm 64 in 1626 mm 64 in 1...

Страница 12: ...False Ceiling Figure 3 5 Chase Assembly F Chimney Requirements When planning your fireplace location the chimney con struction and necessary clearances must be considered The fireplace system and chimney components have been tested to provide flexibility in construction Vertical distances are measured from the base of the fireplace as shown in Figure 5 2 1 2 Figure 3 6 Chase Constructions 1 Firepl...

Страница 13: ...ation a 3 ft 914 m height difference must be maintained from the top of the uppermost chimney section to the outside combustion air inlet See Figure 4 2 See Figure 4 3 for proper placement of outside air inlet Risk of Smoke Spillage Outside air inlet must be located to prevent blockage from Leaves Snow ice Other debris Blockage may cause combustion air starvation CAUTION Sharp Edges Wear protectiv...

Страница 14: ...ide house or in ventilated crawl space YES NO NO NO NO Use only duct materials specified by manufacturer preferably with short run or mainly straight duct except small dip for cold air trap which will help prevent flow of cold air Factory built fireplace Figure 4 3 Outside Combustion Air Placement 3 ft min from top of uppermost chimney section to air inlet Attic insulation shield must be used to k...

Страница 15: ... the front of the elevated platform must be protected with a protective metal hearth strip as shown in Figure 4 6 Raised Platform Floor 2 in 51 mm 1 in 25 mm min overlap 2 in 51 mm Top piece must overlap bottom piece Figure 4 6 Protect the Front of an Elevated Platform Level the Fireplace Level the fireplace side to side and front to back Shim with noncombustible material such as sheet metal as ne...

Страница 16: ... Additional support for tall chimneys Install roof flashing according to minimum requirements Maintain minimum clearances to combustibles as specified Offsets returns may not exceed 30 from vertical Lock chimney sections together firmly to resist movement Ceiling firestops are required where chimney passes through ceiling or floor Support straps for offsets returns must be secured to adequate fram...

Страница 17: ...10 m min height double offset return 90 ft 27 4 m max height 6 ft 1 83 m max unsupported chimney above roof 44 in 1118 mm Effective Height Figure 5 2 Chimney Requirements Table 5 1 Do NOT connect this fireplace to a chimney flue servicing another appliance Do NOT connect to any air distribution duct or system CAUTION Fire Risk Must maintain 2 in 51 mm air clearance to insulation and other combusti...

Страница 18: ...d from the base of the fireplace to the top of the starter collar See Dimensions in Section 12 Table 5 2 A B 1 1 4 in 32 mm OVERLAP Figure 5 3 Chimney Offset Return Fire Risk Draft will be restricted if offset returns greater than 30 are used WARNING Example Your A dimension from Figure 5 3 is 14 1 2 in 368 mm Using Table 5 2 the dimension closest to but not less than 14 1 2 in 368 mm is 15 3 4 in...

Страница 19: ...ons ROOM ABOVE non insulated ceiling ATTIC ABOVE insulated ceiling B A Ceilng firestop from bottom Ceiling firestop from top When attic insulation shield not used Note Use same dimensional lumber for framing ceiling firestop and joists Figure 5 5 Installing the Ceiling Firestop Fire Risk Do NOT install substitute or damaged chimney components MUST use chimney system described in this manual NO OTH...

Страница 20: ...ling firestop is required see Figures 5 7 and 5 8 Roll the shield around the chimney if already installed until you have a 3 in 76 mm overlap and the three holes on each side match up large holes on top Insert three screws into the matching holes to form a tube Bend three tabs on the bottom of the tube inward to 90 to maintain chimney clearance See Figure 5 6 Rest the insulation shield on the ceil...

Страница 21: ... While doing so be aware of the height and unsupported chimney length limitations given un der Section 5 A Chimney Requirements Check each section by pulling up slightly from the top to en sure proper engagement before installing the succeeding sections If they have been connected correctly they will not disengage when tested G Secure the Chimney When offsets and returns are joined to straight pip...

Страница 22: ...Termination B Termination Caps Staggered Height Gas Wood or Fuel Oil Termination Wood 20 in min 508 mm Termination Caps Same Height If using decorative cap cover s this distance may need to be increased Refer to the installation instruc tions supplied with the decorative cap cover 8 ft 2 44 m min for B Vent 20 in 508 mm min for direct vent to Perpendicular Wall Figure 6 2 Multiple Chimneys 6 6 Com...

Страница 23: ...ed This is measured on the horizontal actual length may be larger depending on the pitch of the roof Cut out and frame the opening See Chapter 25 of the Uniform Building Code for roof framing details Assemble the Chimney Sections Through the Roof Continue to add chimney sections through the roof open ing maintaining at least a 2 in 51 mm air space to com bustible materials Install the Roof Flashin...

Страница 24: ...tall the Termination Cap For installations utilizing a TR11T Round Telescoping Termination Cap the uppermost chimney section must be below the top of the chase top but not more than 14 1 2 in 368 mm below the top of the chase top Minimum overlap of chimney and termination cap must be 1 1 2 in 38 mm See Figure 6 6 Install the chimney sections up through the chase enclosure When using a TR11 Round T...

Страница 25: ...1 2 in 114 mm below the chase top See Figure 6 7 For installations utilizing an TCT1175 Terra Cotta Cap the last chimney section must be between 7 in 178 mm below the chase top and 2 in 51 mm above See Figure 6 8 For chase installations you can use a TR11 Round Termination Cap a TR11T Round Telescoping Termination Cap an ST1175 Square Termination Cap or a TCT1175 Terra Cotta Termination Cap For in...

Страница 26: ... with fireplace mortar or high temp noncombustible sealant 4 in 102 mm Outer Shell of Fireplace Figure 7 1 Gas Line Installation 7 7 Accessories Asphyxiation Risk Damper must be locked open when gas logs installed Gas fire generates fumes WARNING Fire Risk For use with solid wood fuel or decorative gas appliance only DO NOT install unvented gas logs WARNING Knockouts are provided on both sides of ...

Страница 27: ... 03 To substitute materials for the factory available hearth ex tensions see Figure 8 3 and calculate insulation alterna tives as per Table 8 1 and the following formulas Thermal conductivity per inch thickness k k BTU inch foot2 hour F Required thickness Rk Thermal resistance per inch thickness r r foot2 hour F BTU inch Required thickness R rB Fire Risk Metal hearth strips MUST be installed Spark...

Страница 28: ...lass or plasters or any combination thereof Materials that are reported as passing ASTM E 136 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 C shall be considered non combustible materials Non Combustible Sealant Material Sealants which will not ignite and burn Rutland Inc Fireplace Mortar 63 Rutland 72R Nuflex 302 GE RTV106 GE RTV116 After completing the framing ...

Страница 29: ...ts between the finished wall and fireplace top and sides using only a 300 F minimum sealant C Mantel A combustible mantel may be positioned no lower than 12 in 305 mm above the top of the fireplace opening The combustible mantel may have a maximum depth of 12 in 305 mm Combustible trim pieces that project no more than 1 1 2 in 38 mm from the face of the fireplace can be placed no closer than 6 in ...

Страница 30: ...ain the system in top operating condition Fire Risk Do not operate fireplace before reading and understanding operating instructions Failure to operate fireplace properly may cause fire WARNING Fire Risk For use with solid wood fuel or decorative gas appliance only Do not install unvented gas logs WARNING Damper Control Up Open Down Closed Outside Air Control Handle Out Open Handle In Closed Figur...

Страница 31: ...ng homes fitted with tightly sealed doors and windows are relatively air tight In this case an outside air source must be made available to feed combustion air from outside the home An outside air control handle allows you control of the out side air inlet if your fireplace is equipped with this option Use of outside air for combustion is highly recommended to conserve heated air within the struct...

Страница 32: ...gallon of water put it in the fireplace and try to burn it This sounds ridiculous but that is exactly what you are doing if you burn unseasoned wood Fire Risk Use only factory installed integral grate May cause overfire WARNING Seasoning Seasoned firewood is nothing more than wood that is cut to size split and air dried to a moisture content of around 20 The time it takes to season wood varies fro...

Страница 33: ... and binders to be burned from the fireplace and the refractory and paint to cure You may notice an industrial odor the first few fires This is consid ered normal Note When first lighting your fireplace it may be neces sary to pre warm the flue to establish a draft This is done by holding a rolled up piece of burning newspaper under the flue damper for a few moments This will help reduce smoke spi...

Страница 34: ...fts tight sealing construction of the structure or mechan ical exhausting devices which will create a negative air pres sure within the structure where the fireplace is located A Understanding Vent Problems If smoke spillage occurs from a fireplace opening when the door is open and the proper chimney height flue size and configuration requirements for the installation have been met there is either...

Страница 35: ...ion in chimney Down draft from chimney temperature or from negative house pressure Does the kindling wood not ignite Condition amount arrangement of kindling and fuel Use more drier well spaced kindling and fuel Does the kindling ignite but the fuel doesn t Amount of kindling Use more kindling use smaller dry wood Condition of fuel Does the fuel ignite but not burn well Condition of fuel Use well ...

Страница 36: ...n air Yes Fire too close to front Build fire farther back Do not use exhaust fans during startup and or check for need for balanced air make up system Competition with exhaust devices Diagnostic Questions Possible Causes of Condition Solutions Is the damper closed No Down draft or negative pressure Close the damper at end of burn Yes Negative pressure from exhaust fans and or house stack effect Ch...

Страница 37: ...ap Remove 2 screws from the front and back and lift the top off Cap Top Be sure holes in cap top and cap base are aligned European Copper Series Termination Cap CT King shown Cap Base Remove 8 screws 9 for King lift top cover Figure 11 1 Chimney Termination Cap Cleaning Fire Risk Disposal of ashes Ashes should be placed in metal container with tight fitting lid Do not place metal container on comb...

Страница 38: ... all joints are properly engaged and the chimney is properly secured A chimney fire can permanently damage your chimney sys tem Failure to replace damaged components and make proper repairs creates risk of fire Inspect Maintenance Tasks Screens 1 Assess condition of screen and replace as necessary Screens are required 2 Verify maintenance of proper clearance to combustible household objects Glass ...

Страница 39: ...erials A Fireplace Dimensions 42 36 40 7 12 40 24 GAS KNOCKOUT GAS KNOCKOUT ELECTRICAL KNOCKOUT FOR ST36C 42 36 40 12 24 11 20 FRONT VIEW BAY 40 END VIEW BAY 40 TOP VIEW BOTH MODELS BOTTOM VIEW BAY 40 FRONT VIEW PIER 40 END VIEW PIER 40 22 5 5 22 3 9 53 8 8 44 8 5 12 175 8 471 8 471 8 ...

Страница 40: ...insula Fireplace BAY 40 Island Fireplace DM1036 Glass Doors bi fold Clear View Black DM1036B Glass Doors bi fold Clear View Polished Brass DM1036S Glass Doors bi fold Clear View Stainless Steel DM1000 Fixed End Glass Panel Clear View Black DM1000B Fixed End Glass Panel Clear View Polished Brass DM1000S Fixed End Glass Panel Clear View Stainless Steel HX3 Hearth Extension GR3 Integral Grate include...

Страница 41: ... in 1219 mm long SL11 Chimney Stabilizer SL1130 Chimney Offset Return 30 deg FS538 Ceiling Firestop Straight FS540 Ceiling Firestop 30 deg AS10 SL1100 Straight Attic Insulation Shield 24 in 610 mm JB577 Chimney Joint Band CB576 Chimney Bracket RF570 Roof Flashing Flat to 6 12 Pitch RF571 Roof Flashing 6 12 to 12 12 Pitch TR11 Round Termination Cap TR11T Round Telescoping Termination Cap TCT1175 Te...

Страница 42: ...m JB577 Chimney Joint Band 10 1 2 in 267 mm CB576 Chimney Joint Band 39 7 8 in 1013 mm 28 in 711 mm 15 1 4in 387 mm RF571 Roof Flashing 25 1 4 in 641 mm 29 in 737 mm 15 1 4 in 387 mm RF570 Roof Flashing 21 in 533 mm Inside Diameter 11 in 279 mm Outside Diameter 13 in 330 mm Catalog A B FS538 0 deg 17 in 432 mm FS540 30 deg 26 in 660 mm Assembled Diameter 17 in 432 mm Height 24 in 610 mm ...

Страница 43: ...40 mm CT56 Chase Top A B C D Decorative Shroud LDS33 LDS46 15 3 4 in 400 mm 32 3 8 in 822 mm 34 3 8 in 873 mm 14 3 4 in 375 mm 23 in 584 mm 23 in 584 mm 9 3 8 in 238 mm 9 1 4 in 235 mm 17 in 432 mm 20 in 508 mm Catalog A B C D in mm in mm in mm in mm LDS33 36 914 36 914 8 1 2 216 11 279 LDS46 48 1219 72 1829 8 1 2 216 11 279 LDS BV Decorative Shroud Catalog A B C D E LDS BV in 26 12 1 2 15 1 2 22 ...

Страница 44: ...hop CT3 Pawn CT3 Knight CT3 King 21 in 533 mm 47 3 4 in 1213 mm 24 in 610 mm 18 1 4 in 464 mm 41 1 8 in 1045 mm 20 in 508 mm 16 in 406 mm 38 3 8 in 975 mm 16 in 406 mm 21 in 533 mm 25 3 4 in 654 mm 20 5 8 in 524 mm 20 3 4 in 527 mm 38 5 8 in 981 mm 20 in 508 mm European Copper Caps ...

Страница 45: ... sides Minimum Base Dimensions Inches N A 26 5 X 28 with Radiation Shield 28 X 30 34 X 34 with Radiation Shield 28 X 30 with Radiation Shield or 34 X 34 Minimum Height Inches N A 28 1 4 27 1 2 28 1 4 27 1 2 ROOFED STYLE with 12 X 22 264 sq in opening on each side and 3 in space between the radiation shield and chase top Minimum Base Dimensions Inches N A 27 X 27 with Radiation Shield 27 X 27 with ...

Страница 46: ...ning Fireplace 34977 Rev T 11 07 46 D Service Parts Service Parts Diagram Multi Sided Woodburning Fireplace Service Parts BAY 40 Beginning Manufacturing Date 2 4 04 Ending Manufacturing Date Active 1 2 3 11 10 14 5 9 6 12 4 13 8 7 ...

Страница 47: ...856 1 10 Side Refractory 27857 2 11 Hearth Refractory 13213A 1 12 Front Ashlip 13214A 1 13 Left Side Ashlip 13827A 1 14 Right Side Ashlip 13828A 1 Nailing Flange 12692 4 Firescreen Rod 11866B 2 Firescreen Assembly 12267 2 Screen Handle 4021 149 1ea Damper Control 13229 1 Damper Weight 19785A 1 Door Track for bottom 4012 002 1 Door Track for top 15425 1 Grate Retainer 13834B 2 Side Refractory Brack...

Страница 48: ...d Woodburning Fireplace 34977 Rev T 11 07 48 Service Parts Diagram Multi Sided Woodburning Fireplace Service Parts PIER 40 Beginning Manufacturing Date N A Ending Manufacturing Date Active 1 2 3 10 7 12 14 13 9 5 4 11 8 6 ...

Страница 49: ...y only post 15 95 23911A 1 8 End Upper Front Face overlay only pre 14 95 13233C 1 8 End Upper Front Face overlay only post 15 95 23949A 1 9 Firescreen Assembly pre 22 97 11855A 4 9 Firescreen Assembly post 23 97 12267 4 Heat Glo Logo Screen Handle 4021 149 4 Firescreen Rod 11866B 4 10 Grate GR3 1 Hairpin Clips 101025 4 Hearth Refractory 13321B 1 Installation Instructions 17920 1 11 Lower Front Fac...

Страница 50: ...Heat Glo Multi Sided Woodburning Fireplace 34977 Rev T 11 07 50 This page intentionally left blank ...

Страница 51: ... at the current minimum wholesale price but HHT SHALL NOT BE RESPONSIBLE FOR ANY LABOR TRANSPORTATION OR OTHER INDIRECT DAMAGES 4 During the first six 6 months after installation HHT shall at its option replace or repair the glass doors and any electrical components if operation is faulty This does not include glass panels broken during shipment misuse or careless handling After the first six 6 mo...

Страница 52: ...may be covered by one or more of the following patents United States 4593510 4686807 4766876 4793322 4811534 5000162 5016609 5076254 5113843 5191877 5218953 5263471 5328356 5341794 5347983 5429495 5452708 5542407 5601073 5613487 5647340 5688568 5762062 5775408 5890485 5931661 5941237 5947112 5996575 6006743 6019099 6048195 6053165 6145502 6170481 6237588 6296474 6374822 6413079 6439226 6484712 654...

Отзывы: