Heat & Glo • 6X-AU Installation Manual • 2508-980 Rev. C
• 3/18
F. Vent Diagrams
Figure 4.8 Vent Cap - Generic Fireplace Shown
General Rules:
• SUBTRACT 3 ft. (914 mm) from the total H measurement
for each 90º elbow installed horizontally.
• SUBTRACT 1-1/2 ft. (457 mm) from the total H
measurement for each 45º elbow installed horizontally.
• A maximum of three 90º elbows (or six 45º elbows) may
be used in any vent configuration. Some elbows may be
installed horizontally. See Figure 4.18.
• Elbows may be placed back to back anywhere in the
system.
•
Any 90º elbow may be replaced with two back to back
45º elbows.
• When penetrating a combustible wall, a wall shield
firestop must be installed.
• When penetrating a combustible ceiling, a ceiling firestop
must be installed.
• Horizontal runs of vent do not require vertical rise;
horizontal runs may be level.
• Horizontal termination cap should have a 1/4 in. (6
mm) downward slant to allow any moisture in cap to be
released. See Figure 4.8.
W
A
LL
1/4 in. max.
(6 mm)
WARNING
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles
between ceiling firestops.
• ALWAYS maintain specified clearances around
venting and firestop systems.
• Install wall shield and ceiling firestops as speci
-
fied.
Failure to keep insulation or other material away
from vent pipe may cause fire.
WARNING
Fire Risk.
• When using DVP-HRC-SS and DVP-HRC-ZC-
SS termination caps on top vented fireplaces, a
6 inch minimum vertical vent section is required
before installing first elbow.