Heat-N-Glo SL-350TV Скачать руководство пользователя страница 10

12

!

C.   Bedroom Installation in Canada

This model 

MUST NOT

 be vented into a vent system in-

stalled exterior to a building.  The part of the vent system

above the roof line can be exterior to the building.

D.  Vent Termination

WARNING: MAJOR U.S. BUILDING CODES

SPECIFY MINIMUM CHIMNEY AND/OR VENT

HEIGHT ABOVE THE ROOF TOP. THESE MIN-

IMUM HEIGHTS ARE NECESSARY IN THE IN-

TEREST OF SAFETY.  FIGURE 6 AND TABLE

SHOW MINIMUM HEIGHTS, PROVIDED THE

TERMINATION  CAP  IS AT  LEAST  8-FEET

FROM A VERTICAL WALL.

!

ROOF PITCH

H (MIN.) FT.

FLAT TO 6/12

1.0

6/12 TO 7/12

1.25

OVER 7/12 TO 8/12

1.5

OVER 8/12 TO 9/12

2.0

OVER 9/12 TO 10/12

2.5

OVER 10/12 TO 11/12

3.25

OVER 11/12 TO 12/12

4.0

OVER 12/12 TO 14/12

5.0

OVER 14/12 TO 16/12

6.0

OVER 16/12 TO 18/12

7.0

OVER 18/12 TO 20/12

7.5

OVER 20/12 TO 21/12

8.0

       Figure 6. Vent Termination

VENT

CAP

12

X

ROOF PITCH

IS  X/ 12

LOWEST 

DISCHARGE 

OPENING

H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING

Step 5.  Positioning, Leveling, and

               Securing the Fireplace

To properly position, level, and secure the fireplace:
• Place the fireplace into position (see Figure 7).
• Level the fireplace from side to side and from front to

back.

• Shim the fireplace with non-combustible material, such

as sheet metal, as necessary.

• Secure the fireplace to the framing by nails or screws us-

ing nailing tabs.

!

!

Figure 7.  Proper Positioning, Leveling,

    and Securing of a Fireplace

Step 6. The Gas Control Systems

WARNING:  THIS UNIT IS NOT FOR USE WITH

SOLID FUEL.

Two types of gas control systems are used with these mod-

els: 

Standing Pilot Ignition

 and 

Direct Spark Ignition (DSI).

Standing Pilot Ignition System

This system includes millivolt control valve, standing pilot,

thermopile/thermocouple flame sensor, and piezo ignitor.

WARNING: 110-120 VAC MUST NEVER BE

CONNECTED TO A CONTROL VALVE IN A

MILLIVOLT SYSTEM.

Direct Spark Ignition (DSI) System

The DSI system includes a 120V control valve, electronic

module, and spark ignitor/flame sensor.

WARNING:  CONTINUOUS 110-120 VAC MUST

BE WIRED TO THE FIREPLACE JUNCTION

BOX IN A DSI SYSTEM.

WARNING:

To ensure proper

clearances the front

framing header must be

installed on its narrow

edge and to the front of

the frame.

Содержание SL-350TV

Страница 1: ...derwriters Laboratories Listed 541 985C 4 00 READ THIS MANUAL BEFORE INSTALLING OR OPERATING THIS APPLIANCE THIS INSTALLERS GUIDE MUST BE LEFT WITH APPLIANCE FOR FUTURE REFERENCE Please contact your H...

Страница 2: ...he installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the first firing of the fireplace READ the Using Your Firepla...

Страница 3: ...m 11 A Vent System Approvals 11 B System Components 11 C Bedroom Installation in Canada 12 D Vent Termination 12 Step 5 Positioning Leveling and Securing the Fireplace 12 Step 6 The Gas Control System...

Страница 4: ...urrent edition The Uniform Mechanical Code current edition and local Building Officials for the options allowed in obtaining an effective bedroom volume of unconfined space This model natural gas and...

Страница 5: ...ailure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat N Glo Warranty will be voided by and Heat N Glo disclaims any responsibility for the following...

Страница 6: ...837mm 30 1 2 775mm 2 1 4 57mm 5 3 8 138mm GAS LINE ACCESS 11 3 8 288mm 1 2 13mm 4 101mm B VENT 8 1 2 216mm 16 1 4 414mm 15 3 4 400mm 22 5 8 575mm ELECTRICAL ACCESS TOP STANDOFFS HOOD VENT COLLARS ELEC...

Страница 7: ...l is 1 2 inch 13mm A 34 B 31 C 16 1 4 Figure 3 Framing Dimensions The distance from the unit to combustible construction is to be measured from the unit outer wrap surface to the combustible construct...

Страница 8: ...e is located It is recommended that all natural venting non air tight gas fireplaces have outside air connected to them It is also recommended that the building be mechanically or passively balanced t...

Страница 9: ...inside the unit to check that the vent pipe is attached NOTE It is always better to first attach a straight section of vent to the unit before attaching an elbow Avoid using elbows in the vent system...

Страница 10: ...Fireplace To properly position level and secure the fireplace Place the fireplace into position see Figure 7 Level the fireplace from side to side and from front to back Shim the fireplace with non co...

Страница 11: ...line through the gas line hole and connect it to the shut off valve When attaching the pipe support the control so that the lines are not bent or torn Step 8 Gas Pressure Requirements Pressure require...

Страница 12: ...ts require that 110 120 VAC be wired to the factory installed junction box before the fireplace is per manently installed Figure 10 Standing Pilot Ignition Wiring Diagram NOTE THIS UNIT IS NOT APPROVE...

Страница 13: ...b into the pilot hole on the outer wrap Optional Accessories Optional remote control kits require that 110 120 VAC be wired to the fireplace junction box Figure 11 Direct Spark Ignition DSI Wiring Dia...

Страница 14: ...ce but MUST NEVER overlap onto the front face The joints between the finished wall and the fireplace top and sides can only be sealed with a 300 F 149 C minimum sealant WARNING WHEN FINISHING THE FIRE...

Страница 15: ...run for 8 hours on the initial start up This will help to cure the chemicals used in the paint and logs Subsequent lightings of the fireplace will not require this purging of air from the gas supply...

Страница 16: ...annually By Qualified service technician Task Brush or vacuum the control compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically B...

Отзывы: