8

Appliance Certification

The Heat-N-Glo fireplace models discussed in this 

Installers

Guide

 have been tested to certification standards and listed

by the applicable laboratories.

Certification

MODEL:

    PIER-38HV, ST-38HV

LABORATORY:   

 Underwriters Laboratories

TYPE:    

Direct Vent Gas Fireplace

STANDARD: 

   ANSI Z21.50•CGA2.22•UL307B

Installation Codes

The fireplace installation must conform to local codes. Before

installing the fireplace, consult the local building code

agency to ensure that you are in compliance with all

applicable codes, including permits and inspections.

In the absence of local codes, the fireplace installation must

conform to the  National Fuel Gas Code ANSI Z223.1 (in

the United States) or the CAN/CGA-B149 Installation Codes

(in Canada). The appliance must be electrically grounded

in accordance with local codes or, in the absence of local

codes with the National Electric Code ANSI/NFPA No. 70

(in the United States), or to the  CSA C22.1 Canadian Electric

Code (in Canada).

These models may be installed in a bedroom or bed-sitting

room in the U.S.A. and Canada.

1

Approvals and Codes

High Altitude Installations

U.L. Listed gas fireplaces are tested and approved for

elevations from 0 to 2,000 feet in the U.S.A. and from 0 to

4,500 feet in Canada.

When installing this fireplace at an elevation above 2,000

feet (in the United States), it may be necessary to decrease

the input rating by changing the existing burner orifice to a

smaller size. Input should be reduced four percent (4%) for

each 1,000 feet above sea level, unless the heating value of

the gas has been reduced, in which case this general rule

will not apply.

When installing this fireplace at an elevation between 2,000

and 4,500 feet (in Canada), the input rating must be reduced

by ten percent (10%).

When installing this fireplace at an elevation above 4,500

feet (in Canada), check with local authorities.

Consult your local gas utility for assistance in determining

the proper orifice for your location.

Heat-N-Glo Quality

Systems registered

by SGS ICS

Содержание Pier-38HV

Страница 1: ...APPLIANCE FOR FUTURE REFERENCE 1 This appliance may be installed in an af termarket permanently located manu factured mobile home where not pro hibited by local codes 2 Thisapplianceisonlyfor usewith...

Страница 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Страница 3: ...Vent System 15 A Vent System Approvals 15 B Installing Vent Components 22 C Vent Termination 25 Step 4 Positioning Leveling and Securing the Fireplace 28 Step 5 The Gas Control Systems 28 Step 6 The G...

Страница 4: ...0 in the United States or to the CSAC22 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting room in the U S A and Canada 1Approvals and Codes High Altitude Ins...

Страница 5: ...e to follow these instructions will void the owner s warranty and may present a fire hazard When planning a fireplace installation it s necessary to determine Where the unit is to be installed The ven...

Страница 6: ...GRILL GAS CONTROLS LABELS GAS LINE ACCESS ELECTRICAL ACCESS 28 3 16 716mm 36 1 16 915mm 38 5 8 981mm 31 3 16 792mm 11 5 16 287mm 22 11 16 576mm 35 3 16 894mm 3 3 8 85mm 2 52mm 2 52mm 3 1 16 79mm 6 5...

Страница 7: ...S LINE ACCESS 2 52MM 3 1 16 79mm 22 11 16 576mm 3 3 8 85mm ELECTRICAL ACCESS 2 52mm 29 1 8 739mm 31 3 16 792mm 38 1 4 972mm 35 3 16 894mm 38 5 8 981mm VENT COLLAR TOP STANDOFFS VENT COLLAR TOP GRILL G...

Страница 8: ...DES THEREFORE YOUR LOCAL BUILD ING CODES MUST BE CHECKED TO DETERMINE THE REQUIREMENTS FOR THESE STEPS Factory built fireplace chases should be constructed in the manner of all outside walls of the ho...

Страница 9: ...the hole is 1 inch 25 4mm above the center of the horizontal vent pipe 37 1 8 943mm Framing should be constructed of 2 X 4 lumber or heavier WARNING FRAMING DIMENSIONS ASSUME USE OF 1 2 INCH THICK WA...

Страница 10: ...2 1054mm 40 3 8 1026mm 1 25mm PIPE CLEARANCE 4 102mm 1 25mm PIPE CLEARANCE 4 102mm Vertical Vent Runs Vertical Vent Runs 40 1016mm 37 7 8 962mm 1 1 2 38mm Horizontal Vent Runs FIRESTOP 1 1 2 38mm FIRE...

Страница 11: ...ing configura tion used Identifying Vent Components The vent systems installed on this gas fireplace may include one two or three 90 elbow assemblies The relationships of vertical rise to horizontal r...

Страница 12: ...10 feet or greater the ver tical baffle kit BAF VERT may be required to improve flame appearance NOTE If the vertical vent component is 10 feet or more you may want to install the vertical baffle to...

Страница 13: ...m VENTING WITH ONE 1 90 ELBOW V FT H FT 1 MIN 305mm 2 MAX 610mm 2 MIN 610mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 86m 4 MIN 1 22m 8 MAX 2 44m 5 MIN 1 5m 10 MAX 3 05m 6 MIN 1 86m 12 MAX 3 6m 7 MIN 2 13m 14 M...

Страница 14: ...10mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 86m 4 MIN 1 22m 8 MAX 2 44m 5 MIN 1 5m 10 MAX 3 04m 6 MIN 1 86m 12 MAX 3 6m 7 MIN 2 13m 14 MAX 4 27m 14 MAX 4 27m V H 37 MAX 11 3m V H H1 1 H V V1 1 NOTE For verti...

Страница 15: ...914 mm 2 MAX 610 mm 6 MAX 1 86 m 4 MIN 1 22 m 2 MAX 610 mm 8 MAX 2 4 m 5 MIN 1 52 m 2 MAX 610 mm 10 MAX 3 04 m 6 MIN 1 86 m 2 MAX 610 mm 12 MAX 3 65 m 7 MIN 2 13 m 2 MAX 610 mm 14 MAX 4 26 m 14 MAX 4...

Страница 16: ...m 4 MAX 1 22 m 3 MIN 914 mm 2 MAX 610 mm 6 MAX 1 86 m 4 MIN 1 22 m 2 MAX 610 mm 8 MAX 2 4 m 5 MIN 1 52 m 2 MAX 610 mm 10 MAX 3 04 m 6 MIN 1 86 m 2 MAX 610 mm 12 MAX 3 65 m 7 MIN 2 13 m 2 MAX 610 mm 14...

Страница 17: ...305mm 2 MAX 610mm 2 MIN 610mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 86m 4 MIN 1 22m 8 MAX 2 44m 5 MIN 1 5m 10 MAX 3 04m 6 MIN 1 86m 12 MAX 3 6m 7 MIN 2 13m 14 MAX 4 27m 14 MAX 4 27m V H 37 MAX 11 3m NOTE Fo...

Страница 18: ...ST VENT COM PONENT FAILURE TO SEAL THIS JOINT MAY CAUSE THE FIREPLACE TO OPERATE IMPROPER LY SEE FIGURE 16 Figure 16 Attaching the First Vent Component to the Starting Collars STARTING COLLAR STOVE SE...

Страница 19: ...e Position the firestops on both sides of the hole previ ously cut and secure the firestops with nails or screws The heat shields of the firestops MUST BE placed to wards the top of the hole Continue...

Страница 20: ...sts Figure 22 Ceiling Firestop Ceiling Side If the area above the ceiling is NOT an attic position and secure the ceiling firestop on the ceiling side of the previously cut and framed hole Figure 21 1...

Страница 21: ...lange of the wall firestop to secure the vent pipe in place For trapezoidal cap termination kits Using screws secure the cap to the exterior wall through the flanges built into the cap Figure 24 Round...

Страница 22: ...pened C 9 U S A 12 Canada clearance to permanently closed window D 24 vertical clearance to ventilated soffit located above the termi nal within a horizontal distance of 2 feet 60 cm from the cen ter...

Страница 23: ...FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMI NATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICALWALLAND 2 FEET BELOWA HORIZON TAL OVERHANG NOTE This also pertains to vertical vent systems i...

Страница 24: ...OT BE USED IN CANADA Step 5 The Gas Control Systems WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL Two types of gas control systems are used with these mod els Standing Pilot Ignition and Direct Spa...

Страница 25: ...nfiltration Open the fireplace lower grille insert the gas supply line through the gas line hole and connect it to the shut off valve When attaching the pipe support the control so that the lines are...

Страница 26: ...ox Maintain correct polarity when wiring the junction box Optional Accessories Optional fan and remote control kits require that 110 120 VAC be wired to the fireplace junction box Wall Switch Position...

Страница 27: ...um Vertical and Maximum Horizontal Dimensions of Combustibles above Fireplace FLAME SENSOR SPARKER IGNITION MODULE GAS VALVE ON OFF SWITCH REMOTE OUTLET FAN OUTLET CONNECTORS HOT GROUND NEUTRAL OPTION...

Страница 28: ...d to be repositioned slightly to avoid excessive flame impingement Step 10 Installing Trim Logs Ember Material Figure 35 Sealant Material Placing the Ember Material See two separate bags of ember mate...

Страница 29: ...he glass and run the fireplace for an additional 8 hours This will help to cure the chemicals used in the paint and logs Step 12 Lighting the Fireplace You ve reviewed all safety warnings you ve check...

Страница 30: ...r vacuum the control compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a...

Отзывы: