CAUTION: IF JOINTS BETWEEN THE FINISHED WALLS

AND THE FIREPLACE SURROUND (TOP AND SIDES)

ARE SEALED, A 300°

 

F. MINIMUM SEALANT MATE-

RIAL MUST BE USED.  THESE JOINTS ARE NOT RE-

QUIRED TO BE SEALED. ONLY NON-COMBUSTIBLE

MATERIAL (USING 300° F. MINIMUM ADHESIVE, IF

NEEDED) CAN BE APPLIED AS FACING TO THE FIRE-

PLACE SURROUND. SEE THE DIAGRAM BELOW.

Hearth Extensions

A hearth extension may be desirable for aesthetic reasons.

However, ANSI or CAN/CGA testing standards 

do not

 require

hearth extensions for gas fireplace appliances.

Installing the Trim

Combustible materials may be brought up to the specified

clearances on the side and top front edges of the fireplace,

but 

MUST NEVER

 overlap onto the front face. The joints

between the finished wall and the fireplace top and sides

can only be sealed with a 300° F. (149° C) minimum sealant.
Install optional marble and brass trim surround kits as

desired. Marble, brass, brick, tile, or other non-combustible

materials can be used to cover up the gap between the

sheet rock and the fireplace.
Do not obstruct or modify the air inlet/outlet grilles. When

overlapping on both sides, leave enough space so that the

bottom grille can be raised and the trim door removed.

Positioning the Logs

The gas logs have been factory installed and should not

need to be positioned. After removing the stretch wrapping,

reinstall the logs and grate (see Figure 37). Make sure the

end of the grate with the incomplete cross bar is on the

pilot end of the firebox.
If sooting occurs, the logs might need to be repositioned

slightly to avoid excessive flame impingement.

Step 10. Installing Trim, Logs & Ember Material

Figure 35.   Sealant Material

Placing the Ember Material

See two separate bags of ember material. The bag labeled

Golden Ember (GE-93) is flame colorant material. The bag

labeled Glowing Ember (050-721) is standard glowing ember

material. To place the ember material:
• Remove the wing nuts, glass clips and spring clips around

the glass door. Remove the glass door.

• Ember material is to be placed on burner with caution. Do

NOT

 place ember material over burner port holes. Place

only dime size pieces along outer edges of port trails (see

Figure 37). The bag is for (4) ember applications. Failure to

apply ember material as directed could result in poor light-

ing conditions and sooting problems. After placing ember

material sprinkle GE-93 on top of the burner. Save the re-

maining ember materials for use during fireplace servicing.

CAUTION: IT IS STRONGLY RECOMMENDED THAT

TRIM DOORS WITH OPTIONAL MESH SCREENS BE IN-

STALLED ON PROPANE MODELS.

• Replace the glass door and a front trim door on the unit.

Pull out and latch the glass clips into the groove on the

glass frame. Hand tighten the wing nuts.

Figure 37.   Placement of the Ember Material

ST-38HV

PIER-38HV

TOP EDGE

SIDE EDGE

0” GAP

TOP EDGE

SIDE EDGE

0” GAP

Figure 38.

• Replace the wing nut, glass clips and spring clips.
• If using the optional mesh doors, attach to fireplace glass

doors using the mesh clips provided in the manual bag.

See Figure 38.

PILOT

ASSEMBLY

INCORRECT

EMBER PLACEMENT

CORRECT

EMBER

PLACEMENT

FIRST

GRATE BAR

EMBER

MATERIAL

DO NOT PLACE EMBER
MATERIAL ON FIRST
SECTION OF PORTS
BETWEEN THE PILOT
ASSEMBLY AND THE 
FIRST GRATE BAR.

MESH

CLIP

Содержание Pier-38HV

Страница 1: ...APPLIANCE FOR FUTURE REFERENCE 1 This appliance may be installed in an af termarket permanently located manu factured mobile home where not pro hibited by local codes 2 Thisapplianceisonlyfor usewith...

Страница 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Страница 3: ...Vent System 15 A Vent System Approvals 15 B Installing Vent Components 22 C Vent Termination 25 Step 4 Positioning Leveling and Securing the Fireplace 28 Step 5 The Gas Control Systems 28 Step 6 The G...

Страница 4: ...0 in the United States or to the CSAC22 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting room in the U S A and Canada 1Approvals and Codes High Altitude Ins...

Страница 5: ...e to follow these instructions will void the owner s warranty and may present a fire hazard When planning a fireplace installation it s necessary to determine Where the unit is to be installed The ven...

Страница 6: ...GRILL GAS CONTROLS LABELS GAS LINE ACCESS ELECTRICAL ACCESS 28 3 16 716mm 36 1 16 915mm 38 5 8 981mm 31 3 16 792mm 11 5 16 287mm 22 11 16 576mm 35 3 16 894mm 3 3 8 85mm 2 52mm 2 52mm 3 1 16 79mm 6 5...

Страница 7: ...S LINE ACCESS 2 52MM 3 1 16 79mm 22 11 16 576mm 3 3 8 85mm ELECTRICAL ACCESS 2 52mm 29 1 8 739mm 31 3 16 792mm 38 1 4 972mm 35 3 16 894mm 38 5 8 981mm VENT COLLAR TOP STANDOFFS VENT COLLAR TOP GRILL G...

Страница 8: ...DES THEREFORE YOUR LOCAL BUILD ING CODES MUST BE CHECKED TO DETERMINE THE REQUIREMENTS FOR THESE STEPS Factory built fireplace chases should be constructed in the manner of all outside walls of the ho...

Страница 9: ...the hole is 1 inch 25 4mm above the center of the horizontal vent pipe 37 1 8 943mm Framing should be constructed of 2 X 4 lumber or heavier WARNING FRAMING DIMENSIONS ASSUME USE OF 1 2 INCH THICK WA...

Страница 10: ...2 1054mm 40 3 8 1026mm 1 25mm PIPE CLEARANCE 4 102mm 1 25mm PIPE CLEARANCE 4 102mm Vertical Vent Runs Vertical Vent Runs 40 1016mm 37 7 8 962mm 1 1 2 38mm Horizontal Vent Runs FIRESTOP 1 1 2 38mm FIRE...

Страница 11: ...ing configura tion used Identifying Vent Components The vent systems installed on this gas fireplace may include one two or three 90 elbow assemblies The relationships of vertical rise to horizontal r...

Страница 12: ...10 feet or greater the ver tical baffle kit BAF VERT may be required to improve flame appearance NOTE If the vertical vent component is 10 feet or more you may want to install the vertical baffle to...

Страница 13: ...m VENTING WITH ONE 1 90 ELBOW V FT H FT 1 MIN 305mm 2 MAX 610mm 2 MIN 610mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 86m 4 MIN 1 22m 8 MAX 2 44m 5 MIN 1 5m 10 MAX 3 05m 6 MIN 1 86m 12 MAX 3 6m 7 MIN 2 13m 14 M...

Страница 14: ...10mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 86m 4 MIN 1 22m 8 MAX 2 44m 5 MIN 1 5m 10 MAX 3 04m 6 MIN 1 86m 12 MAX 3 6m 7 MIN 2 13m 14 MAX 4 27m 14 MAX 4 27m V H 37 MAX 11 3m V H H1 1 H V V1 1 NOTE For verti...

Страница 15: ...914 mm 2 MAX 610 mm 6 MAX 1 86 m 4 MIN 1 22 m 2 MAX 610 mm 8 MAX 2 4 m 5 MIN 1 52 m 2 MAX 610 mm 10 MAX 3 04 m 6 MIN 1 86 m 2 MAX 610 mm 12 MAX 3 65 m 7 MIN 2 13 m 2 MAX 610 mm 14 MAX 4 26 m 14 MAX 4...

Страница 16: ...m 4 MAX 1 22 m 3 MIN 914 mm 2 MAX 610 mm 6 MAX 1 86 m 4 MIN 1 22 m 2 MAX 610 mm 8 MAX 2 4 m 5 MIN 1 52 m 2 MAX 610 mm 10 MAX 3 04 m 6 MIN 1 86 m 2 MAX 610 mm 12 MAX 3 65 m 7 MIN 2 13 m 2 MAX 610 mm 14...

Страница 17: ...305mm 2 MAX 610mm 2 MIN 610mm 4 MAX 1 22m 3 MIN 914mm 6 MAX 1 86m 4 MIN 1 22m 8 MAX 2 44m 5 MIN 1 5m 10 MAX 3 04m 6 MIN 1 86m 12 MAX 3 6m 7 MIN 2 13m 14 MAX 4 27m 14 MAX 4 27m V H 37 MAX 11 3m NOTE Fo...

Страница 18: ...ST VENT COM PONENT FAILURE TO SEAL THIS JOINT MAY CAUSE THE FIREPLACE TO OPERATE IMPROPER LY SEE FIGURE 16 Figure 16 Attaching the First Vent Component to the Starting Collars STARTING COLLAR STOVE SE...

Страница 19: ...e Position the firestops on both sides of the hole previ ously cut and secure the firestops with nails or screws The heat shields of the firestops MUST BE placed to wards the top of the hole Continue...

Страница 20: ...sts Figure 22 Ceiling Firestop Ceiling Side If the area above the ceiling is NOT an attic position and secure the ceiling firestop on the ceiling side of the previously cut and framed hole Figure 21 1...

Страница 21: ...lange of the wall firestop to secure the vent pipe in place For trapezoidal cap termination kits Using screws secure the cap to the exterior wall through the flanges built into the cap Figure 24 Round...

Страница 22: ...pened C 9 U S A 12 Canada clearance to permanently closed window D 24 vertical clearance to ventilated soffit located above the termi nal within a horizontal distance of 2 feet 60 cm from the cen ter...

Страница 23: ...FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMI NATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICALWALLAND 2 FEET BELOWA HORIZON TAL OVERHANG NOTE This also pertains to vertical vent systems i...

Страница 24: ...OT BE USED IN CANADA Step 5 The Gas Control Systems WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL Two types of gas control systems are used with these mod els Standing Pilot Ignition and Direct Spa...

Страница 25: ...nfiltration Open the fireplace lower grille insert the gas supply line through the gas line hole and connect it to the shut off valve When attaching the pipe support the control so that the lines are...

Страница 26: ...ox Maintain correct polarity when wiring the junction box Optional Accessories Optional fan and remote control kits require that 110 120 VAC be wired to the fireplace junction box Wall Switch Position...

Страница 27: ...um Vertical and Maximum Horizontal Dimensions of Combustibles above Fireplace FLAME SENSOR SPARKER IGNITION MODULE GAS VALVE ON OFF SWITCH REMOTE OUTLET FAN OUTLET CONNECTORS HOT GROUND NEUTRAL OPTION...

Страница 28: ...d to be repositioned slightly to avoid excessive flame impingement Step 10 Installing Trim Logs Ember Material Figure 35 Sealant Material Placing the Ember Material See two separate bags of ember mate...

Страница 29: ...he glass and run the fireplace for an additional 8 hours This will help to cure the chemicals used in the paint and logs Step 12 Lighting the Fireplace You ve reviewed all safety warnings you ve check...

Страница 30: ...r vacuum the control compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a...

Отзывы: