9

Installing the Fireplace

Step 1.

Locating the Fireplace

The diagram below shows space and clearance require-
ments for locating a fireplace within a room.

Minimum Clearances

 from the Fireplace to Combustible Materials

Inches

mm

Glass Front ........................ 36 ..................... 914
Floor .................................... 0 ........................ 0
Rear ................................... 1/2 ..................... 13
Sides ................................. 1/2 ..................... 13
Top ....................................... 4 ...................... 102
Ceiling* ............................... 31 ..................... 787

 Figure 2.    Fireplace Dimensions, Locations,

                     and Space Requirements

For minimum clearances, see the direct vent termination
clearance diagrams on pages 17 and 18 in this manual.

Minimum Clearances

 from the Vent Pipe to Combustible Materials

Inches

mm

Vertical Sections

. .............. 1................. 25

Horizontal Sections

Top ...................................... 3................. 75
Bottom ................................ 1................. 25
Sides .................................. 1................. 25

At Wall Firestops

Top ................................... 2 1/2 ............. 63.7
Bottom .............................. 1/2 ............... 13
Sides .................................. 1................. 25

* The clearance to the ceiling is measured from the top

of the unit, excluding the standoffs (see Figure 26).

The distance from the unit to combustible construction
is to be measured from the unit outer wrap surface to
the combustible construction,

NOT

 from the screw

heads that secure the unit together.

A

B

C

D

E

F

63

 1/8”

31

 1/2”

44

 5/8”

20

 1/4”

39

 3/4” 1/2”

D

A

A

B

C

E

F

1 INCH

Clearance Requirements

The top, back, and sides of the fireplace are defined by
stand-offs. The minimum clearance to a perpendicular wall
extending past the face of the fireplace is one inch (25 mm).
The back of the fireplace may be recessed 19 1/4 inches
(489mm) into combustible construction.

Constructing the Chase

A chase is a vertical box-like structure built to enclose the
gas fireplace and/or its vent system. Vertical vents that run
on the outside of a building may be, but are not required to
be, installed inside a chase.

CAUTION: TREATMENT OF FIRESTOP SPACERS AND
CONSTRUCTION OF THE CHASE MAY VARY WITH THE
TYPE OF BUILDING. THESE INSTRUCTIONS ARE NOT
SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL
BUILDING CODES. THEREFORE, YOUR LOCAL BUILD-
ING CODES MUST BE CHECKED TO DETERMINE THE
REQUIREMENTS FOR THESE STEPS.

Factory-built fireplace chases should be constructed  in the
manner of all outside walls of the home to prevent cold air
drafting problems. The chase should not break the outside
building envelope in any manner.

This means that the walls, ceiling, base plate and cantilever
floor of the chase should be insulated. Vapor and air infiltra-
tion barriers should be installed in the chase as per regional
codes for the rest of the home. Additionally, Heat-N-Glo rec-
ommends that the inside surfaces be sheetrocked and taped
for maximum air tightness.

To further prevent drafts, the firestops should be caulked to
seal gaps. Gas line holes and other openings should be
caulked or stuffed with insulation. If the unit is being in-
stalled on a cement slab, we recommend that a layer of
plywood be placed underneath to prevent conducting cold
up into the room.

THE CHASE SHOULD BE CONSTRUCTED SO THAT ALL
CLEARANCES TO THE FIREPLACE ARE MAINTAINED
AS SPECIFIED WITHIN THIS INSTALLERS GUIDE.

‹

Содержание CFX-DA

Страница 1: ...writers Laboratories Listed 514 900G 9 02 READ THIS MANUAL BEFORE INSTALLING OR OPERATING THIS APPLIANCE THIS INSTALLERS GUIDE MUST BE LEFT WITH APPLIANCE FOR FUTURE REFERENCE PleasecontactyourHeat N...

Страница 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Страница 3: ...vals 12 B Installing Vent Components 15 C Vent Termination 17 Step 4 Positioning Leveling and Securing the Fireplace 20 Step 5 The Gas Control Systems 20 Step 6 The Gas Supply Line 21 Step 7 Gas Press...

Страница 4: ...2 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting room in the U S A and Canada Approvals and Codes High Altitude Installations U L Listed gas fireplaces ar...

Страница 5: ...Termination Kits as indicated in this guide for exhausting flue gases AND model AK CFX Air Kit for combustion air See venting section for details The Heat N Glo Warranty will be voided by and Heat N...

Страница 6: ...2 977mm 34 1 2 876mm 3 3 8 86mm 5 3 4 146mm GAS LINE ACCESS 19 3 4 501mm 11 5 8 294mm 11 1 16 281mm 22 1 8 562mm 8 5 8 219MM 3 3 8 86mm 5 3 4 146mm 15 1 8 384mm 4 3 4 121mm ELECTRICAL ACCESS 35 889mm...

Страница 7: ...combustible construction Constructing the Chase A chase is a vertical box like structure built to enclose the gas fireplace and or its vent system Vertical vents that run on the outside of a building...

Страница 8: ...g A B C D 43 750 REF Step 2 Framing the Fireplace Fireplace framing can be built before or after the fireplace is set in place Framing should be positioned to accommo date wall coverings and fireplace...

Страница 9: ...AP 1 3 8 INCHES 34 93 mm AT EACH JOINT DV 36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 12D DV 09D DV 06D DV 48D DV 90D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 11 15 16 303mm 5 7 8 149mm 8 5 8 220mm 8 1 2...

Страница 10: ...Guide Termination Kits Vent Components HEAT SHIELD DVK TVCD DVK 01TRD HORIZONTAL TERMINATION WALL FIRESTOP 90 DEGREE ELBOW VERTICAL TERMINATION STORM COLLAR ROOF FLASHING HORIZONTAL PIPE SUPPORT PIPE...

Страница 11: ...ertical run of 40 feet maximum could be introduced at any point of the horizontal run and even right off the top of the unit Total H Horizontal run 50 feet maximum Total V Vertical run 40 feet maximum...

Страница 12: ...14 Figure 8 Straight Up Vertical Venting STRAIGHT UP VERTICAL VENTING V FT 40 MAX 12 4 M CAP V...

Страница 13: ...tical axis If an el bow does not end up in a locked position with the pre ceding component attach with a minimum of two 2 sheet metal screws Figure 10 Adding Venting Components 3 Install Support Brack...

Страница 14: ...bove the center of the horizontal vent pipe For Vertical Runs One ceiling firestop is REQUIRED at the hole in each ceiling through which the vent passes To install firestops for vertical runs that pas...

Страница 15: ...H AS A DECK THE SIDE OF THE CAP MUST BE A MINIMUM OF 6 INCHES 152 MM AWAY FROM A PARALLEL OUTSIDE WALL VENTING TERMINALS SHALL NOT BE RE CESSED INTO A WALL OR SIDING SEE FIGURE 19 FOR VENT TERMINATION...

Страница 16: ...APS IT IS STRONGLY RECOMMENDED WHENEVER POSSIBLE TO USE THE VINYL PROTECTOR KIT 30 minimum for vinyl clad soffits a vent shall not terminate directly above a sidewalk or paved driveway which is locate...

Страница 17: ...FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMI NATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICAL WALLAND 2 FEET BELOW AHORIZON TAL OVERHANG NOTE This also pertains to vertical vent systems...

Страница 18: ...on level and secure the fireplace Figure 21 Proper Positioning Leveling and Securing of a Fireplace Figure 22 Gas Control System Step 5 The Gas Control System WARNING THIS UNIT IS NOT FOR USE WITH SOL...

Страница 19: ...pe and outer casing Step 6 The Gas Supply Line NOTE Have the gas supply line installed in accordance with local building codes by a qualified installer approved and or licensed as required by the loca...

Страница 20: ...MUST SILICONE THE HOLE IN THE FIBER BOX TO SEAL IT FROM THE OUTSIDE HIGH TEMPERATURE 300o F OR 149o C MINIMUM SEALANT Optional Accessories Optional remote control kits require that 110 120 VAC be wire...

Страница 21: ...ANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL USING 300 F MINIMUM ADHESIVE IF NEEDED CAN BE APPLIED AS FACING TO THE FIRE PLACE SURROUND SEE THE...

Страница 22: ...ccompany the logs Save the log instructions with this manual If sooting occurs the logs might need to be repositioned slightly to avoid excessive flame impingement Adjusting the Ignitor Air Deflector...

Страница 23: ...nes to purge themselves of this air Once the purging is complete the fireplace will light and will operate normally Subsequent lightings of the fireplace will not require this purging of air from the...

Страница 24: ...vacuum the control compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a...

Отзывы: