= VENT  TERMINAL

X

= AIR SUPPLY INLET

= AREA WHERE TERMINAL IS NOT PERMITTED

     Figure 19. Vent Termination Minimum Clearances

A

= 12" ....................... clearances above grade, veran-

da, porch, deck or balcony

B

= 12" ....................... clearances to window or door

that may be opened, or to per-
manently closed window.

D*

= 18" ....................... vertical clearance to ventilated

soffit located above the terminal
within a horizontal distance of 2
feet (60 cm) from the center-line
of the terminal

E*

= 18" ....................... clearance to unventilated soffit

F

=  9" ......................... clearance to outside corner

G

= 6" .......................... clearance to inside corner

H

= 3 ft. (Canada) ...... not to be installed above a gas

meter/regulator assembly within
3 feet (90cm) horizontally from the
center-line of the regulator

I

= 3 ft. (U.S.A.)

6 ft. (Canada) ....... clearance to service regulator

vent outlet and electric service

J

= 9" (U.S.A.)

12" (Canada) ......... clearance to non-mechani-

cal air supply inlet to build-
ing or the combustion air in-
let to any other appliance

K

= 3 ft. (U.S.A.)

6 ft. (Canada) ......... clearance to a mechanical

air supply inlet

L** = 7 ft. ......................... clearance  above paved

sidewalk or a paved driveway
located on 

public

 property

M*** = 18" ......................... clearance under veranda,

porch, deck or balcony

N

= 6” ........................... non-vinyl soffit and siding

12” ......................... vinyl soffit and siding

O

= 18” ......................... non-vinyl soffit and siding

42” ......................... vinyl soffit and siding

P

= 8 ft.

D

E

B

L

v

v

v

v

v

v

v

v

B

B

A

H

M

X

J or K

I

A

G

F

U.S.

(3 FT)

B

CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS NECESSARY TO INSTALL THE VINYL PROTECTOR
KIT TO THE TOP OF THE EXTERIOR FIRESTOP (FOR ALL ROUND TERMINATION CAPS). IT IS STRONGLY RECOMMENDED
WHENEVER POSSIBLE TO USE THE VINYL PROTECTOR KIT.

*

 30” minimum for vinyl clad soffits.

  ** a vent shall not terminate directly above a sidewalk or paved

driveway which is located between two single family dwellings
and serves both dwellings.

 *** only permitted if veranda, porch, deck or balcony is fully open on

a minimum of 2 sides beneath the floor.

NOTE 1

: On private property where termination is less than 7 feet

above a sidewalk, driveway, deck, porch, veranda or balcony, use of
a listed cap shield is suggested.

NOTE 2

: Termination in an alcove space (spaces open only on one side

and with an overhang) are permitted with the dimensions specified for
vinyl or non-vinyl siding and soffits. 

1

. There must be 3 feet minimum

between termination caps. 

2.

 All mechanical air intakes within 10 feet

of a termination cap must be a minimum of 3 feet below the termination
cap.

3.

 All gravity air intakes within 3 feet of a termination cap must be

a minimum of 1 foot below the termination cap.

O

N

P

R

Q

(See Note 1)

(See Note 1)

(See Note 2)

NOTE 3

: Local codes or regulations may require different

clearances.

NOTE 4:

Termination caps may be hot. Consider their proximity to

doors or other traffic areas.

WARNING: In the U.S:

 Vent system termination is

NOT

 permitted

in screened porches. You must follow side wall, overhang and
ground clearances as stated in the instructions.

In Canada:

 Vent system termination is

NOT

 permitted in screened

porches. Vent system termination is permitted in porch areas
with two or more sides open. You must follow all side walls,
overhang and ground clearances as stated in the instructions.

Heat-N-Glo assumes no responsibility for the improper perfor-
mance of the fireplace when the venting system does not meet
these requirements.

Q

MIN

     R

MAX

  1 cap

  3 feet

   2 x Q 

ACTUAL

  2 caps

  6 feet

   1 x Q 

ACTUAL

  3 caps

  9 feet

2/3 x Q 

ACTUAL

  4 caps

12 feet

1/2 x Q 

ACTUAL

Q

MIN

 = # termination caps x 3        R

MAX

 = (2 / # termination caps) x Q

ACTUAL

Содержание CFX-DA

Страница 1: ...writers Laboratories Listed 514 900G 9 02 READ THIS MANUAL BEFORE INSTALLING OR OPERATING THIS APPLIANCE THIS INSTALLERS GUIDE MUST BE LEFT WITH APPLIANCE FOR FUTURE REFERENCE PleasecontactyourHeat N...

Страница 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Страница 3: ...vals 12 B Installing Vent Components 15 C Vent Termination 17 Step 4 Positioning Leveling and Securing the Fireplace 20 Step 5 The Gas Control Systems 20 Step 6 The Gas Supply Line 21 Step 7 Gas Press...

Страница 4: ...2 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting room in the U S A and Canada Approvals and Codes High Altitude Installations U L Listed gas fireplaces ar...

Страница 5: ...Termination Kits as indicated in this guide for exhausting flue gases AND model AK CFX Air Kit for combustion air See venting section for details The Heat N Glo Warranty will be voided by and Heat N...

Страница 6: ...2 977mm 34 1 2 876mm 3 3 8 86mm 5 3 4 146mm GAS LINE ACCESS 19 3 4 501mm 11 5 8 294mm 11 1 16 281mm 22 1 8 562mm 8 5 8 219MM 3 3 8 86mm 5 3 4 146mm 15 1 8 384mm 4 3 4 121mm ELECTRICAL ACCESS 35 889mm...

Страница 7: ...combustible construction Constructing the Chase A chase is a vertical box like structure built to enclose the gas fireplace and or its vent system Vertical vents that run on the outside of a building...

Страница 8: ...g A B C D 43 750 REF Step 2 Framing the Fireplace Fireplace framing can be built before or after the fireplace is set in place Framing should be positioned to accommo date wall coverings and fireplace...

Страница 9: ...AP 1 3 8 INCHES 34 93 mm AT EACH JOINT DV 36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 12D DV 09D DV 06D DV 48D DV 90D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 11 15 16 303mm 5 7 8 149mm 8 5 8 220mm 8 1 2...

Страница 10: ...Guide Termination Kits Vent Components HEAT SHIELD DVK TVCD DVK 01TRD HORIZONTAL TERMINATION WALL FIRESTOP 90 DEGREE ELBOW VERTICAL TERMINATION STORM COLLAR ROOF FLASHING HORIZONTAL PIPE SUPPORT PIPE...

Страница 11: ...ertical run of 40 feet maximum could be introduced at any point of the horizontal run and even right off the top of the unit Total H Horizontal run 50 feet maximum Total V Vertical run 40 feet maximum...

Страница 12: ...14 Figure 8 Straight Up Vertical Venting STRAIGHT UP VERTICAL VENTING V FT 40 MAX 12 4 M CAP V...

Страница 13: ...tical axis If an el bow does not end up in a locked position with the pre ceding component attach with a minimum of two 2 sheet metal screws Figure 10 Adding Venting Components 3 Install Support Brack...

Страница 14: ...bove the center of the horizontal vent pipe For Vertical Runs One ceiling firestop is REQUIRED at the hole in each ceiling through which the vent passes To install firestops for vertical runs that pas...

Страница 15: ...H AS A DECK THE SIDE OF THE CAP MUST BE A MINIMUM OF 6 INCHES 152 MM AWAY FROM A PARALLEL OUTSIDE WALL VENTING TERMINALS SHALL NOT BE RE CESSED INTO A WALL OR SIDING SEE FIGURE 19 FOR VENT TERMINATION...

Страница 16: ...APS IT IS STRONGLY RECOMMENDED WHENEVER POSSIBLE TO USE THE VINYL PROTECTOR KIT 30 minimum for vinyl clad soffits a vent shall not terminate directly above a sidewalk or paved driveway which is locate...

Страница 17: ...FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMI NATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICAL WALLAND 2 FEET BELOW AHORIZON TAL OVERHANG NOTE This also pertains to vertical vent systems...

Страница 18: ...on level and secure the fireplace Figure 21 Proper Positioning Leveling and Securing of a Fireplace Figure 22 Gas Control System Step 5 The Gas Control System WARNING THIS UNIT IS NOT FOR USE WITH SOL...

Страница 19: ...pe and outer casing Step 6 The Gas Supply Line NOTE Have the gas supply line installed in accordance with local building codes by a qualified installer approved and or licensed as required by the loca...

Страница 20: ...MUST SILICONE THE HOLE IN THE FIBER BOX TO SEAL IT FROM THE OUTSIDE HIGH TEMPERATURE 300o F OR 149o C MINIMUM SEALANT Optional Accessories Optional remote control kits require that 110 120 VAC be wire...

Страница 21: ...ANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL USING 300 F MINIMUM ADHESIVE IF NEEDED CAN BE APPLIED AS FACING TO THE FIRE PLACE SURROUND SEE THE...

Страница 22: ...ccompany the logs Save the log instructions with this manual If sooting occurs the logs might need to be repositioned slightly to avoid excessive flame impingement Adjusting the Ignitor Air Deflector...

Страница 23: ...nes to purge themselves of this air Once the purging is complete the fireplace will light and will operate normally Subsequent lightings of the fireplace will not require this purging of air from the...

Страница 24: ...vacuum the control compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a...

Отзывы: