HeatLink
®
Mixing Valve Reset Control Stk# 31360
H
e
a
tL
in
k
®
Link
Heat
21
www.heatlinkgroup.com
Range
Display
Description
Page #
Installer
Advanced
Actual
Setting
5,
10
5,
10
35ß to 100ßF, OFF
(2ß to 38ßC, OFF)
35ß to 100ßF, OFF
(2ß to 38ßC, OFF)
ßF, ßC
WWSD Occupied
The system s warm weather shut down
during the occupied (Day) period.
WWSD Unoccupied
The system s warm weather shut
down during the unoccupied (Night) period.
Units
The units of measure that all of the temperatures are
to be displayed in the control.
Exit
This item exits the ADJUST menu by pressing either
the Up or Down button.
(European version only)
ADJUST
ADJUST
ß
F
ADJUST
WWSD
ß
F
OCC
UN
ADJUST
WWSD
ß
F
OCC
Testing the Main Control
The HeatLink
®
Mixing Valve Reset Control Stk# 31360 has a built-in test routine which is used to test the main
control functions. The Stk# 31360 continually monitors the sensors, and displays an error message whenever
a fault is found. See the following pages for a list of the Stk# 31360’s error messages and possible causes.
When the Test button is pressed, the test light is turned on. The individual outputs and relays are tested in the
following test sequence.
Test
not testing
testing
testing paused
off
red
red
Test Sequence
Each step in the test sequence lasts 10 seconds.
During the test routine, the test sequence may be paused by pressing the Test button. Only if there is a mixing demand can the control be paused
in a step. If the Test button is not pressed again for 5 minutes while the test sequence is paused, the control exits the entire test routine. If the test
sequence is paused, the Test button can be pressed again to advance to the next step. This can also be used to rapidly advance through the test
sequence. To reach the desired step, repeatedly press and release the Test button until the appropriate device and segment in the display turn on.
Step 1 - The mixing valve is run fully open.
Step 2 - The mixing valve is run fully closed, and then the system pump (Sys Pmp) is turned on.
Step 3 - The Boiler contact is turned on for 10 seconds. After 10 seconds, the Boiler and Sys Pmp contacts are shut off.
Step 4 - After the test sequence is completed, the control resumes its normal operation.
Adjust Menu / Testing & Troubleshooting
North American & European Versions
Содержание 31360
Страница 29: ...This page is intentionally blank...
Страница 33: ...This page is intentionally blank...
Страница 37: ...This page is intentionally blank...
Страница 42: ...HeatLink Mixing Valve Reset Control Stk 31360 Link Heat www heatlinkgroup com HeatLink 42 User Notes...
Страница 43: ...HeatLink Mixing Valve Reset Control Stk 31360 HeatLink Link Heat 43 www heatlinkgroup com User Notes...