Packaged Thru-The-Wall Heat Pump   

                             

OWNER’S MANUAL

                                                  Heat Controller, Inc.

 

…………………………………………………………………………………………………………… 

 

2.  INSTALLATION     

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRAINAGE HOLE (P13) 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This unit has two alternative drainage methods to 

manage  condensate.  Before  installing  the  unit, 

choose  the  most  suitable  method  for  your 

application. There are 2 drain connections on the 

unit, one is vertical to the floor which is named 

“A” 

and the other one is horizontal to the floor which is 

named 

“B” as shown in P13.   

Method  “A”: 

Employing  this  method  allows  the 

condensate  to  drain  to  the  outdoors.    Begin  by 

drilling a hole through the wall measuring Ø1-

1/4” 

in  the  position  shown  on  the  paper  template. 

Drainage  occurs  by  gravity, thus  it is essential  to 

have  a  minimum  downward  slope  of  at  least  3 

degrees  throughout 

the  drain  line’s  length.

 

Connect the drain pipe (from soft terminal) to the 

unit  (hole 

“A”)  after  unplugging  the  black  rubber 

cap  (see  picture  P13). 

Note: 

If  method 

“A”  is 

used,  do  not  unplug  the  black  rubber  cap  for 

drainage hole 

“B”.     

Method 

“B”:   

Drainage  occurs  indoors  to  an 

external floor drain, water tank, or sump pump.

 

Unplug  the  black  rubber  cap  of  system 

“B”  (see 

picture  P13),  then  connect  the  drain  pipe  (from 

soft terminal) to the unit hole 

“B” after unplugging 

the black rubber cap. Place the hard terminal into 

a water tank, floor drain, or sump pump.   

Note:

 If 

system 

“B” is used, do not unplug the black rubber 

cap for drainage hole 

“A” 

 

2.3 DRILLING THE WALL (P5)   

 

 

 

 

 

 

Please  note:  If  you  are  drilling  the  hole  above 

ground floor  level,  please  ensure  while the  holes 

are  drilled  the  outside  area  is  supervised,  until 

drilling has been completed.   

INTAKE AND OUTLET AIR HOLES, FRESH AIR 

HOLE AND CONDENSATE DRAIN HOLE 

This  operation  should  be  carried  out  using  the 

proper tools (diamond tip or core 

borer’s drills with 

high  twisting  torque  and  adjustable  rotation 

speed).   

 

Fasten the template to the wall taking care to 

check the distance from the floor or ceiling.   

Keep it horizontal by using a level.   

 

Use a pilot drill to mark the centre of each 

core hole to be drilled, and then use a 

Ø6-

3/8” core boring head to drill the two 

holes for intake and outlet the air.   

 

Use a pilot drill to mark the centre of the core 

hole to be drilled, and then use a Ø2-1/8

” 

core boring head to drill the hole for fresh air.   

 

Use a pilot drill to mark the centre of the core 

hole to be drilled, and then use a Ø1-1/4

” 

core boring head to drill the hole for 

condensate drain 

 

All holes should be drilled in one operation. 

 

For detail holes sizing and dimension for the 

holes, please refer to the template on page 

22. 

It  is  recommended  that  the  holes  must  have  a 

slightly downward  slope of 3-5 degree to prevent 

any backflow of water in the pipes.   

 

 

INCLINE/SLOPE 

Содержание RPHE-093G Series

Страница 1: ...Heat Controller Inc 1900 Wellworth Ave Jackson MI 49203 517 787 2100 www heatcontroller com INSTALLATION OPERATION MANUAL Packaged Thru the Wall Heat Pump RPHE 093G Series...

Страница 2: ...PRODUCT READ THIS MANUAL BEFORE INSTALLING OPERATING OR PERFORMING MAINTENANCE ON THE RPHE 093G PACKAGED ROOM AIR HEATPUMP UNIT Do not dispose this product as unsorted municipal waste Collection of s...

Страница 3: ...F THE PIPES 6 2 6 FITTING THE GRATINGS 7 2 7 FITTING THE UNIT ON THE BRACKET 8 3 1 INTRODUCTION OF LCD ICONS 9 3 2 REMOTE CONTROL FUNCTIONS 9 3 3 STANDARD HEATING MODE 10 3 4 SUPER HEATING MODE 11 3 5...

Страница 4: ...unattended Before operating the product remove the unit from its packaging and check it is in good condition Do not operate any product with a damaged cord or plug or after the unit malfunctions has b...

Страница 5: ...ronment They must be removed from the remote control when they reach the end of their life and disposed of responsibly 1 3 RECEIVING THE GOODS The unit is delivered in a protective packaging and is ac...

Страница 6: ...ity Btu h 9300 Heating capacity Btu h 9300 Electric heater capacity Btu h 6800 Power input in cooling W 922 Power input in heating W 864 Power input for Electric heater W 2000 EER Btu W 9 99 COP Btu B...

Страница 7: ...on as described above please check to ensure that the wall can be drilled in the chosen area without interfering with other structures or installations beams studs pipes wires etc Please also ensure t...

Страница 8: ...al into a water tank floor drain or sump pump Note If system B is used do not unplug the black rubber cap for drainage hole A 2 3 DRILLING THE WALL P5 Please note If you are drilling the hole above gr...

Страница 9: ...ll and pipe Insert the fresh air pipe 1 31 32 into the 2 1 16 hole Please center the pipes into the holes in the wall and insulate and seal their perimeters to prevent air and humidity infiltration us...

Страница 10: ...g of the flexible grating and the metal grille to the tube before installation Insert the cords through the centre of the grating Note The flexible grating fits on the outside of the tube and the meta...

Страница 11: ...rely fastened to the wall and that any necessary preparations for electric connection and condensate drainage have been made fasten the unit to its supporting bracket Lift up by holding the sides at t...

Страница 12: ...e unit starts 7 TIMER OFF BUTTON Selects the time the unit stops 8 CLOCK BUTTON Adjusts the clock 9 LOUVER SWING BUTTON Adjusts the airflow direction 10 SLEEP BUTTON Change the set temperature of the...

Страница 13: ...ss the ON OFF button to switch on the unit The unit will begin to run in memory mode 1 Press the MODE button to select heat mode The unit will heat 2 Press UP or DOWN button to select the desired temp...

Страница 14: ...ode The unit will heat 1 3 4 Press UP or DOWN button to select the desired temperature Press the FAN SPEED button to select the fan speed is low speed is middle speed is high speed flashing is auto sp...

Страница 15: ...to select cool mode The unit will cool Press the FAN SPEED button set up the fan speed is low speed is middle speed is high speed flashing is auto speed For auto fan the speed is chosen automatically...

Страница 16: ...to select dry mode The unit will dehumidify FAN SPEED button is disabled Indoor fan speed is always low in dry mode 3 Press the MODE button to select fan mode The unit will run in fan Press the FAN S...

Страница 17: ...either increase in cooling mode or decrease in heating mode by 1 degree after an hour then by another degree an hour later The sleep mode function can be cancelled by pressing the sleep button at any...

Страница 18: ...will run in auto mode 1 2 Press the FAN SPEED button to select the fan speed is low speed is middle speed is high speed flashing is auto speed For auto fan the speed is chosen automatically by the di...

Страница 19: ...etting temperature 4 Press the TIMER OFF button to select the time to switch off the unit Press the button to adjust up 1 hour Press the button to adjust up 1 minute When the time is over the unit wil...

Страница 20: ...ting Mode is ON or OFF 8 Down button Reduces the set temperature 9 Up button Increases the set temperature 10 Fan speed button Selects the desired fan speed low medium high auto 11 Auto fan speed LED...

Страница 21: ...carefully and select the correct operating mode for the correct outdoor temperature condition STANDARD HEATING MODE is recommended mainly in Late Spring Summer Early Autumn when heating is required an...

Страница 22: ...the above wash it do not use hot water and only when it is dried replace it in same way ATTENTION 1 Do not use the unit without the filter 2 Do not use the fresh air system in heating mode below 41 F...

Страница 23: ...n filter which not only has the function of eliminating suspended particles the standard filter has but also eliminates smaller particles such as free chlorine odors colors and toxic particles that ar...

Страница 24: ...anges 3 17 TROUBLESHOOTING POSSIBLE PROBLEMS The unit does not work The unit does not heat or cool the room Strange smell in the room Water drips from the unit The remote control does not work The uni...

Страница 25: ...Heat Controller Inc OWNER S MANUAL Packaged Thru The Wall Heat Pump 22...

Страница 26: ...04 2011...

Отзывы: