MGD-B SERIES GAS FURNACE

 

Heat Controller, Inc.

G18D Series Gas Furnace

 OWNER’S MANUAL

Mortex Products Inc. / Fort Worth, TX 76106

   

 

 

    G18D Owner’s Manual

  

3

12.  After three (3) trials for ignition, if the furnace will     

 

not operate, follow the instructions, “TO TURN OFF 

  

 

GAS TO APPLIANCE” and call your service 

  

 

 

technician or gas supplier.

13.  Replace control access panels. 

AUTO IGNITION GAS VALVE

TO TURN OFF GAS TO FURNACE

Automatic Ignition Models

1.   Set thermostat to the lowest setting.
2.   Turn off all electric power to the appliance if service 

  

 

is to be performed.

3.   Remove control access panels. 
4.   Push the switch on the gas valve to the “OFF”

position. DO NOT FORCE. 

 5.

 

Replace control access panels.

SEQUENCE OF OPERATION

  

 

 

Continuous Blower 

On cooling / heating thermostats with a 

AUTO

 /

 ON

  fan 

switch, when the fan switch is set to the 

ON 

position, 24 VAC 

is sent from the red thermostat wire to the green thermostat 
wire energizing the blower motor cooling fan terminal (“

G

” 

Terminal) on the control board. The control board switches 
115 VAC to the 

COOL 

terminal on the control board and the 

motor runs on the selected blower motor speed tap. 

 

Intermittent Blower - Cooling 

On cooling / heating thermostats with a 

AUTO

 /

 ON

  fan 

switch, when the fan switch is set to the 

AUTO 

position and 

the thermostat calls for cooling, 24 VAC is sent from the red 
thermostat wire to the green thermostat wire and the yellow 
thermostat wire. The green thermostat wire will energize the 
blower motor cooling fan terminal (“

G”

 Terminal) on the 

control board. The control board switches 115 VAC to the 

COOL 

terminal on the control board and the motor runs on 

the selected blower motor speed tap. The yellow thermostat 
wire 

(“Y”)

 will send 24 VAC to the contactor on the outdoor 

unit causing the contactor to close, energizing the 
compressor and the outdoor fan motor. 

Intermittent Blower - Heating 

On cooling / heating thermostats with an 

AUTO

 /

 ON

 fan 

switch, when the fan switch is set to the 

AUTO 

position and 

the thermostat calls for heating, 24 VAC is switched from the 
red thermostat wire to the white thermostat wire. The 
control board has a programmed time delay period that will 
place 115 VAC on the 

HEAT 

terminal on the control board at 

the completion of the time delay and allow the blower motor 
run on the selected blower motor speed tap. 

Power ON 

When the line power (115 VAC) is turned on to the furnace 
the 115 VAC is applied between the 

L1 

terminal and the 

neutral terminal on the control board. The step down 
transformer applies 24 VAC to the “

24 VAC

” and the “

COM

” 

terminals on the control board. The control board places 24 
VAC from the grey wire

 

on the 9 pin plug, thru the upper limit 

control (Manual Reset), thru the blue wire to the main limit 
(Auto Reset) and returns 24 VAC signal thru the orange wire 
back to the 9 pin plug on the control board. This signal 
indicates to the control board software that the limit circuit is 
closed. The control board software then checks for a 24 VAC 
signal from the pressure switch. If the pressure switch is open 
the software checks the flame sensor to determine if a flame 
is present. If no flame is present then the software places the 
control board into the ready mode which is indicated by a 
steady green diagnostic indicator light. 

NOTE: 

 If a limit is open  when the line power (115 VAC) is turned on; 
the control board software switches 115 VAC to the 

HEAT  

terminal on the control board sending 115 VAC to the indoor 
fan motor energizing the indoor fan on the selected speed 
tap and the diagnostic led will flash four flashes. 

NOTE:

  

If the pressure switch electrical contacts are stuck closed 
nothing will happen until there is a call for heat. Upon a call 
for heat the control board software will wait 30 seconds for 
the pressure switch electrical contacts to open. During this 
time, none of the components will operate. After 30 seconds 
the diagnostic indicator led will flash two flashes and none of
the components will operate.

Heating Cycle

 

When the thermostat switch is set to the 

HEAT

 position, the 

thermostat fan switch is set to the

 AUTO

 position and the 

thermostat calls for heat; 24 VAC is switched from the red 
thermostat wire to the white thermostat wire  sending a 24 
VAC signal to the 

“W”

 terminal on the control board. This 

signal tells the control board software there is a call for heat. 
The control board switches 115 VAC to the black wires on the 
6 pin plug located at the bottom right side of the control 
board, energizing the combustion air booster motor. 

 

3

Содержание MGD-B Series

Страница 1: ...OWNER S MANUAL Manufactured Home Downflow Gas Furnace MGD B Series Heat Controller Inc 1900 Wellworth Ave Jackson MI 49203 517 787 2100 www heatcontroller com ...

Страница 2: ...Owner s Manual MGD B SERIES GAS FURNACE Heat Controller Inc 1 ...

Страница 3: ...Heat Controller Inc MGD B SERIES GAS FURNACE Owner s Manual See warranty card that was provided with your unit 2 ...

Страница 4: ...ill place 115 VAC on the HEAT terminal on the control board at the completion of the time delay and allow the blower motor run on the selected blower motor speed tap Power ON When the line power 115 VAC is turned on to the furnace the 115 VAC is applied between the L1 terminal and the neutral terminal on the control board The step down transformer applies 24 VAC to the 24 VAC and the COM terminals...

Страница 5: ...the pressure ports on the pressure switch providing the negative and positive pressures to the switch If the pressures applied to the positive and negative ports Differential Pressure of the pressure switch exceed 0 2 wc 05 wc the switch electrical contacts close providing a 24 VAC signal back to the control board thru the blue wires attached to the 9 pin plug indicating to the control board softwa...

Страница 6: ... turns on the blower when sufficient heat has built up inside the furnace Gas Valve The gas valve for all models are 100 shut off type and will fail safe if for some reason the gas is turned off INSPECTION AND MAINTENANCE BY THE HOMEOWNER Make a visual inspection of the furnace every 30 days Do the following Filters Clean filters at least every 3 months and replace as needed Size 16 x20 x1 Motor L...

Страница 7: ... 7 MICROAMPS 0 000001 0 0000037 AMPS WITH THE CURRENT METER CONNECTED IN SERIES BETWEEN THE FLAME SENSOR AND THE CONTROL BOARD THEN UNPLUG THE 9 PIN PLUG AT THE CONTROL BOARD AND PERFORM A RESISTANCE TEST OHM Ω TEST ON THE YELLOW FLAME SENSOR WIRE IF THE OHMS Ω METER DOES NOT INDICATE A READING OR SHOWS THE SYMBOL SHOWS A OPEN WIRE THEN REPLACE THE FLAME SENSOR WIRE OR THE WIRE HARNESS IF THE OHMS...

Страница 8: ... TERNINALS THEN GO TO STEP 6 IF THERE IS 24 VAC TO THE GAS VALVE ELECTRICAL TERMINALS THE GAS VALVE TOGGLE SWITCH IS IN THE ON POSITION AND THERE IS NO FLAME PRESENT THEN CHECK THE GAS VALVE OUTLET MANIFOLD PRESSURE TO DETERMINE IF THERE IS 3 5 INCHES OF WATER INWC GAS PRESSURE FOR NATURAL GAS OR 10 0 INCHES OF WATER INWC GAS PRESSURE FOR PROPANE GAS WHEN THERE IS 24 VAC PRESENT AT THE ELECTRICAL ...

Страница 9: ...VAC BETWEEN BOTH CONTACTS AND COMMON AND THE COMBUSTION AIR BOOSTER MOTOR IS NOT OPERATING REPLACE THE PRESSURE SWITCH CALL FOR HEAT BURNER FLAME WILL NOT LIGHT FOUR FLASHS OPEN LIMIT CONTROL USE A VOLT METER TO CHECK FOR 24 VAC AT THE UPPER LIMIT CONTROL AND THE PRIMARY LIMIT CONTROL TO CHECK THE VOLTAGE PLACE ONE PROBE OF THE VOLT METER ON THE TERMINAL OF THE LIMIT CONTROL AND THE OTHER PROBE ON...

Страница 10: ...04 2009 07 2009 ...