Multi type Air Conditioner
Troubleshooting Guide
Error
Title
Cause of error
Check point & Normal condition
code
33
D-Pipe Temp. High
• Discharge sensor
temp. high
• Check the discharge pipe sensor.
• Check the install condition for over load.
• Check the leakage of refrigerent.
• Check the SVC V/V open.
Error
Title
Cause of error
Check point & Normal condition
code
51
Capacitor error
• Over Capacitor com-
bination
• Check the indoor unit capacity.
• Check the combination table
❑
Check Point
1. Check the indoor unit capacity.
2. Check the combination table.
★
In the tropical model case
➔
single cycle has no error for over capacity.
❑
Check Point
1. Check the install condition for over load.
2. Check the SVC V/V open.
3. Check the leakage of refrigerent.
4. Check the constant compressor.
COMP OFF
LEV OPEN(16PULSE/MIN)
LEV OPEN(10PULSE/MIN)
NORMAL
115
°
C(239
°
F)
100
°
C(212
°
F)
95
°
C(203
°
F)