24 Multi type Air Conditioner
Outdoor
Align the center of the pipings and sufficiently tighten
the flare nut by hand.
Finally, tighten the flare nut with torque wrench until the
wrench clicks.
• When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow on
the wrench.
Liquid side piping
Torque wrench
B-UNIT
A-UNIT
Gas side piping
Outdoor unit
Flaring Work and Connection of Piping
mm
inch
kgf.m(lbf-ft)
Ø6.35
1/4
1.8~2.5(13)
Ø9.52
3/8
3.4~4.2(30)
Outside diameter
Torque