DVC/DVH Inverter Mini-Split
Heat Controller
36
10.3.5 Open or Short Circuit of Temperature Sensor Diagnosis and Solution (E5)
Error Code
E5
Malfunction
If the sampling voltage is lower than 0.06V or higher than 4.94V,
the LED will display the this error code.
Possible Causes
●
Wiring Error
●
Faulty Sensor
Trouble shooting:
Check the connections
between temperature
sensor and main PCB.
Are the connections
good?
Correct the connections.
No
Yes
Yes
Replace indoor or
outdoor main PCB.
Replace the sensor and
check if the problem happen
again?
Check the resistance value
of the sensor via
table1(p64)and table
2(p65), is it normal?
No
Disconnect the temperature sensor from PCB,
measure the resistance value of each winding by
using the multi-meter.
Temperature Sensors:
T1:
Room Temperature Sensor
T2:
Indoor Coil Temperature Sensor
T3:
Outdoor Coil Temperature Sensor
T4:
Outdoor Ambient Temperature Sensor
T5:
Compressor Discharge Temperature Sensor
Check if the resistance value
of the sensor is normal
*See following tables