23
Heat Controller
DVC/DVH Inverter Mini-Split
21
9.3.2 Outdoor Fan Operation-Heating Mode
The outdoor fan operates based on the Outdoor
Ambient Temperature (T4):
17
15
Low
High
When the outdoor ambient temperature T4 is
above 63°F(17°C), the outdoor fan runs low
speed, however when the temperature is below
this, the fan speed increases to high and
continues to run at high speed when the
temperature
is 63°F(17°C) or below.
9.3.3 Indoor Fan Operation-Heating Mode
The indoor fan runs based on the evaporator
coil temperature (T2) as follows:
TEL8
TEL7
TEL6
TEL5
T2
TEL4
Setting
Low
Breeze
Off
TEL3
Medium
TEL2
TEL0
Super
Breeze
TEL1
TEL0
TEL1
TEL2
TEL3
TEL4
TEL5
TEL6
TEL7
TEL8
75°F
(24
°C)
83°F
(28
°C)
90°F
(32
°C)
95°F
(35
°C)
97°F
(36
°C)
102°F
(39
°C)
111°F
(44
°C)
Notes:
•
If the compressor stops due to the room
temperature rising, the indoor fan will be
forced to run for 127seconds in breeze
mode. During this period, the
anti-cold-wind is disabled.
•
If the unit runs in forced operation mode,
the indoor fan will run with rating speed
and the anti-cold-wind function is
disabled.
9.3.3.1 Auto Fan Operation-Heating Mode
When the fan is placed in auto mode, while the
unit is in cooling mode, the auto fan operation
takes into account the difference (ΔT) in indoor
room temperature (T1) and the set point
temperature (Ts):
2.5
2
High
Low
1
Medium
1.5
The indoor fan will run at low speed when the
ΔT is greater than 2.5Degrees, medium speed
when the ΔT is between 2.5
and 1.5 degrees,
and high speed between 1.5 and 1 degrees or
less.
9.4 Defrost Mode
9.4.1 Defrosting Conditions:
When T4
>32°F(0°C),
if the following two items
are satisfied, the units start defrosting:
1. T3<
38°F(3°C)
for 40 minutes and T3
remains lower than
21°F(
-
6°C)
for more
than 3 minutes.
2. T3<
38°F(3°C)
for 80 minutes and T3
remains lower than 25
°F(
-4
°C)
for more
than 3 minutes.
When T4
<32°F(0°C), both the first and second
conditions are satisfied, then the program will
determine if T2 has decreased more than
41°F(5°C) or not
. When T2 has decreased
more than
41°F(5°C), the unit enter the defrost
mode.
ΔT =T1-Ts
ΔT°
T2°
T4
°F (°C)
63 (17)
59 (15)
Содержание A-DVC09SD-0
Страница 14: ...14 DVC DVH Inverter Mini Split Heat Controller B DVC24SD 1 B DVH24SD 1 ...
Страница 44: ...44 DVC DVH Inverter Mini Split Heat Controller P V P W ...
Страница 45: ...45 Heat Controller DVC DVH Inverter Mini Split P N ...
Страница 51: ...51 Heat Controller DVC DVH Inverter Mini Split This page is left intentionally blank ...