Finishing
A. Facing Material
Figure 11.1 Noncombustible Facing Diagram
Fire Risk.
Finish all edges and fronts to clearances and
specifi cations listed in manual.
• Black metal appliance front may be covered with
noncombustible material only.
• Do NOT overlap combustible materials onto appliance
front.
• Install combustible materials up to specifi ed clearances
on top, front and side.
• Seal joints between the fi nished wall and appliance top
and sides using only a 150º C minimum sealant.
SEALANT MATERIAL
NON-COMBUSTIBLE ZONE
FINISH WALL MATERIAL MAY BE
COMBUSTIBLE - TOP AND SIDES
203 mm
740 mm
0 mm
0 mm
0 mm
B. Mantel Projections
No mantels are allowed below 200 mm when using Stu-
dio-CE fronts.
Risk of Fire
• Non-combustible clearances
MUST
be
maintained.
• Sheetrock, wood or other combustibles must
NOT
be used as sheathing or facing in the non-
combustible zone.
• See
Sections 3
and
11
for proper clearances.
• See
Section 1
for combustible/non-combustible
defi nitions.
WARNING
WARNING
Figure 11.2 Minimum vertical and maximum horizontal
dimensions of combustibles above appliance
when using the DF-SOHOCE-BK dress guard.
127
178
102
OPENING OF FIREPLACE
76
127
203
305
51
229
254
279
152
26
407
152
178
203
229
254
279
305
330
356
381
Note: All dimensions are shown in millimeters