I. Install Metal Roof Flashing
• See minimum vent heights for various pitched roofs
(Figure 10.16) to determine the length of pipe to extend
through the roof.
• Slide the roof flashing over the pipe sections extending
through the roof as shown in Figure 10.17.
Figure 10.16 Minimum Height From Roof To Lowest Discharge
Opening
NOTICE:
Failure to properly caulk the roof flashing and
pipe seams may permit entry of water entry.
• Caulk the gap between the roof flashing and the outside
diameter of the pipe.
• Caulk the perimeter of the flashing where it contacts the
roof surface. See Figure 10.17.
• Caulk the overlap seam of any exposed pipe sections
that are located above the roof line.
Important Notice:
Heat shields may not be field constructed.
H. Heat Shield Requirements for Horizontal
Termination
WARNING! Risk of Fire!
To prevent overheating and fire,
heat shields must extend through the entire wall thick-
ness.
•
DO NOT
remove the heat shields attached to the
wall shield firestop and the horizontal termination cap
(shown in Figure 10.14).
• Heat shields must overlap 1-1/2 in. (3,8 cm) mini-
mum.
There are two sections of the heat shield. One section
is factory-attached to the wall shield firestop. The other
section is factory-attached to the cap. See Figure 10.14.
If the wall thickness does not allow the required 1-1/2 in.
(3,8 cm) heat shield overlap when installed, an extended
heat shield must be used.
• If the wall thickness is less than or 4-3/8 in. (11,1 cm),
the heat shields on the cap and wall shield firestop
must be trimmed. A minimum 1-1/2 in. (3,8 cm) overlap
MUST be maintained.
• Use an extended heat shield if the finished wall
thickness is greater than 7-1/4 in. (18,4 cm).
• The extended heat shield may need to be cut to length
maintaining sufficient length for a 1-1/2 in. (3,8 cm)
overlap between heat shields.
• Attach the extended heat shield to either of the existing
heat shields using the screws supplied with the extended
heat shield. Refer to vent components diagrams in the
back of this manual.
• Rest the small leg on the extended heat shield on top
of the pipe section to properly space it from the pipe
section.
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
VERTICAL
WALL
TERMINATION
CAP
HORIZONTAL
OVERHANG
30,5 cm
X
ROOF PITCH
IS X/ 30,5 cm
LOWEST
DISCHARGE
OPENING
51 cm MIN.
61 cm MIN.
Angle
H (Min.) cm
0°-26,6° ............................................................... 30*
26,6°-30,3° .......................................................... 38*
30,3°-33,7° .......................................................... 46*
33,7°-36,9° .......................................................... 61*
36,9°-39,8° ..........................................................
76
39,8°-42,5° .......................................................... 99
42,5°-45,0° ........................................................
1
22
45,0°-49,4° ........................................................
1
52
49,4°-53,1° ........................................................
1
83
53,1°-56,3° ........................................................2 13
56,3°-59,0° ........................................................2 29
59,0°-60,3° ........................................................2 44
*91 cm minimum in snow regions