Heat & Glo • SL350TRSI-N-CE, SL350TRSI-PB-CE • 2033-980 Rev. J • 3/13
13
Finishing
A. Mantel and Wall Projections
WARNING! Risk of Fire!
Comply with all minimum clear
-
ances as specified. Framing closer than the minimums list
-
ed must be constructed entirely of noncombustible materials
(i.e., steel studs, concrete board, etc.)
Figure 13.2 Combustible Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
Figure 13.1 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles
Combustible Mantels
Combustible Mantel Legs or Wall Projections
B. Facing Material
• Metal front faces may be covered with non-combustible
materials only.
• Facing and/or finishing materials must not interfere with
air flow through louvers, operation of louvers or doors,
or access for service.
• Facing and/or finishing materials must never overhang
into the glass opening.
• Observe all clearances when applying combustible
materials.
• Seal joints between the finished wall and appliance top
and sides using a 300 ºF (149 ºC) minimum sealant.
WARNING! Risk of Fire! DO NOT
apply combustible
materials beyond the minimum clearances. Comply with
all minimum clearances to combustibles as specified in
this manual. Overlapping materials could ignite and will
interfere with proper operation of doors and louvers.
Figure 13.3 Noncombustible Facing Diagram
B
A
A
B
SL350TRSI-N-CE
SL350TRSI-PB-CE
Centimeters
74,1
83,7
Note:
All measurements in centimeters.
Note:
Measurement is taken from top of the opening,
NOT the top of the fireplace.
7,6
15,2
17,8
20,3
22,9
27,9
30,5
5,1
7,6
10,2
12,7
30,5
27,9
25,4
22,9
20,3
17,8
15,2
5,1
10,2
12,7
25,4
TOP FRONT EDGE
OF FIREPLACE
NON-COMBUSTIBLE
BOARD
91,44 cm MAXIMUM
TOP VIEW
7,3 cm*
MINIMUM
1,3 cm*
MINIMUM
* Add 1,3 cm for rear vent