23
Heat & Glo • SL350TRSI-N-CE, SL350TRSI-PB-CE • 2033-980 Rev. J • 3/13
D. Mantel and Wall Projections
WARNING! Risk of Fire!
Comply with all minimum clear
-
ances as specified. Framing or finishing material closer than
the minimums listed must be constructed entirely of non-
combustible materials (i.e., steel studs, concrete board, etc).
Combustible Mantels
Combustible Mantel Legs or Wall Projections
Note:
All measurements in centimeters.
Note:
Measurement is taken from top of the opening,
NOT the top of the fireplace.
Figure 5.5 Clearances to Mantel Legs or Wall Projections
(Acceptable on both sides of opening.)
Figure 5.4 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles
Figure 5.6 Non-combustible zone
Figure 5.7
7,6
15,2
17,8
20,3
22,9
27,9
30,5
5,1
7,6
10,2
12,7
30,5
27,9
25,4
22,9
20,3
17,8
15,2
5,1
10,2
12,7
25,4
TOP FRONT EDGE
OF FIREPLACE
NON-COMBUSTIBLE
BOARD
If joints between the finished walls and the fireplace sur-
round (top and sides) are sealed, a 150º C minimum seal-
ant material must be used. These joints are not required
to be sealed. Only non-combustible material (using 150°
c. Minimum adhesive, if needed) can be applied as facing
to the fireplace surround. See Figure 5.7.
FINISH WALL MATERIAL MAY BE
COMBUSTIBLE - TOP AND SIDES
NON-COMBUSTIBLE
BOARD
HIGH TEMPERATURE (150 ºC MIN.)
TOP AND SIDE SEAL JOINT
Note:
Zero clearance finishing allowed on sides of surround
and top of non-combustible board.
91,44 cm MAXIMUM
TOP VIEW
7,3 cm*
MINIMUM
1,3 cm*
MINIMUM
* Add 1,3 cm for rear vent
1,3 cm
SHEETROCK
8,89 cm
1,3 cm
NON-COMBUSTIBLE ZONE
NON-COMBUSTIBLE
BOARD SHIPPED
WITH APPLIANCE