Heat & Glo • RED60 Installation Manual • 2159-980 Rev. D • 11/13
FAN
INTERMITTENT
PILOT IGNITOR
ORANGE
WHITE
SENSOR
WIRE
IGNITER
WIRE
6VDC TRANSFORMER
ELECTRICAL
ACCESS KNOCKOUT
APPLIANCE ON/OFF CONTROL
HARNESS
THERMO SNAP DISC
HARNESS
JUMPER
HARNESS
AUX300
MODULE
WALL SWITCH
JUMPER WIRE
ACCESSORY
CABLE
IPI WIRE
HARNESS
MALE/FEMALE
WIRE ASSEMBLY
8K1-PVI
TO PVI-DVP
ORANGE
GREEN
GREEN
VALVE
JUMPER
JUMPER
JUMPER
HI LIMIT SWITCHES
GROUND TO
FIREPLACE CHASSIS
JUNCTION BOX
TO FAN OUTLET
ON JUNCTION
BOX
Figure 4.19 RED60 PVI-DVP with IntelliFire Plus Pilot Ignition Wiring Diagram
Vacuum Switch Orientation
WARNING! Risk of Fire and Explosion!
Install vacuum
switch on a vertical plane. Failure to follow instructions could
result in
fi
re or explosion.
If the PVI is mounted in a vertical position, the vacuum
switch needs to be moved. To do this, loosen and remove
the two nuts currently using to secure it to the inside wall
of the PVI. Move and secure the vacuum switch onto the
adjacent wall using the two bolts that are sticking out of
the surface. See Figure 4.20 for the location on the vert-
Installation Inspection
1. Follow safety inspection procedures recommended by
national, provincial, and/or local codes.
2. Be certain all electrical connections are properly made
and secure.
3. Visually inspect the vent system and determine that
there is no
fl
ue gas spillage, blockage or restriction,
leakage, corrosion or other unsafe de
fi
ciencies.
4. Place the
fi
replace in operation and determine that the
burner and power vent are operating properly. The
main burner should show no signs of
fl
oating, lifting, or
fl
ashbacks.
WARNING:
If any unsafe condition is determined when
inspecting the installation and operation of the
fi
replace
and Power Vent, the equipment should be shut off. Cor-
rections
MUST
be made before the equipment is put into
continuous operation.
cal plane in regards to horizontal or vertical orientation.
The vacuum switch must be installed on a vertical plane.
If the PVI is orientated horizontally in the vent run, install
the vacuum switch in location “A” noted in Figure 4.20. If
the PVI is orientated vertically in the vent run, install the
vacuum switch in location “B” in Figure 4.20. Follow in-
structions on label attached inside the PVI. Remove the
label as directed. See Figure 4.21 for the switch and wire
orientation.
Figure 4.20 Vacuum Switch Location - Horizontal/Vertical Orientation
PVI VERTICAL
PVI HORIZONTAL
VACUUM
SWITCH
B
A