background image

Heat & Glo  • GEM-36B  •  2095-900  Rev. H  •  3/06

43

Troubleshooting

14

With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service.  If you do
experience a problem, this troubleshooting guide will assist a qualified service person in the diagnosis of a problem and the
corrective action to be taken. This troubleshooting guide can only be used by a qualified service technician.

A.   Intellifire Ignition System

Symptom

Possible Causes

Corrective Actions

1.

 The

ignitor/module
makes noise, but no

spark.

a. Incorrect wiring.

Verify "S" wire (white) for sensor and "I" wire (orange) for ignitor are
connected to correct terminals on module and pilot assembly. Reversed wires
at the module may cause system to make sparking noise, but spark may not

be present at pilot hood.

b. Loose

connections or
electrical shorts in

the wiring.

Verify no loose connections or electrical shorts in wiring from module to pilot
assembly. Rod closest to pilot hood should be ignitor. Verify connections

underneath pilot assembly are tight; also verify connections are not grounding

out to metal chassis, pilot burner, pilot enclosure, mesh screen if present, or
any other metal object.

c. Ignitor gap is too

large.

Verify gap of igniter to pilot hood. The gap should be approximately .17 inch
or 1/8 inch.

d. Faulty module.

Turn ON/OFF rocker switch or wall switch to OFF position. Remove ignitor
wire "I" from module. Place ON/OFF Rocker switch or wall switch in ON

position. Hold ground wire about 3/16 inch away from "I" terminal on module.

If there is no spark at "I" terminal module must be replaced. If there is a spark
at "I" terminal, module is fine. Inspect pilot assembly for shorted sparker wire
or cracked insulator around electrode.

2.

  Pilot won't light,

there is no noise or

spark.

a. A shorted or

loose connection in

wiring configuration
or wiring harness.

Remove and reinstall the wiring harness that plugs into module. Verify there is

a tight fit. Verify pilot assembly wiring to module. Remove and verify continuity
of each wire in wiring harness.

b. Improper wall

switch wiring.

Verify that 110/VAC power is "ON" to junction box.

c.  Module not
grounded.

Verify black ground wire from module wire harness is grounded to metal
chassis of appliance.

d.  Faulty module.

Turn ON/OFF rocker switch or wall switch to OFF position. Remove ignitor
wire "I" from module. Place ON/OFF Rocker switch or wall switch in ON

position. Hold ground wire about 3/16 inch away from "I" terminal on module.

If there is no spark at "I" terminal module must be replaced. If there is a spark
at "I" terminal, module is fine. Inspect pilot assembly for shorted sparker wire
or cracked insulator around electrode.

3.

 Pilot lights but

continues to spark,
and main burner will

not ignite. (If the
pilot continues to

spark after the pilot

flame has been lit,
flame rectification

has not occurred.)

a.  A shorted or

loose connection in

sensor rod.

Verify all connections to wiring diagram in manual. Verify connections

underneath pilot assembly are tight. Verify connections are not grounding out

to metal chassis, pilot burner, pilot enclosure or screen if present, or any other

metal object.

b.  Poor flame
rectification or

contaminated
sensor rod.

Verify that flame is engulfing sensor rod. If the pilot assembly does not have a
ground strap, consider installing one to increase flame rectification. Verify
correct pilot orifice is installed and inlet gas specifications. Flame carries

rectification current, not the gas. If flame lifts from pilot hood, the circuit is
broken. A wrong orifice or too high an inlet pressure can cause pilot flame to
lift. The sensor rod may be contaminated. Clean sensor rod with emery cloth.

c.  Module is not
grounded.

Verify that module is securely grounded to metal chassis of appliance. Verify

that wire harness is firmly connected to module.

Содержание GEM-36B

Страница 1: ...ppliance Alert children and adults to hazards of high temperatures Do NOT operate with protective barriers open or removed Keep clothing furniture draperies and other combustibles away Glass and other...

Страница 2: ...can be found on the rating plate usually located in the control area of the appliance Homeowner Reference Information Heat Glo a of Hearth Home Technologies Inc brand 20802 Kensington Boulevard Lakevi...

Страница 3: ...C Installing non combustible Facing Material 19 D Installing Flue Restrictors 20 E Adjusting Pilot Shield 20 Section 8 Installing Vent Pipe A Assembly of Vent Sections 21 B Disassembly of Vent Sectio...

Страница 4: ...iters Laboratories Inc UL TYPE Direct Vent Gas Fireplace Heater STANDARD ANSI Z21 88 2002 CSA2 33 M02 UL307B Model U S or Canada Maximum Input BTUH Minimum Input BTUH Orifice Size DMS GEM 36B NG US 0...

Страница 5: ...nt size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equip...

Страница 6: ...The vent system components and trim doors are shipped in separate packages The gas logs may be packaged separately and must be field installed Report to your dealer any parts damaged in shipment parti...

Страница 7: ...g Appliance Location When selecting a location for your appliance it is important to consider the required clearances to walls see Figure 3 1 Figure 3 1 Appliance Locations A B C D E F G Inches 50 1 2...

Страница 8: ...revent drafts the wall shield and ceiling firestops should be caulked with high temperature caulk to seal gaps Gas line holes and other openings should be caulked with C Clearances Figure 3 2 Clearanc...

Страница 9: ...gure 3 6 Hearth Extension Dimensions A B in 41 1 2 8 mm 1054 203 Figure 3 5 1 in BOTTOM OF FIREPLACE TO BOTTOM OF NON COMBUSTIBLE FACING MATERIAL 37 1 8 in MIN CLEARANCE TO CEILING COMBUSTIBLE SHEATHI...

Страница 10: ...er 18 12 to 20 12 7 5 Over 20 12 to 21 12 8 0 Figure 4 1 Figure 4 2 Minimum Height from Roof to Lowest Discharge Opening Termination Locations 4 Measure horizontal clearances from this surface Measure...

Страница 11: ...with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air intakes within 10 fe...

Страница 12: ...ength of straight pipe is allowed between two 450 elbows see Figure 5 1 Figure 5 1 A Vent Table Key The abbreviations listed in this vent table key are used in the vent diagrams Symbol Description V1...

Страница 13: ...5 ft 1 5 m 3 ft 914 mm 8 ft 2 4 m 4 ft 1 2 m 11 ft 3 4 m 5 ft 1 5 m 14 ft 4 3 m 6 ft 1 8 m 17 ft 5 2 m 7 ft 2 1 m 20 ft 6 1 m 8 ft 2 4 m 23 ft 7 0 m V1 40 ft 12 2m Maximum H1 23 ft 7 0 m Maximum V1 H1...

Страница 14: ...17 5 2 m 7 ft 2 1m 22 6 7 m H1 H2 22 ft 6 7 m Max V1 V2 H1 H2 62 ft 18 9 m Max H1 V2 H2 V1 NOTE Must have a one foot minimum vertical vent before attaching a 90o elbow to the unit Figure 5 6 V1 40 FT...

Страница 15: ...ft 18 9 m Max NOTE Must have a one foot minimum vertical vent before at taching a 90o elbow to the unit Figure 5 8 H1 V2 H2 V1 INSTALLED HORIZONTALLY Figure 5 7 Two Elbows V1 V2 Minimum H1 Maximum 1 f...

Страница 16: ...pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe may cause fire B Wall Penetration Framing Figure 6 1 Pipe Clearances 1 in CLEARANCE...

Страница 17: ...e vent pipe Installing Attic Shield Note An additional ceiling firestop is not required if attic shield is used Frame opening for attic shield Attic shield may be installed above or below ceiling see...

Страница 18: ...ure 7 1 Remove 5 screws from upper shelf see Figure 7 2 Bend sheetmetal brace away from unit see Figure 7 2 until tabs on shelf are released from standoffs Remove 3 screws at bottom of sheetmetal brac...

Страница 19: ...spacers Failure to keep insulation framing or other material away from the appliance may cause fire Place the appliance into position Level the appliance from side to side and front to back Shim the a...

Страница 20: ...ling Flue Restrictors Locate the flue restrictors inside the unit to the left of the control panel Use the following table to determine which restrictors to use for the vent run Vent Run Vertical 15 f...

Страница 21: ...r than 1 inch to hold outer pipe sections together If predrilling holes do NOT penetrate inner pipe Figure 8 2 Lances Figure 8 3 A B Figure 8 4 Figure 8 5 Seams Note Make sure the seams are not aligne...

Страница 22: ...he inner and outer flues of the slip section can be cut to the desired length Assembling Minimum Installations MI Sections MI sections are non unitized so that they can be cut to a certain length Cut...

Страница 23: ...ipe must be supported every 8 feet after the 25 foot maximum unsupported rise The vent support or plumber s strap spaced 120 apart may be used to do this see Figure 8 9 Horizontal Sections Horizontal...

Страница 24: ...the pipe section see Figure 8 13 Installing the Horizontal Termination Cap Vent termination must not be recessed in the wall Siding may be brought to the edge of the cap base Flash and seal as approp...

Страница 25: ...Pitch H Min Ft Flat to 6 12 1 0 Over 6 12 to 7 12 1 25 Over 7 12 to 8 12 1 5 Over 8 12 to 9 12 2 0 Over 9 12 to 10 12 2 5 Over 10 12 to 11 12 3 25 Over 11 12 to 12 12 4 0 Over 12 12 to 14 12 5 0 Over...

Страница 26: ...around the exposed pipe section and align brackets Insert a bolt provided through the brackets and tighten nut to complete storm collar assembly see Figure 8 17 Slide the assembled storm collar down t...

Страница 27: ...ovided the hole in the outer wrap does NOT exceed 2 1 2 inches in diameter and does not penetrate the firebox NOTE A listed and Commonwealth of Massachusetts ap proved 1 2 inch 13mm T handle manual sh...

Страница 28: ...k with local authorities Ensure that gas line does not come in contact with outer wrap of appliance Follow local codes Incoming gas line should be piped into the valve com partment and connected to th...

Страница 29: ...proper and dangerous op eration Verify proper operation after servicing Shock hazard Replace damaged wire with type 105O C rated wire Wire must have high temperature insulation WARNING C Intellifire I...

Страница 30: ...T Connection AUX BLACK Ground Pigtail Green FAN CONNECTION Flame High Low AC Plug Flame On RED RED ORANGE BLACK ORANGE RED BLACK 3V DC YELLOW YELLOW FACTORY CONNECTED TOGETHER FRONT VIEW IPI Valve ORA...

Страница 31: ...r plate to the outer shell If the box is being wired from the INSIDE of the appliance Remove the screw attaching the junction box to the outer shell rotate the junction box inward to disengage it from...

Страница 32: ...11 1 Clearances to Mantels or other Combustibles above Appliance Fire Risk Do NOT obstruct air inlet or outlet grilles Do NOT modify grilles Modifying or covering grilles could cause temperature rise...

Страница 33: ...e GEM36 Template is available for purchase to use instead of constructing a template Non combustible facing material is supplied with this appliance This material extends from the header to one inch a...

Страница 34: ...h extension required to protect combustible floors in front of appliance WARNING An 8 inch minimum hearth extension must be constructed of non combustible material D Hearth Extension Figure 11 7 Heart...

Страница 35: ...m above the base of the appliance see Fig ure 6 2 Install the interior firestop with the hole towards the top Secure the firestop to wall framing members Reference the Heat Out kit instructions for th...

Страница 36: ...NOT be placed directly over ports Care should be taken not to cover the lighting trail of ports from back to front When placing Glowing Embers onto the burner care should be taken so that the ports ar...

Страница 37: ...e the logs from the packaging Logs are fragile Before proceeding be sure to remove and discard the foam shipping pads shown here 4 1 2 3 STEP 1 Remove grate which is shipped on top of appliance Positi...

Страница 38: ...log 4 so that the straight end is positioned onto log 3 as shown and the Y end rests on log 1 as shown 4 4 Front view STEP 4 LOG 3 SRV370 702 Locate the grate slot in the underside of log 3 Place the...

Страница 39: ...other noncombustible materials can be used to cover up the gap between the sheet rock and the appliance Do not obstruct or modify the air inlet outlet grilles When overlapping on both sides leave eno...

Страница 40: ...operate the appliance with the protective barrier removed Contact your dealer or Hearth Home Technologies if the barrier is not present or help is needed to properly install one Glass door must be in...

Страница 41: ...soline and other liquids having flammable vapors away Do not operate the appliance with panel s removed cracked or bro ken Replacement of the panel s should be done by a licensed or qualified service...

Страница 42: ...r if appliance will not be used for an extended period of time Property damage possible from elevated temperatures CAUTION Fire Hazard Keep combustible materials gasoline and other flammable vapors an...

Страница 43: ...ection in wiring configuration or wiring harness Remove and reinstall the wiring harness that plugs into module Verify there is a tight fit Verify pilot assembly wiring to module Remove and verify con...

Страница 44: ...or wall switch in ON position Hold ground wire about 3 16 inch away from I terminal on module If there is no spark at I terminal module must be replaced If there is a spark at I terminal module is fi...

Страница 45: ...ndle glass assembly with care NOTE Clean glass after initial 3 4 hours operation Longer operation without cleaning glass may cause a permanent white film on glass CAUTION When cleaning glass door Avoi...

Страница 46: ...sooting Correct as necessary Firebox 1 Inspect for paint condition warpage corrosion or perforation Sand and repaint as necessary 2 Replace appliance if firebox has been perforated Burner Ignition and...

Страница 47: ...5 D 35 25 32 909 L 36 3 16 919 E 30 5 32 766 M 18 3 32 460 F 1 1 16 26 N 8 204 G 2 52 O 3 77 H 4 1 2 115 P 5 1 4 133 Appliance Dimensions Table A Appliance Dimensions Diagram Dimensions are actual app...

Страница 48: ...6 mm 45 7 3 8 in 187 mm 11 3 8 in 289 mm 1 1 4 in 32 mm 9 1 4 in 235 mm 13 1 4 in 337 mm 1 2 in TYP DVP90ST 90 Elbow 10 in 254 mm 1 in 25 mm 12 in 305 mm 14 in 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 m...

Страница 49: ...eld DVP TRAP SERIES Horizontal Term Cap 15 1 8 in 384 mm 14 in 566 mm 8 in 203 mm Max Effective Length DVP TRAP1 DVP Trap2 DVP TRAPK1 DVP TRAPK2 Minimum Maximum Term Cap Effective Effective TRAP1 4 1...

Страница 50: ...mm 24 5 8 in 625 mm 13 1 4 in 367 mm RF12M Roof Flashing Multi pak DVP BEK2 Trap Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm BEK Trap Cap Brick Extensio n 13 3 4 in 349 mm 5 in...

Страница 51: ...vered by this warranty unless expressly authorized and approved by HEAT GLO in writing 6 Any damages caused by environmental conditions inadequate ventilation or drafting caused by tight sealing const...

Страница 52: ..._________________________________________________ _______________________________________________________________________________ Printed in U S A Copyright 2006 DO NOT DISCARD THIS MANUAL CAUTION Imp...

Отзывы: