background image

Heat & Glo • EM-42 • 28324 Rev U • 02/07

35

A. Disposal of Ashes

Ashes should be placed in a metal container with a tight-

¿

 t-

ting lid. The closed container of ashes should be placed on 
a noncombustible 

À

 oor or on the ground, well away from all 

combustible materials, pending 

¿

 nal disposal. If the ashes 

are disposed of by burial in soil or otherwise locally dis-
persed, they should be retained in the closed container until 
all embers have thoroughly cooled.

B. Chimney Inspection/Cleaning

Inspect the chimney internally for obstructions and construc-
tion damage. Flue pipe joints and seams must be continu-
ous and mechanically tight.

The chimney should be inspected once every two months 
during the heating season.

If creosote has accumulated, it should be removed to reduce 
the risk of a chimney 

¿

 re.

Refer to Figure 11.1 to remove/reinstall termination caps.

Chimney

Remove 4 screws
and lift top pan off.

Cap

Slip
Section

ST375

Square

Termination Cap

Cap

Remove screws, 
lift top cover.

Top Cover

TR344/TR342

Round

Termination Cap

Chase

Cap

1.  Remove the 4 screws.
2.  Remove the screen.
3.  Remove the baffle.

TS345/TS345P

Square

Termination Caps

TCT375

Terra Cotta

Termination Cap

Remove 2 screws from
the front and back and
lift the top off.

Cap Top

(Be sure
holes in
cap top
and cap
base are
aligned.)

European Copper Series

Termination Cap

(CT3-King shown)

Cap Base

Remove 8 screws 
(9 for King), lift top 
cover.

Figure 11.1  Chimney & Termination Cap Cleaning

Fire Risk

Disposal of ashes

•  Ashes should be placed in metal container with tight 

¿

 tting lid.

•  Do not place metal container on combustible 

surface.

•  Ashes should be retained in closed container until all 

embers have thoroughly cooled.

WARNING

Fire Risk

Prevent creosote buildup

• 

Inspect chimney once every two months during heating 
season.

•  Remove creosote to reduce risk of chimney 

¿

 re.

•  Ignited creosote is extremely HOT.

WARNING

C. Firebox Refractory

Check 

¿

 rebox refractory for excessive cracks or gaps. If 

cracks exceed 1/4 in. (6 mm) in width the refractory should 
be replaced. See Section 12 for replacement information.

Fire Risk

• Inspect 

¿

 replace refractory annually.

Crumbling, deteriorated refractory can allow 
overheating of surrounding materials.

WARNING

Note: 

As you use the 

¿

 replace, expansion and contraction 

will cause minor cracking of the refractory. This is normal, 
unavoidable, and will not affect the performance of the 

¿

 replace. If the cracks become large enough that the metal 

behind the refractory is exposed or large pieces fall out, the 
panels should be replaced.

11 

11 

Maintenance and Servicing the Fireplace 

Содержание EM-42

Страница 1: ...URNS MAY RESULT CLOTHING IGNITION MAY RESULT WARNING Keep children away CAREFULLY SUPERVISE children in same room as replace Alert children and adults to hazards of high temperatures Keep clothing furniture draperies and other combustibles away Glass and other surfaces are hot during operation and cool down Fire Risk For use with solid wood fuel or decorative gas appliance only Do not install unve...

Страница 2: ...tion The model information regarding your speci c replace can be found on the rating plate located on the smoke shield of the replace Congratulations FIREPLACE NO MODEL NO MODEL NO MFG DATE WARNING RISK OF FIRE DAMAGE REPLACE GRATE WITH HEARTH HOME TECHNOLOGIES INC FIRECHAMBER INTENDED FOR USE WITH HEARTH HOME TECHNOLOGIES INC LISTED FIREPLACE PARTS SEE INSTALLATION AND OPERATING INSTRUCTIONS FOR ...

Страница 3: ...Chimney 20 6 Complete the Enclosure 21 A Chimney Termination 21 B Chase Top 22 C Install the Termination Cap 22 7 Accessories 24 A Side Brick Installation 24 B Gas Log Lighter Provisions 24 C Installation of Fan 25 8 Finishing 26 A Hearth Extension 26 B Finishing Material 27 C Mantel 27 D Sidewalls Surrounds 27 E Glass Doors 27 9 Operating Instructions 28 A General Information 28 B Outside Air 29 ...

Страница 4: ...ecorative re place It should not be factored as a primary heat source in residential heating calculations Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to the owner s information manual provided with this replace For assistance or additional information consult a quali ed installer service agency or your dealer WARNING Fire Risk Do not...

Страница 5: ... the replace Avoid installing the replace near doors walkways or small isolated spaces Recessed lighting should be a sealed can design attic hatches weather stripped or sealed attic mounted duct work and air handler joints and seams taped or sealed Basement installations should be avoided due to stack effect Stack effect creates negative pressure in lower levels Hearth Home Technologies recommends...

Страница 6: ... the highest part of the roof This minimizes the effects of wind turbulence Be located away from trees adjacent structures uneven roof lines and other obstructions Offsets can restrict draft so their use should be minimized Consider the replace location relative to Àoor and ceiling and attic joists Recommended Location Marginal Location Location Not Recommended Recommended Location Multi level Roo...

Страница 7: ...ecting roof rafters Offset Return with hanger straps Framing headed off in ceiling joists Enclosed space above and around fireplace Mantel and surround Decorative facing and trim Hearth extension Factory built fireplace Protective metal hearth strip s Outside combustion air Combustible framing header on top of V shaped standoffs spacers Chimney system Attic insulation shield not shown must be used...

Страница 8: ...TION E Inspect Fireplace and Components Carefully remove the replace and components from the packaging The vent system components and doors are shipped in separate packages Report to your dealer any parts damaged in shipment Read all the instructions before starting the installation Follow these instructions carefully during the installation to ensure maximum safety and bene t Fire Risk Explosion ...

Страница 9: ...mm B 25 5 8 in 651 mm B 25 5 8 in 651 mm A B Figure 3 1 Fireplace Locations Fire Risk Provide adequate clearances Around air openings To combustibles For service access Locate replace away from traf c areas WARNING Note Illustrations and photos reÀect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation appearance may vary due to ...

Страница 10: ... 51 mm min 2 in min 51 mm Must have 2 in 51 mm minimum clearance to header 0 in to floor 2 in 51 mm min 2 in 51 mm min 2 in 51 mm min 2 in 51 mm min Figure 3 2 Clearances to Combustible Materials Fire Risk Comply with all minimum clearances to combustibles as speci ed Framing or nishing material used on the front of or in front of the appliance closer than the minimums listed must be constructed e...

Страница 11: ...ls are used All re quired clearances to combustibles around the replace must be adhered to See Figure 3 2 Any framing across the top of the replace must be above the level of the top standoffs 18 1 2 in 470 mm 53 deg 12 in 305 mm 39 deg 4 in 102 mm Brick Front Flush Front 12 in 305 mm 14 1 2 in 368 mm 43 1 4 in 1099 mm framing 36 in 914 mm opening Figure 3 3 Sidewalls and Surrounds 25 5 8 in 651 m...

Страница 12: ... False Ceiling False Ceiling Insulation Insulation Figure 3 5 Chase Assembly F Chimney Requirements When planning your replace location the chimney con struction and necessary clearances must be considered The replace system and chimney components have been tested to provide Àexibility in construction Vertical distances are measured from the base of the replace as shown in Figure 5 2 1 2 3 All out...

Страница 13: ...upplied with this replace Using an outside air kit is highly recommended to minimize the effects of negative pressure within the structure We recommend you utilize the shortest duct run to optimize the performance of the outside air kit Cold air Àow can be minimized by put ting a small dip in the duct creating a cold air trap This trap can also help prevent heat build up and exhausting out the int...

Страница 14: ...entilated crawl space YES NO NO NO NO Use only duct materials specified by manufacturer preferably with short run or mainly straight duct except small dip for cold air trap which will help prevent flow of cold air Factory built fireplace Figure 4 3 Outside Combustion Air Placement 3 ft min from top of uppermost chimney section to air inlet Attic insulation shield must be used to keep insulation aw...

Страница 15: ...tform must be protected with a protective metal hearth strip as shown in Figure 4 6 Raised Platform Floor 2 in 51 mm 1 in 25 mm min overlap 2 in 51 mm Top piece must overlap bottom piece Figure 4 6 Protect the Front of an Elevated Platform Level the Fireplace Level the replace side to side and front to back Shim with noncombustible material such as sheet metal as necessary Secure the replace using...

Страница 16: ...pport for tall chimneys Install roof flashing according to minimum requirements Maintain minimum clearances to combustibles as specified Offsets returns may not exceed 30 from vertical Lock chimney sections together firmly to resist movement Ceiling firestops are required where chimney passes through ceiling or floor Support straps for offsets returns must be secured to adequate framing Terminatio...

Страница 17: ...x unsupported chimney above roof 40 in 1016 mm Effective Height Figure 5 2 Chimney Requirements Table 5 1 Do NOT connect this fireplace to a chimney flue servicing another appliance Do NOT connect to any air distribution duct or system CAUTION Fire Risk Must maintain 2 in 51 mm air clearance to insulation and other combustible materials WARNING HEIGHT OF CHIMNEY COMPONENTS in mm Chimney Stabilizer...

Страница 18: ...gree SL306 SL312 SL318 SL324 SL336 SL348 A B A B in mm in mm in mm in mm 1 5 8 41 13 3 8 340 3 5 8 92 15 1 2 394 2 7 8 73 17 3 4 451 5 1 2 140 18 5 8 473 1 4 1 8 102 22 3 8 568 7 1 4 184 21 3 4 552 2 4 1 2 114 23 5 8 600 8 1 2 216 23 3 4 603 1 5 3 4 146 28 1 4 718 10 1 4 260 27 686 1 1 6 152 29 3 8 746 11 1 2 292 29 737 1 7 1 4 184 34 864 13 1 4 337 32 1 8 816 2 7 3 4 197 36 1 8 918 14 1 2 368 34 ...

Страница 19: ... pipe during con struction and check to be sure inadvertent loading has not dislodged the chimney section from the replace or at any chimney joint Note Inner Àue and outer liner sections cannot be disas sembled once locked together Plan ahead to ensure the proper installation height is achieved with the selected chimney components Ceiling restop must be used at ceiling Àoor Chase construction requ...

Страница 20: ...himney When offsets and returns are joined to straight pipe sections they must be locked into position with the screws provided outer only using the predrilled holes To prevent gravity from pulling the chimney sections apart the returns and the chimney stabilizers have hanger straps for securing these parts to joists or rafters See Figure 5 8 or equivalent 6 or 8 sheet metal screw no longer than 3...

Страница 21: ...e plugged by snow or other material Must terminate at least 3 ft 914 mm above the roof and at least 2 ft 610 mm above any portion of the roof within 10 ft 3 05 m Must be located away from trees or other structures Mark the Exit Point of the Roof Locate the point where the chimney will exit the roof by plumbing down to the center of the chimney Drive a nail up through the roof to mark the center Se...

Страница 22: ...on allows sparks heat and embers to escape WARNING C Install the Termination Cap For installations utilizing a TR342 Round Telescoping Termination Cap the uppermost chimney section must be below the top of the chase top but not more than 14 1 2 in 368 mm below the top of the chase top Minimum overlap of chimney and termination cap must be 1 1 2 in 38 mm See Figure 6 6 Install the chimney sections ...

Страница 23: ...p See Figure 6 7 For installations utilizing a TS345 TS345P Square Termination Cap the uppermost chimney section must not be more than 3 in 76 mm below the chase top See Figure 6 8 For installations utilizing a TCT375 Terra Cotta Cap the last chimney section must be between 7 in 178 mm below the chase top and 2 in 51 mm above See Figure 6 9 For chase installations you can use a TR344 Round Termina...

Страница 24: ...lation 7 7 Accessories A Side Brick Installation Remove side brick pieces from inside of replace Set bottom of brick into lower brick support three pieces per side See Figure 7 1 Bend upper brick support up just enough to pivot brick under channel Push upper brick support down over brick until it bottoms out in the channel Repeat procedure for other side CHANNEL UPPER BRICK LOWER BRICK SUPPORT SUP...

Страница 25: ...e Route cord away from appliance Do NOT route cord under or in front of appliance CAUTION Note If a speed control option is desired it is recommended that you use the BC10 Motor Speed Control Kit supplied with the replace to ensure proper functioning Refer to the instructions packed with it for proper installation C Installation of Fan The EM 42 is a heat circulating replace that comes equipped wi...

Страница 26: ...ute materials for the factory available hearth ex tensions see Figure 8 3 and calculate insulation alterna tives as per Table 8 1 and the following formulas Thermal conductivity per inch thickness k k BTU inch foot2 hour F Required thickness Rk Thermal resistance per inch thickness r r foot2 hour F BTU inch Required thickness R rB 16 in min 406 mm 36 in 914 mm 8 in 203 mm 8 in 203 mm 52 in 1321 mm...

Страница 27: ...lls Surrounds Fire Risk Do NOT obstruct air inlet or outlet grilles Do NOT modify grilles Modifying or covering grilles could cause temperature rise and re hazard Finishing materials must not interfere with Air Àow through grilles or louvers Operation of louvers or doors Access for service WARNING C Mantel A combustible mantel may be positioned no lower than 16 in 406 mm above the top of the repla...

Страница 28: ...d operation of the replace Make certain that installation and operation of the replace system is in accordance with these instructions It is extremely important that the re be supervised when ever the replace is in use It is also recommended that an annual inspection be performed on the replace system to determine if the Àue system needs to be cleaned or as in the case of any appliance if minor re...

Страница 29: ...ith tightly sealed doors and windows are relatively air tight In this case an outside air source must be made available to feed combustion air from outside the home An outside air control handle allows you control of the out side air inlet if your replace is equipped with this option Use of outside air for combustion is highly recommended to conserve heated air within the structure and to provide ...

Страница 30: ... it in the replace and try to burn it This sounds ridiculous but that is exactly what you are doing if you burn unseasoned wood Fire Risk Use only factory installed integral grate May cause over re WARNING Seasoning Seasoned rewood is nothing more than wood that is cut to size split and air dried to a moisture content of around 20 The time it takes to season wood varies from around nine months for...

Страница 31: ...s to be burned from the replace and the refractory and paint to cure You may notice an industrial odor the rst few res This is consid ered normal Note When rst lighting your replace it may be neces sary to pre warm the Àue to establish a draft This is done by holding a rolled up piece of burning newspaper under the Àue damper for a few moments This will help reduce smoke spillage during start up O...

Страница 32: ...t sealing construction of the structure or mechan ical exhausting devices which will create a negative air pres sure within the structure where the replace is located A Understanding Vent Problems If smoke spillage occurs from a replace opening when the door is open and the proper chimney height Àue size and con guration requirements for the installation have been met there is either a leakage in ...

Страница 33: ...himney Down draft from chimney temperature or from negative house pressure Does the kindling wood not ignite Condition amount arrangement of kindling and fuel Use more drier well spaced kindling and fuel Does the kindling ignite but the fuel doesn t Amount of kindling Use more kindling use smaller dry wood Condition of fuel Does the fuel ignite but not burn well Condition of fuel Use well seasoned...

Страница 34: ...ire too close to front Build re farther back Do not use exhaust fans during startup and or check for need for balanced air make up system Competition with exhaust devices Diagnostic Questions Possible Causes of Condition Solutions Is the damper closed No Down draft or negative pressure Close the damper at end of burn Yes Negative pressure from exhaust fans and or house stack effect Check for need ...

Страница 35: ...screws from the front and back and lift the top off Cap Top Be sure holes in cap top and cap base are aligned European Copper Series Termination Cap CT3 King shown Cap Base Remove 8 screws 9 for King lift top cover Figure 11 1 Chimney Termination Cap Cleaning Fire Risk Disposal of ashes Ashes should be placed in metal container with tight tting lid Do not place metal container on combustible surfa...

Страница 36: ...properly engaged and the chimney is properly secured A chimney re can permanently damage your chimney sys tem Failure to replace damaged components and make proper repairs creates risk of re Inspect Maintenance Tasks Screens 1 Assess condition of screen and replace as necessary Screens are required 2 Verify maintenance of proper clearance to combustible household objects Glass Doors 1 Inspect glas...

Страница 37: ...1035 mm 19 1 8 in 486 mm 7 3 4 in 197 mm 35 in 889 mm 36 in 914 mm 42 1 8 in 1070 mm 10 1 2 in 267 mm Dia 25 in 635 mm 3 7 8 in 98 mm 9 7 8 in 251 mm 1 1 8 in 29 mm 18 3 4 in 476 mm 10 1 4 in 260 mm 9 in 229 mm 40 in 1016 mm effective height 3 1 2 in 89 mm Gas Knockout Outside Air 25 in 635 mm 10 1 4 in 260 mm 9 in 229 mm Gas Knockout 10 1 2 in 267 mm Dia ...

Страница 38: ...AT1936B BC10 Blower Control Catalog Description EM 42 Fireplace with integral grate hearth protection strips rebrick fan kit outside air kit and blower control DM1936B Bi fold glass doors Bright brass nish AT1936 Gasketed glass doors Black nish AT1936B Gasketed glass doors Bright brass nish HX3 Hearth extension BC10 Variable Speed Blower Control included with replace GR27 Integral grate included w...

Страница 39: ...Ceiling Firestop Straight FS339 Ceiling Firestop 15 deg FS340 Ceiling Firestop 30 deg AS8 SL300 Straight Attic Insulation Shield 24 in 610 mm JB877 Chimney Joint Band CB876 Chimney Bracket RF370 Roof Flashing Flat to 6 12 Pitch RF371 Roof Flashing 6 12 to 12 12 Pitch TR344 Round Termination Cap TR342 Round Telescoping Termination Cap ST375 Square Termination Cap TS345 Square Termination Cap TS345P...

Страница 40: ... mm JB877 Chimney Joint Band 10 1 2 in 267 mm CB876 Chimney Joint Band 12 in 305 mm 31 in 787 mm 24 5 8 in 625 mm RF371 Roof Flashing 12 in 305 mm 24 5 8 in 625 mm 27 3 8 in 695 mm RF370 Roof Flashing Inside Diameter 8 in 203 mm Outside Diameter 10 1 2 in 267 mm Effective Height 4 3 4 in 121 mm Catalog A B FS338 0 deg 14 1 2 in 368 mm FS339 15 deg 18 3 8 in 467 mm FS340 30 deg 23 in 584 mm ...

Страница 41: ...LDS46 Decorative Shroud 15 3 4 in 400 mm 34 3 4 in 883 mm 32 1 2 in 826 mm 23 in 584 mm 19 in 483 mm 15 5 8 in 397 mm 13 1 4 in 337 mm 18 in 457 mm 16 1 4 in 413 mm 22 in 559 mm 23 1 8 in 587 mm 20 in 508 mm 9 3 8 in 238 mm 17 in 432 mm 9 1 4 in 235 mm Catalog A B C D in mm in mm in mm in mm LDS33 36 914 36 914 8 1 2 216 11 279 LDS46 48 1219 72 1829 8 1 2 216 11 279 LDS BV Decorative Shroud E D A ...

Страница 42: ... CT3 Knight CT3 King 21 in 533 mm 49 in 1245 mm 24 in 610 mm 18 1 4 in 464 mm 41 1 8 in 1045 mm 20 in 508 mm 16 in 406 mm 40 3 8 in 1256 mm 18 in 457 mm 21 in 533 mm 25 3 4 in 654 mm 20 5 8 in 524 mm 20 3 4 in 527 mm 38 5 8 in 981 mm 20 in 508 mm European Copper Caps ...

Страница 43: ... Base Dimensions Inches N A 26 5 X 28 with Radiation Shield 28 X 30 34 X 34 with Radiation Shield 28 X 30 with Radiation Shield or 34 X 34 Minimum Height Inches N A 28 1 4 27 1 2 28 1 4 27 1 2 ROOFED STYLE with 12 X 22 264 sq in opening on each side and 3 in space between the radiation shield and chase top Minimum Base Dimensions Inches N A 27 X 27 with Radiation Shield 27 X 27 with Radiation Shie...

Страница 44: ...Heat Glo EM 42 28324 Rev U 02 07 46 This page intentionally left blank ...

Страница 45: ...t minimum wholesale price but HHT SHALL NOT BE RESPONSIBLE FOR ANY LABOR TRANSPORTATION OR OTHER INDIRECT DAMAGES 4 During the first six 6 months after installation HHT shall at its option replace or repair the glass doors and any electrical components if operation is faulty This does not include glass panels broken during shipment misuse or careless handling After the first six 6 months HHT will ...

Страница 46: ...076254 5113843 5191877 5218953 5263471 5328356 5341794 5347983 5429495 5452708 5542407 5601073 5613487 5647340 5688568 5762062 5775408 5890485 5931661 5941237 5947112 5996575 6006743 6019099 6048195 6053165 6145502 6170481 6237588 6296474 6374822 6413079 6439226 6484712 6543698 6550687 6601579 6672860 6688302B2 6715724B2 6729551 6736133 6748940 6748942 6769426 6774802 6796302 6840261 6848441 68630...

Отзывы: