Heat & Glo LifeStyle Collection • Twilight-II • 2087-900 Rev. G • 12/05
18
A. Mantel Projections
Figure 8.1 shows the minimum vertical and corresponding
maximum horizontal dimensions of appliance mantels or
other combustible projections above the top front edge of
the appliance.
Finishing
8
Figure 8.2 Clearances to
Combustible Mantel Leg or
Wall Projections (Acceptable
on both sides of opening.)
Figure 8.1 Indoor Clearances to Mantels or other
Combustibles above Appliance
12
11
10
9
8
7
6
13-5/8
12-5/8
11-5/8
10-5/8
9-5/8
8-5/8
7-5/8
HOOD
NON-COMBUSTIBLE BOARD
(SUPPLIED ON APPLIANCE)
Note:
Measurements
are in inches.
Interior
V i e w
MEASURED
FROM CORNER
FIREPLACE
HOOD
½ IN.
TOP VIEW
B. Facing Material
Fire Risk.
Do NOT obstruct air inlet or outlet grilles.
Do NOT modify grilles.
•
Modifying or covering grilles could cause
temperature rise and fire hazard.
WARNING
Finishing materials must not interfere with:
•
Air flow through grilles or louvers.
•
Operation of louvers or doors.
•
Access for service.
Inside Facing Material
•
May install combustible materials up to specified
clearances on top, front and sides of appliance.
•
Seal joints between finished wall and appliance top and
sides with 300
0
F (140
0
C) minimum sealant.
•
Leave space so bottom grille can be lowered for trim
door removal.