45
F. Sidewalls/Surrounds
• Adjacent combustible sidewalls must be located
a minimum of 24 in. (610 mm) from the fireplace
opening.
• Combustible or non-combustible mantel legs, surrounds
and stub walls may be constructed per Figure 11.12.
B
A
24 in.
[610 mm]
19 3/4 in.
[502 mm]
24 in.
[610 mm]
28 5/8 in.
[727 mm]
FLUSH
FRONT
4 in.
[102 mm]
BRICK
FRONT
50° angle
39° angle
Note: Grid depicts 1-in scale.
Figure 11.12 Mantel Leg or Wall Projections (acceptable on both sides of opening)
Model
A
B
EXCLAIM-36
inches
36
45
mm
914
1130
EXCLAIM-42
inches
42
50 1/2
mm
1067
1283
Heat & Glo • EXCLAIM-36, EXCLAIM-42 • 4013-251 Rev C • 11/08