Hearthstone Quality Home Heating Products, Inc.
Tucson DX/ST Model 8702
18
Venting Information
Venting Components
Starter collar is installed by Hearthstone.
Use the following instructions along with the pipe
manufacturer’s instructions to complete the
installation. Do not mix vent components from
different manufacturers within the same venting
system.
Approved Venting Manufacturers
The Tucson Direct Vent (8702) is approved for
installation only with the venting components
provided by manufactures listed on
this page.
Simpson Dura-Vent, Inc.
P.O. Box 1510
Vacaville, CA 95696-1510
800-835-4429
American Metal Products
(AmeriVent)
8601 Hacks Cross Rd.
Olive Branch, MS 38654
800-423-4270
Selkirk Corporation
1301 W. President George Bush Hwy, Suite 330
Richardson, TX 75080-1139
800-992-8368
Security Chimneys International Ltd
(Secure Vent)
2125 Monterey, Laval, Quebec
Canada, H7L 3T6
450-973-9999
ICC, Inc.
400 J-F Kennedy, St. Jerome, Quebec
Canada, J7Y 4B7
450-565-6336
Metal-Fab, Inc.
P.O. Box 1138
Wichita, Kansas 67201
316-943-2351
Venting Terminations
The Tucson cannot be vented jointly with any other
solid fuel or gas appliance. It must be vented directly
to the outside of the building using a proper
termination as listed in this manual. After
determining the venting configuration for your stove,
select the vent system that will best accommodate
your installation.
CAUTION: ENSURE ALL STOVE AND
TERMINATION CAP CLEARANCES ARE
OBSERVED PER THIS OWNER’S MANUAL.
CAUTION: ENSURE THERE IS NO WIRING OR
PLUMBING IN THE CHOSEN LOCATION.
CAUTION: DO NOT RECESS VENTING
TERMINALS INTO A WALL OR SIDING.
Approved Venting Configurations
WARNING: IN HIGH WIND AREAS AND
PARTICULARLY COLD CLIMATES IT MAY BE
NECESSARY TO HEAT YOUR VENT SYSTEM
WITH THE PILOT PRIOR TO IGNITION OF THE
MAIN BURNER. IN THESE INSTANCES IT IS
RECOMMENDED THAT YOU LEAVE THE PILOT
RUNNING FOR 5 MINUTES PRIOR TO IGNITING
THE MAIN BURNER. THIS WILL ALLOW FOR
PROPER START UP AND IGNITION OF ALL
PORTS ON THE BURNER.
There are three types of venting configurations
approved for use with this appliance:
Vertical Venting/Vertical Termination
Vertical Venting/Horizontal Termination
Horizontal Venting/ Snorkel Termination
Pipe Clearances to combustibles:
1" to vertical runs
1" below and to the side of horizontal runs
2" from the top of horizontal runs
Vertical Venting and Termination
The Tucson 8702 is approved for venting vertically
through a roof or ceiling. When installing a vertical
vent and/or vertical terminations you must adhere to
the following requirements:
When terminating vertically you must have at
least 10’ of vertical pipe.
Always maintain a minimum of 1” clearance from
all sides of the vent system to any combustible
material.
A listed fire stop is required at any floor
penetration. The opening must be framed in
according to the venting manufacturer’s
instructions.
Steep roofs, nearby trees, or predominantly
strong windy conditions can promote poor draft
or down draft conditions. In this event, an
increase to the height of the vent may improve
performance.
A maximum of two 90
⁰
or four 45
⁰
elbows may
be used in vertical terminations. (This includes
the one 45
⁰
elbow off the stove outlet)
Whenever possible use 45
⁰
elbows instead of
90
⁰
elbows as they offer less restriction to the
flue gases.
Vertical terminations may require additional
restriction in order to perform as intended.