(1) 90º E
LBOW
•
The termination must fall within the area outlined by the shaded area shown in the
illustration below.
•
A minimum of a 9” rise is required directly off the heater.
•
Use a vinyl siding standoff when installing against vinyl siding.
•
Horizontal sections require a ¼” rise every 12” of horizontal run.
NOTES:
1. The vent must terminate within one of the regions outlined by the shaded area.
2. For each 90º elbow after 2, remove 5’ from horizontal run.
3.
For Canadian installations: remove 4’ from horizontal run.
4. At minimum vertical rise, maximum horizontal run 14”.
5. Use with snorkel termination 14” maximum horizontal run.