background image

Page 4

506746−01 05/12

desired current is reached, the fill valve (1) will close and
the water will then begin to warm and produce steam. If the
water reaches the cylinder full probe (9) or if current rises
too much, the drain pump (11) will be activated to drain
away some water and reduce the current flow to accept-
able levels. Note that, any time the drain pump is activated,
the tempering valve (10) will be opened for tempering the
hot drained water down to 140º F (60ºC) in accordance to
local and national standards.

Periodically, based on the incoming water conductivity, the
unit will run drain pump (11) and drain some water to re-
duce the mineral concentration. A strainer (12) in the cylin-
der helps to prevent mineral debris from jamming the drain
pump (11).

In case the HCSteam−16/−35 humidifier remains powered
but idle, i.e. without producing steam, for more than 48
hours (2 days), the cylinder will be emptied to not have
stagnant water inside.

If there is no water in the cylinder, there will be no current
flow and no steam production. The electrodes do not burn
out, but they will eventually become completely coated
with mineral and the cylinder will then need to be replaced.
Cleaning cylinders may cause electrode damage, there-
fore voiding its warranty. See maintenance section on
Page 21.

Installation

Installing the nozzle

The HCSteam−16/−35 humidifier’s nozzle must be installed
onto the ductwork near the humidifier. Refer to the Steam
Distribution section (Page 8) for information on how to
properly locate the nozzle, for dimensions for the hole
mounting pattern, and for connections to the humidifier
and to the condensate drain. (Also see figure 6 for a typical
installation diagram.)

Drill a 2−1/4" (57 mm) hole in the ductwork at the selected
location for inserting the nozzle into the duct work. Position
the nozzle in the hole. Mark and drill 1/16" mounting holes
and use self−tapping sheet metal screws to attach the
nozzle to the duct.

Removing the humidifier front cover

The front cover is secured by four screws located at the
four corners of the unit. Using a Phillips head screwdriver,
loosen the four cover screws and then pull the front cover
away from the back part of the unit (see figure 3).

Installing the humidifier

CAUTION

Do not install the humidifier in an location that is
within the reach of children.

If unit must be located where any leaking water
could cause damage, an auxiliary drain pan is rec-
ommended.

Do not install humidifier in a location where freezing
temperatures may occur. Water supply and drain
lines may freeze causing water damage.

Positioning the humidifier

The HCSteam−16/−35 humidifier has been designed for
on−wall installation. The simplest and most efficient instal-
lation would have the humidifier installed just below the
duct where the steam nozzle is to be installed. This mini-
mizes steam hose length and the amount of condensate.

Certain clearances must be maintained around the
unit for safety and maintenance (see table 1 on
Page 2).

.

If present, remove packing as shown in figure 4.

REMOVE PROTECTIVE
FILM FROM COVER

Figure 3. Removing the front cover

REMOVE PACK-
ING BEFORE
INSTALLING

LATCH THE CYLINDER
CLAMP

REMOVE PACKING
BEFORE INSTALLING

REMOVE
RESTRAINT
BEFORE
INSTALLING

REMOVE PRO-
TECTIVE FILM
FROM DISPLAY

Figure 4. Removing Packing

Содержание HCSteam?16

Страница 1: ...pping damage or missing components if found immediately report any discrepancies to the last carrier INSTALLATION INSTRUCTIONS HCSteam 16 35 Residential Healthy Climate Steam Humidifier INDOOR AIR QUA...

Страница 2: ...through an electric fill valve Periodically based on the water quality the unit will also drain some water to di lute the build up of minerals in the steam generator This humidifier has been designed...

Страница 3: ...cylinder A flow restrictor 4 prevents the unit from filling too quickly or with too much pressure The water flows up the fill tube 2 and into the fill cup 3 Water then flows over the dam in the fill c...

Страница 4: ...hole mounting pattern and for connections to the humidifier and to the condensate drain Also see figure 6 for a typical installation diagram Drill a 2 1 4 57 mm hole in the ductwork at the selected lo...

Страница 5: ...5 128 10 1 8 257 2 1 2 65 Dimensions in inches mm 1 7 8 48 2 3 4 70 2 1 8 54 3 8 9 17 5 8 448 3 7 8 98 1 1 2 38 2 3 8 60 2 3 8 60 23 5 8 600 3 5 8 92 5 8 16 3 1 4 82 1 3 8 35 2 dia 51 7 8 dia 23 1 5...

Страница 6: ...rt to the negative pressure tap Check for closure of the switch when blower is turned on Plumbing Water characteristic requirements The humidifier must be supplied with water with the following charac...

Страница 7: ...ILTER Recommended SUPPLY WATER EXTENSION TUBE SHUTOFF VALVE AND FILTER Recommended OPEN DRAIN DRAIN LINE Water inlet with filtering screen 3 4 hose con nection 1 1 4 Water drain STEAM HOSE ADAPTER FIL...

Страница 8: ...jection The maximum allowed duct static pressure is 2 w c The HCSteam 16 35 humidifier include a plastic injection nozzle figure 7 CONDENSATE CONNECTION 2 1 2 63m 2 1 2 63m STEAM INLET O D 2 2 56mm dr...

Страница 9: ...0 3 m TYPICAL INSTALLATION WHEN UNIT IS ABOVE THE STEAM NOZZLE 5 ft 1 5 M MAX 5 ft 1 5 M MAX IF NO SLOPE 3 9M MAX 20 5 10 ft 3M MAX 5ft 1 5 M MAX 20 5 GENTLE BEND OBSTRUCTION SUPPORTED STEAM HOSE AND...

Страница 10: ...ct the ground wire to the unit s chassis ground lo cated just behind the power wiring terminal block see fig ure 11 C L1 L2 A B C SERVICE DISCONNECT STRAIN RELIEF L1 L2 GND GND WIRE NUT POWER CONTROL...

Страница 11: ...a heating demand or thermostat blower demand When the indoor blower stops the air proving switch contacts will open SLP98 Furnace CBX40 Air Handler C NO Note 1 Do not connect H on CS7000 to H on furna...

Страница 12: ...he thermo stat s humidity RH set point a demand message for humidification is sent to the HVAC unit control board S The demand message starts the indoor blower and sends a 24 volt signal from the H te...

Страница 13: ...sent to the furnace control board S The demand message starts the indoor blower and closes the HUM contacts on the furnace control 24 VAC passes through a field installed jumper from the R terminal on...

Страница 14: ...EXT FAN contacts open de energizing the blower interlock coil and stopping the indoor blower if not running due to a heating demand or thermostat blower demand When the indoor blower stops the air pr...

Страница 15: ...rogramming port Connecting to Programming port or supervisor factory use only AB AB Remote enabling input Imposes an external NO contact Rmax 300 Ohm Vmax 33 Vdc Imax 6mAdc humidifier enabled contact...

Страница 16: ...wired to close when air flow is proved S Hi limit humidistat if used is wired to open on humid ity rise above setpoint S Unit wires have been checked to make sure they and all connectors are tight fr...

Страница 17: ...f 03 or higher not applicable for these models If value is higher than 02 press reset sel until the display goes back to the normal operating mode and re start from step 1 4 Press and hold drain mini...

Страница 18: ...humidifier back on DO NOT release reset sel and drain buttons until the wrench icon blinks then re lease both buttons 3 Press reset sel until the display shows 03 DO NOT confirm any value higher than...

Страница 19: ...y used for 2000 hrs Press reset sel key for 1 seconds to reset Off Change cylinder not urgent E4 Fill alarm unable or slow fill current does not increase within timeout Press reset sel key for 1 secon...

Страница 20: ...rrectly 2 Increase air flow in duct or decrease maximum steam production setting see Page 17 3 Check the connection of the device flow switch or differential pressure switch controlling the humidifier...

Страница 21: ...nd the general condition of the cylinder Check that during operation there is no arcing between the electrodes S Every three months or no more than 1000 operating hours Check operation that there are...

Страница 22: ...the electrical connections from the top of the cylinder 7 Carefully remove cylinder from the pump manifold Make sure the O ring remains in the manifold see fig ure 26 8 Verify cylinder model voltage f...

Страница 23: ...5 S Steam Nozzle Y3781 Table 6 Technical Specifications Steam flows VAC kW 5 5 lbs hr 2 5 kg h 110 120 VAC 1 phase 50 60 Hz 1 86 kW 12 lbs hr 5 4 kg h 220 240 VAC 1 phase 50 60 Hz 4 05 kW Notes Steam...

Страница 24: ...Page 24 506746 01 05 12 070222075 rel 1 2 dated 25 05 2012...

Отзывы: