Installed system piping network must be flushed 

properly before placing the Deluge valve in service.
A qualified and trained person must commission 

the system. After  few initial successful tests, 

an authorized person must be trained to perform 

inspection and testing of the system. It is 

recommended to have regular inspection and test run 

of the system as per NFPA guideline or in accordance 

to the organisation having local jurisdiction.

(i) WARNING

 

Inspection and testing is to be carried out only by 

 

authorised and trained personnel. DO NOT TURN 

 

OFF the water supply or close any valve to make 

 

repair(s), or test the valve without placing a 

 

roving fire patrol in the area covered by the 

 

system. Also inform the local security personnel 

 

and central alarm station, so that there is no 

 

false alarm signal.

 

It is recommended to carry out physical inspection 

 

of the system at least twice in a week. The 

 

inspection should verify that all the control valves 

  are in proper position as per the system 

   requirement and that there are no damages to 

 

any component.

 

The frequency of inspections must be increased 

 

in the presence of contaminated water supplies,  

 

corrosive/scaling water supplies, and corrosive 

 

 atmospheres.

(ii)  NORMAL CONDITION

(a) All main valves are open and are sealed with 

 

tamper proof seal

(b)  Drain valves must be kept closed
(c)  No leak or drip is detected from the drip valve
(d) All the gauges except the system side water 

 

  pressure gauge, should show the required 

 pressure
(e)  There should be no leakage in the system

(iii)  NORMAL CONDITION TEST

(a) The system should be checked for normal 

 

 

condition at least once in a week

(b)  Test the sprinkler alarm bell or electric alarm 

 

 

by turning the alarm test valve to the test 

 

position. The alarm should sound. This test should  

 

be carried out at least once in a week

(c) Depress the drip valve knob. Significant 

 

accumulation indicates a possible seat leakage

(d)  Conduct the water flow test as per the system  

 

testing procedure at least once a month

(iv)  PERIODIC CHECK

 Conduct the water flow test by actuating few of 

the release devices provided in the system. Clean 

all strainer(s) and  line restriction nipple. This 

test is to be carried out at least once in three 

months.

ABNORMAL CONDITION

(i)  ALARM  FAILS TO SOUND

(a)  Check  for any obstruction in the alarm test 

 

line, make certain that the sprinkler alarm is free 

 

to operate

(b) If an electric alarm is provided, check the 

 

 

electrical circuitry to the alarm

(ii)  FALSE TRIPS

(a)  Check  for clogging in priming line,  restriction 

 

orifice check valve, priming valve & strainer

(b)  Leakage  in  the release  system
(c)  The deluge air line restriction orifice clogged or   

 

low supply  pressure

(iii)  LEAKAGE THROUGH THE DELUGE VALVE

(a) Damaged deluge valve seat or obstruction on 

 

 

the seat face by foreign object

(b)  Leakage in release system
(c)  Partly  clogged  priming line restriction orifice 

 

check valve

(d)  Low  air pressure on  release  system  line or 

 

leakage in release system

NOTE

:

(1) UL Listing  is valid only when Deluge Valve is 

 

installed with trim set as per trim drawing.

(2)  The trip time of deluge valve on-off device through 

detection network, will depend on volume of 

detection network. If the trip time of deluge valve 

is more, then it can be substantially reduced by 

installing check valve  in branch of release line in  

the  detection network.  The check valve flow shall  

be towards releasing device.

(3) The pneumatic system must have restricted 

 

 

orifice at air or gas supply point. The restriction 

 

nozzle are supplied with HD dry pilot actuation 

 trim.
(4)  UL Listing is valid only when Listed Solenoid Valve 

provided for electric operation of the deluge valve  

is retained in the trim. If any other solenoid valve 

is used, the deluge valve trip time may be quite 

high or deluge valve may not trip.

(5)  The Pressure Gauges standard supply is 300 psi 

for water gauge for system pressure upto 175 

psi. If system pressure is more than 175 psi, 

then order for 600 psi water pressure gauges.

Содержание H3

Страница 1: ... 165 1mm REQUIREMENT SPECIFY IN ORDER DESCRIPTION Deluge Valve is known as a system control valve in a deluge system used for fast application of water in a spray system Deluge valve protects areas such as power transformer installation storage tank conveyor protection and other industrial application etc With the addition of foaming agent deluge valve can be used to protect aircraft hanger and in...

Страница 2: ...lve drops and the Deluge valve opens c ELECTRIC RELEASE TRIM To actuate a Deluge valve electrically a solenoid valve is provided to drain the water from the top chamber of the Deluge valve A pressure switch is provided to activate an electric alarm to shut down the desired equipment or to give Tripped indication of the Deluge valve In addition to this a pressure switch can also monitor Low air pre...

Страница 3: ...g connection is from the inlet of Deluge Valve Auto resetting i The deluge valve will reset automatically when releasing devices which were responsible for deluge valve opening are closed or restored back to their original status i e closing of ERS or replacing the damaged Sprinkler if release was through Sprinkler QB Detector or closing of Solenoid valve The reset time may be long or cause vibrat...

Страница 4: ... valve knob Significant accumulation indicates a possible seat leakage d Conduct the water flow test as per the system testing procedure at least once a month iv PERIODIC CHECK Conduct the water flow test by actuating few of the release devices provided in the system Clean all strainer s and line restriction nipple This test is to be carried out at least once in three months ABNORMAL CONDITION i A...

Страница 5: ...MARCH 2022 HD 235 PAGE 5 OF 16 HD FIRE PROTECT PVT LTD DELUGE VALVE MODEL H3 SIZE 200 150 100 80 50 NB 2 4 5 6 7 8 9 10 12 13 14 15 16 17 19 11 18 20 21 3 1 Groove x Groove Flange x Flange ...

Страница 6: ...1 STAINLESS STEEL 4 9151 9112 9112 BOLT 8 4 4 STAINLESS STEEL 5 3546 3545 3544 3543 3543 RUBBER CLAMP 1 1 1 1 DUCTILE IRON 6 117466 117465 117464 117463 117463 RUBBER SEAT 1 1 1 1 EPDM 7 4034 3990 4011 4041 4041 CLAPPER 1 1 1 1 DUCTILE IRON 8 117462 117461 117460 117459 117459 DIAPHRAGM 1 1 1 1 EPDM 9 3542 3541 3540 3539 3539 CLAMP RING 1 1 1 1 DUCTILE IRON 10 8806 9151 9151 9151 9151 BOLT 12 8 8 ...

Страница 7: ...E GAUGE VALVE RN RESTRICTIOIN NOZZLE AIR LINE OD OPEN DRAIN STRAINER SV SOLENOID VALVE DPA DRY PILOT ACTUATOR BY USER PS1 LOW AIR ALARM PRESSURE SWITCH NRV NON RETURN VALVE PS2 WATER FLOW PRESSURE ALARM SWITCH OPTIONAL FLANGE X FLANGE GROOVE X GROOVE FLANGE X FLANGE GROOVE X GROOVE PG M OD INLET OUTLET OD DV PS2 PG DPA RN LINE TO DETECTION OD AIR SUPPLY PS1 PG NRV SV PG M OD INLET OUTLET OD DV PS2...

Страница 8: ...NIPPLE M EMERGENCY RELEASE STATION PG PRESSURE GAUGE VALVE RN RESTRICTIOIN NOZZLE AIR LINE OD OPEN DRAIN STRAINER SV SOLENOID VALVE DPA DRY PILOT ACTUATOR BY USER PS1 LOW AIR ALARM PRESSURE SWITCH NRV NON RETURN VALVE PS2 WATER FLOW PRESSURE ALARM SWITCH OPTIONAL PG M OD INLET OUTLET OD DV G OD TO DETECTION LINE PG NRV PS2 SV PG M OD INLET OUTLET OD DV G OD TO DETECTION LINE PG NRV PS2 SV PG M OD ...

Страница 9: ...SE STATION PG PRESSURE GAUGE VALVE RN RESTRICTIOIN NOZZLE AIR LINE OD OPEN DRAIN STRAINER SV SOLENOID VALVE DPA DRY PILOT ACTUATOR ANGLE VALVE PS1 LOW AIR ALARM PRESSURE SWITCH DR V DRIP VALVE BY USER PS2 WATER FLOW PRESSURE ALARM SWITCH NRV NON RETURN VALVE OPTIONAL PG M OD INLET PG OUTLET OD DV DR V OD OD OD TO DETECTION LINE PS2 SV PG M OD INLET PG OUTLET OD DV DR V OD OD OD TO DETECTION LINE P...

Страница 10: ...D NRV TO DETECTION LINE PS2 SV PG M OD INLET PG OUTLET OD DV SV G OD PS2 PG DR V DPA RN LINE TO DETECTION OD OD OD OD AIR SUPPLY NRV PS1 NRV PG M OD INLET PG OUTLET OD DV G OD PG DR V DPA RN LINE TO DETECTION OD OD OD OD AIR SUPPLY NRV NRV SV PS2 PS1 ABBREVIATION SYMBOLS DV DELUGE VALVE G SPRINKLER ALARM WMG NRV WITH RESTRICTION HEX NIPPLE M EMERGENCY RELEASE STATION PG PRESSURE GAUGE VALVE RN RES...

Страница 11: ... WITH RESTRICTION HEX NIPPLE M EMERGENCY RELEASE STATION PG PRESSURE GAUGE VALVE RN RESTRICTIOIN NOZZLE AIR LINE OD OPEN DRAIN STRAINER SV SOLENOID VALVE DPA DRY PILOT ACTUATOR BY USER PS1 LOW AIR ALARM PRESSURE SWITCH NRV NON RETURN VALVE PS2 WATER FLOW PRESSURE ALARM SWITCH OPTIONAL INLET PG OUTLET PG OD M OD DV TO DETECTION LINE SV PS2 INLET PG OUTLET PG OD M OD DV TO DETECTION LINE SV PS2 INLE...

Страница 12: ...EX NIPPLE M EMERGENCY RELEASE STATION PG PRESSURE GAUGE VALVE RN RESTRICTIOIN NOZZLE AIR LINE OD OPEN DRAIN STRAINER SV SOLENOID VALVE DPA DRY PILOT ACTUATOR BY USER PS1 LOW AIR ALARM PRESSURE SWITCH NRV NON RETURN VALVE PS2 WATER FLOW PRESSURE ALARM SWITCH OPTIONAL INLET PG OUTLET PG OD M OD DV G OD TO DETECTION LINE NRV SV PS2 INLET PG OUTLET PG OD M OD DV G OD TO DETECTION LINE NRV SV PS2 INLET...

Страница 13: ... PG PRESSURE GAUGE VALVE RN RESTRICTIOIN NOZZLE AIR LINE OD OPEN DRAIN STRAINER SV SOLENOID VALVE DPA DRY PILOT ACTUATOR ANGLE VALVE PS1 LOW AIR ALARM PRESSURE SWITCH DR V DRIP VALVE BY USER PS2 WATER FLOW PRESSURE ALARM SWITCH NRV NON RETURN VALVE OPTIONAL INLET PG OUTLET PG OD M OD DV OD OD DR V OD TO DETECTION LINE SV PS2 INLET PG OUTLET PG OD M OD DV OD OD DR V OD TO DETECTION LINE SV PS2 INLE...

Страница 14: ...TO DETECTION LINE G OD NRV PS2 SV ABBREVIATION SYMBOLS DV DELUGE VALVE G SPRINKLER ALARM WMG NRV WITH RESTRICTION HEX NIPPLE M EMERGENCY RELEASE STATION PG PRESSURE GAUGE VALVE RN RESTRICTIOIN NOZZLE AIR LINE OD OPEN DRAIN STRAINER SV SOLENOID VALVE DPA DRY PILOT ACTUATOR ANGLE VALVE PS1 LOW AIR ALARM PRESSURE SWITCH DR V DRIP VALVE BY USER PS2 WATER FLOW PRESSURE ALARM SWITCH NRV NON RETURN VALVE...

Страница 15: ...VALENT LENGTH BASED ON 1 2 SCHEDULE 40 PIPE WITH C 120 KG SQ CM METERS MAXIMUM PILOT LINE HEIGHT FT 60 20 20 40 120 80 100 140 5 10 15 20 25 30 35 40 40 2 4 6 8 10 12 160 180 200 14 16 18 45 50 55 60 50 100 150 200 250 0 220 65 25 FEET 250 FEET 500 FEET 60 20 20 40 120 80 100 140 5 10 15 20 25 30 35 40 40 2 4 6 8 10 12 160 180 200 14 16 18 45 50 55 60 50 100 150 200 250 0 220 65 25 FEET 250 FEET 5...

Страница 16: ...including but not limited to any implied warranties or merchantability or fitness for a particular purpose All such other warranties and representations are hereby cancelled NOTICE The equipment presented in this bulletin is to be installed in accordance with the latest publication standards of NFPA or other similar organisations and also with the provision of government codes or ordinances wherev...

Отзывы: