9. After the selected phase has been tested and the AMMETER CLEAR button is released,

rotate the select knob to another position to test the other phases and repeat step 7
for each phase. The LCD will always indicate which phase that is being tested.

THERMAL OVERLOAD

The FACT-1 contains several resistors to limit the current supplied to the selected phase.
Since these resistors are required to dissipate several hundred watts, significant heat can
build up inside the case if the AMMETER CLEAR button is pressed for a long time on a
faulted cable. If the internal sensor detects a temperature that is too high, a message will
be displayed to the LCD:

Unit Temperature is Too High. Please Allow to Cool (with power switch on)

If this situation occurs, leave the FACT-1 plugged in with the POWER switch ON. This will
operate the fan and reduce the internal temperature. When the unit temperature' drops to
an operational level, the message will disappear and the unit may be used for testing again.

REVERSED POLARITY OPERATION

The FACT-1 has been designed to not only protect against an incorrectly wired outlet, but
to operate normally if such a situation arises. If the unit detects incorrect polarity, a message
is displayed to the operator to alert him of the situation. The operator must then press the
SELF-TEST button momentarily to clear the notice:

NOTICE:

LINE CORD POLARITY IS REVERSED PRESS SELF-TEST TO CONTINUE

DIAGNOSTICS

The FACT-1 has built-in comprehensive diagnostics to assure that the FACT-1 is operating
correctly. The test cable assembly should NOT be connected to the FACT-1 during the Self-
Test. The Self Test mode is entered by pressing the SELF-TEST button. If at any time, you wish
to exit the Self-Test mode, simply press the SELF-TEST button a second time. The FACT-1 will
guide the operator through the Self-Test procedure using messages on the LCD.

Once Self-Test mode is entered, a message will be displayed to rotate the selector knob
to the correct position:

Rotate Switch to Pos A, then Press & Hold Ammeter Clear Button
(Self-Test to Cancel)

If the selector knob was already in that position or if the selector knob is rotated to that
position, the LCD will instruct the operator to press & hold the AMMETER CLEAR button
until a test PASS or test FAIL message is displayed. Once the AMMETER CLEAR button
is released, the operator will be instructed to rotate the selector knob to each of the
remaining positions and to press the AMMETER CLEAR button.

At the conclusion of the test, an ALL TESTS PASSED or TEST FAILURE message will be
displayed before returning to normal operation.

The FACT-1 should never be operated outside of its maximum operating temperature
range of -20C to +60C (-4F to +140F). Operating the FACTS outside of its temperature
range may permanently damage the unit.

Содержание FACT-1

Страница 1: ...uction Manual HD ELECTRIC COMPANY 1 4 7 5 L A K E S I D E D R I V E W A U K E G A N I L L I N O I S 6 0 0 8 5 U S A PHONE 847 473 4980 FAX 847 473 4981 website www HDElectricCompany com FACT 1 FEEDER AMMETER CLEARTEST ...

Страница 2: ... grills in the cord storage compartment Never attempt to close the cover while the unit is operating or while any cables are connected Do not connect the FACT 1 unit to a GFI protected circuit Before connecting the FACT to any circuit test and ground that circuit to verify it is both de energized and discharged DO NOT use the FACT 1 if any chance of a back feed exists The FACT 1 contains sensitive...

Страница 3: ...by an internal 24 ohm power resistor In the primary phase to phase fault scenario the LCD ammeter display will also indicate a fault current of approximately 5 Amps with a nominal line voltage of 120V In the secondary side fault scenario a short circuit fault from a feeder transformer secondary conductor to ground occurs This allows more current to flow through the primary windings of this transfo...

Страница 4: ...he Feeder All ClearTest Set the self test mode to assure proper operation The test cable assembly must be removed during the self test 5 POWER This button is the master power switch for the Feeder Ammeter ClearTest Set It is a latching pushbutton type Pressing this button powers up all the electronics and fan for operation 6 AMMETER CLEAR Pressing this button provides 120V AC to the selected bindi...

Страница 5: ...itch again The POWER switch should no longer be illuminated and the fan will stop CAUTION Assure that the feeder cable being connected to the FACT 1 is not energized The Feeder Ammeter ClearTest Set is not designed to be used or connected in the presence of voltages greater than 300V 5 Connect the test cable assembly to the FACT 1 Connect the appropriate test leads to the A B and C phase of the ca...

Страница 6: ...ge will be displayed A ALIVE NO FAULT DETECTED Depending on the number of transformers connected to the network feeder during the test some small current 0 3Amp could be detectable due to the excitation currents of the transformers If the FACT 1 detects maximum current flow in the live selected phase only a phase to ground fault exists and is displayed A ALIVE PHASE A TO GND FAULT If the FACT 1 de...

Страница 7: ... the SELF TEST button momentarily to clear the notice NOTICE LINE CORD POLARITY IS REVERSED PRESS SELF TESTTO CONTINUE DIAGNOSTICS The FACT 1 has built in comprehensive diagnostics to assure that the FACT 1 is operating correctly The test cable assembly should NOT be connected to the FACT 1 during the Self Test The SelfTest mode is entered by pressing the SELF TEST button If at any time you wish t...

Страница 8: ...ny determines is defective HD Electric will at its option either 1 repair or authorize the repair of the Productor 2 replacetheProduct subjecttothefollowing TheProductsaremadeusingpartssourcedfromavarietyofmanufacturers Duetotherapidly changing technology environment parts may become obsolete unavailable over time end of life In the event that a Product cannot be repaired or replaced due to unavai...

Отзывы: