H B X E C O - 0 6 0 0 G e o t h e r m a l C o n t r o l
V e r s i o n 1 . 0 . 0
Page 10
DHW TANK SETUP
Use DHW Tank
- Once this option is enabled you will be
able to program the remaining options for your DHW
setup.
(OFF/ON) Default: OFF
DHW Target
– This option allows you to select your DHW
target temperature in the tank.
(35°F to 180°F) Default: 130°F
Differential
– This is the differential for the DHW tank.
Set this parameter to the desired differential for the
DHW tank.
(2°F to 100°F) Default: 8°F
WWSD-CWSD TIME
This setting is used as a lagtime for CWSD and WWSD.
This will hold the control from entering CWSD or WWSD
until this time has elapsed. The timer starts when the
outdoor temperature hits the CWSD or WWSD. This
setting is useful in the shoulder seasons when there are
large outdoor temperature swings.
(0H to 240H) Default: 0H