10
MGCplus−ML71BS6
A0851-3.1 en
HBM
1
Use the shift key
to change to set-up mode and then press the
function key
. Use the cursor keys to select “Settings CAN1” and
confirm with
.
Settings CAN1
CHANNEL3
1000 kBaud
System
Display
Parameters
Options
Float
8
1200 1/2
Baud rate
Format
Number of signals
Output rate
ID range used
1000 kBaud
500 kBaud
.
.
10 kBaud
Float
32−bit integers
16−bit integers
1 1/s
10 1/s
.
.
1200 1/s
First ID
Last ID
Reset CAN1 port
640
641
Fig. 4.1:
CAN1 / CAN2 dialogue window
2
Use the cursor keys
to choose the baud rate selection field. Use
to
call the selection list and choose the desired baud rate. Confirm with
.
3
Select the output rate in the same way as for 2.
4
Use the cursor keys
to select the “Number of signals” edit field and
enter the desired figure.
5
Select the output rate in the same way as for 2.
6
Use the cursor keys
to select the “First ID” edit field and enter the
desired figure. The “Last ID” edit field is set automatically.
7
Use the shift key
to change to measuring mode and confirm the
follow-up question with
.