Assembly Instructions M8100-EN 

 

M8100-EN   2018-03 

 

7/8

 

 

  

  

 

16.

  Proceed as follows in order to calibrate the temperature 

sensor: 

 

When setting partameters set 

DFM recognition

 to the 

"integrated“ value (in 

Settings / Various)

, continue with Ste

17

. 

 

When setting parameters set 

DFM recognition

 

to the "modular“ 

value (in 

Settings / Various)

, continue with Step 

18

.

 

 

  

 

 

Fig. 11: Sensor calibration during 
integrated operation 

Integrated operation 

17. 

Temperature sensor main line ext 1..8 and temperature 
sensor return line ext. Proceed as follows in order to calibrate 
1..8 , if necessary, the temperature sensor: 

  With a constant deviation set parameter 

Sensor… offset

 under 

Service / Calibration / Temperature

  With a linear deviation, set parameter 

Sensor… asc.cor.

 under 

Service / Calibration / Temperature

 

 

 

Fig. 12: Sensor calibration during modular 
operation 

Operation Modular 

18. 

Proceed as follows, if necessary calibrate the temperature 
sensor for the main line and temperature sensor of the return 
line:  

 

Select the module affected e.g. "A1“ with the 

 or 

 

buttons. 

  With a constant deviation set parameter 

Sensor… offset

 under 

Service / Calibration / Temperature

  With a linear deviation, set parameter 

Sensor… asc.cor.

 under 

Service / Calibration / Temperature

 

 

19.

  Check unit functions. 

 

 

20.

  Switch the unit off by press the 

 key. 

 

21.

  Main switch off. 

  

 

Содержание T24693

Страница 1: ...on for carrying outconversion work on the unit Procedure DANGER Danger to life caused by electric current Touching conductive parts causes a direct danger to life Therefore For all work on the electri...

Страница 2: ...1 Front side of the evaluation unit Fig 2 Rear side of the evaluation unit 4 Proceed as follows in order to remove the cover of the evaluation unit Remove screws Label 1 Fig 1 Detach screws Label 2 F...

Страница 3: ...o the keyboard and attach the cover Attach screws Label 1 Fig 4 Tighten screws Label 2 Fig 5 7 Connect control cable to ext flow rate meter Flow 5 8 Reconnect mains plug and switch on main switch 9 Sw...

Страница 4: ...configuration 10 Proceed as follows to assemble the new printed circuit board DFM 51 A 9 Change to the next screen page with the key Configure ext flow rate meter information on the rating plate Selec...

Страница 5: ...et corresponding parameter Flow rate ext 1 8 Calibration at Service Calibration Flow rate external 1 to 4 or Service Calibration Flow rate external 5 to 8 to ON The flow rate is calibrated automatical...

Страница 6: ...fected e g A1 with the or buttons Set parameter Flow rate calibration at Service Calibration Flow rate to ON The flow rate is calibrated automatically Only in the case of water devices If present set...

Страница 7: ...if necessary the temperature sensor With a constant deviation set parameter Sensor offset under Service Calibration Temperature With a linear deviation set parameter Sensor asc cor under Service Calib...

Страница 8: ...M8100 EN 2018 03 8 8 Parts list Pos Description O ID Pcs 01 Flow rate measuring board DFM 51 T24693 1 02 Assembly instructions German M8100 DE 1 03 Assembly instructions English M8100 EN 1 04 Assembly...

Отзывы: