Assembly Instructions M8100-EN 

 

M8100-EN   2018-03 

 

6/8

 

 

  

 

 

 

 

 

Fig. 10: Calibrate flow rate during modular 
operation 

Operation Modular 

14.

  Proceed as follows to calibrate the corresponding flow rate 

metre: 

  In normal operation operate the device at 40 °C for at least 10 

minutes. 

 

Only in the case of water devices:

 

If present set the parameter 

Pressure relief with unit OFF

 at 

Setting / Miscellaneous

 to "OFF". 

  Switch the unit off using button 

 and wait at least 10 

seconds. 

  Select the module affected e.g. "A1" with the 

 or 

 

buttons. 

  Set parameter 

Flow rate calibration

 at 

Service / Calibration / 

Flow rate

 to "ON". 

  The flow rate is calibrated automatically. 

 

Only in the case of water devices:

 

If present set the parameter 

Pressure relief at unit

 

OFF

 at 

Setting / Miscellaneous

 to "ON". 

 

Switch the unit on with the 

 key. 

   

 

 

15.

  Inspection of calibration of Flow rate meter 

  In normal operation operate the unit at 40 °C for at least 5 

minutes following calibration. 

  Close the corresponding shut-off valve between main and 

return lines. 

  Flow rate returns to 0 L/min. 

  If this is not the case repeat the Flow rate meter point. 

 

 

  Repeat the Flow rate meter calibration item for each measuring 

circuit. 

   

 

Содержание T24693

Страница 1: ...on for carrying outconversion work on the unit Procedure DANGER Danger to life caused by electric current Touching conductive parts causes a direct danger to life Therefore For all work on the electri...

Страница 2: ...1 Front side of the evaluation unit Fig 2 Rear side of the evaluation unit 4 Proceed as follows in order to remove the cover of the evaluation unit Remove screws Label 1 Fig 1 Detach screws Label 2 F...

Страница 3: ...o the keyboard and attach the cover Attach screws Label 1 Fig 4 Tighten screws Label 2 Fig 5 7 Connect control cable to ext flow rate meter Flow 5 8 Reconnect mains plug and switch on main switch 9 Sw...

Страница 4: ...configuration 10 Proceed as follows to assemble the new printed circuit board DFM 51 A 9 Change to the next screen page with the key Configure ext flow rate meter information on the rating plate Selec...

Страница 5: ...et corresponding parameter Flow rate ext 1 8 Calibration at Service Calibration Flow rate external 1 to 4 or Service Calibration Flow rate external 5 to 8 to ON The flow rate is calibrated automatical...

Страница 6: ...fected e g A1 with the or buttons Set parameter Flow rate calibration at Service Calibration Flow rate to ON The flow rate is calibrated automatically Only in the case of water devices If present set...

Страница 7: ...if necessary the temperature sensor With a constant deviation set parameter Sensor offset under Service Calibration Temperature With a linear deviation set parameter Sensor asc cor under Service Calib...

Страница 8: ...M8100 EN 2018 03 8 8 Parts list Pos Description O ID Pcs 01 Flow rate measuring board DFM 51 T24693 1 02 Assembly instructions German M8100 DE 1 03 Assembly instructions English M8100 EN 1 04 Assembly...

Отзывы: