Pentair/Purex/MiniMax

1.  Turn power off to heater.
2.  Remove factory installed jumper from the “Ext Switch” connector.
3.  Wire the OnCommand to the “Ext Switch” connector as shown below.
4.  The wires to the OnCommand must be separated from any line voltage wires.  Failure to follow these

instructions may cause erratic operation of the heater.

5.  Set the Power (Thermostat Select) switch to either “Pool” or “Spa”.
6.  Set the “Pool” and “Spa” thermostats to their maximum settings.

Raypak RP2100 Pool/Spa Heater

1.  Turn power off to heater.
2.  Push the mode button to “spa” mode.
3.  Set the temperature to the maximum.
4.  Push the mode button to “OFF”.
5.  Lastly, plug the prewired connector in the P7 position on the board.

!

 

 IMPORTANT:  The heater will display “OFF” when it is being remotely controlled by the

OnCommand.  Some homeowners see the “OFF” display and, thinking this is a mistake, change the

mode to “POOL” or “SPA” which then disables the remote control by the OnCommand.  To prevent

this:  Remove the heater touch pad connector (P5) which will disable the touchpad.

10

Filter Config.

+ to view/change

Filter Pump 

1 Speed

Freeze Protect 

Enabled

Lowest Speed

10%

Highest Speed

100%

Push to access pump options

Rotates between 1-speed (default), 2-speed and variable speed options

Toggle between Enabled (default) and Disabled Freeze Protection 

Adjust the lowest speed desired for variable speed operation

Adjust the highest speed desired for variable speed operation

Move to next menu item

Move to previous/next configuration menu

Move to next menu item or previous/next configuration menu

Move to next menu item

Move to next menu item

if “Variable Speed” is selected

if “Variable Speed” is selected

Freeze Temp

38ºF

Freeze Protect

High Speed

Adjust the desired freeze protection temperature (33ºF - 42ºF)

Toggle between high speed (default) and low speed

Move to previous/next configuration menu

Move to next menu item

if “Freeze Protect” is enabled

if “Freeze Protect” is enabled
and “1-speed Filter” is not selected

Filter Pump

For 2-speed pumps:  When a 2-speed pump is configured, one of  the AUX relays must also be
configured to control the low speed motor winding on the pump.  Refer to the appropriate sections in
the Installation manual for specific information regarding the control logic for 2-speed and variable
speed pump operation.

For the Hayward Tristar variable speed pump:  The Filter relay is used to supply input power to the
VSC pump control.  The relay will be on when the filter pump output is on.  When the filter pump
output is off, the relay will be off.  On , off and speed is controlled by commands sent to the pump.

Lowest Speed

This is the lowest speed that the variable speed pump is allowed to run at. It is used as the lower limit
in the Low Speed Settings Menu. Set lowest speed from 10% (default) to 50%.

Highest Speed

This is the highest speed that the variable speed pump is allowed to run at. It is used as the upper limit

in the High Speed Settings Menu.  Also, this is the speed that the pump will run at during the first 3

minutes of operation anytime the pump has been off for more than 30 seconds. Set highest speed from

20% to 100% (default).

Freeze Protection

Freeze protection is used to protect the pool and plumbed equipment against freeze damage.  If freeze

protection is enabled and the AIR temperature sensor falls below the freeze threshold (see below), the

OnCommand will turn on the filter pump to circulate the water. If “Pool and Spa” is selected in the Pool/

Spa sub-menu, the valves will also alternate between the pool and spa every 30 minutes and the filter

pump will turn off while the valves are turning.  The chlorinator will not operate if freeze protection is
the only reason the pump is running.

Freeze Protection Speed

This menu only appears if freeze protection is enabled and the pump is configured for 2-speed or
variable speed pump operation. This is the speed that the pump will run at during freeze protection
operation. Select high (default) or low speed operation.

Freeze Protection Temperature

Select the temperature to be used for freeze protection.  Temperature is adjustable from 33ºF  -  42ºF
(1ºC - 6ºC).  38ºF (3ºC) is default. This threshold will be used for all outputs that have freeze protection
enabled.

17

MINIMAX

Ext.

Switch

Remove 

Factory Jumper

P7

Light Blue

Black

Orange Stripe

Orange

Stripe

Black 

RAYPAK RP2100

Drawing is for digital heater. If heater is a
millivolt (analog) run red wires from Fireman’s
Switch to heater relay.

Содержание ONCOM

Страница 1: ...Hayward OnCommand Automation Installation Manual ONCOM ONCOM ACT ONCOM RC ONCOM ACT RC www haywardnet com for models ...

Страница 2: ...arked Earth Ground is located inside the wiring compartment To reduce the risk of electric shock this terminal must be connected to the grounding means provided in the electric supply service panel with a continuous copper wire equivalent in size to the circuit conductors supplying the equipment A wire connector is provided on this unit to connect a minimum 8AWG 8 4 mm solid copper conductor betwe...

Страница 3: ...emote Control 2 Base Station 3 Optional ValveActuators 3 2 Plumbing Plumbing Configuration 4 3 Electrical Grounding 5 Wiring Input Wiring 5 High Voltage Pool Equipment 6 Low Voltage Wiring 8 4 Configuration Configuration Menu 13 5 System Startup Before Startup 26 and Checkout Heater Checkout 26 Service Mode 27 6 Warranty OnCommand Limited Warranty 28 ...

Страница 4: ...ndheld Wireless Remote Control AQL2 SS RF Wireless Spa Side Remote Control Included with ONCOM RC ONCOM ACT RC AQL2 BASE RF Base Station required if usingAQL2 SS RF included with ONCOM RC ONCOM ACT RC AQR Aqua Rite chlorination unit AQL DIM Light Dimmer Relay refer toAQL DIM manual to ensure dimmer wattage specifications match lighting wattage GV A 24 ValveActuator V A xx Valve Actuator xx 1P 1 5 ...

Страница 5: ...insulation and whitepaint Air Sensor Mount the air sensor outdoors IMPORTANT Mount the air sensor out of direct sunlight Solar Sensor For solar applications mount the sensor near the solar collector array so that it is exposed to the same sunlight as the collectors Use additional cable 20AWG if necessary Wireless Remote Controls A single Base Station must be installed on the OnCommand in order to ...

Страница 6: ...station andthentightenthenutfromtheinside AlsorefertotheBaseStationinstallationmanualandthediagram on page 12 Optional Valve Actuators included with ONCOM ACT ONCOM ACT RC ForoptionalactuatorsusedwiththeOnCommand notethattheinternalcamsintheactuatormayalsohavetobe adjusted depending on the way the actuator is mounted on the valve and the desired valve action RETURN SUCTION OUT Common IN Common OUT...

Страница 7: ...efilterpump is on and the system is in the pool only operating mode 6 Theplumbingdiagramaboveisintendedtobeusedasageneralguidelineandisnotacompleteplumbing schematicforthepool 7 Theairsensormustbeinstalledifthefreezeprotectionfeatureisenabledforthefilter valvesorauxoutputs orifthechlorinatorisenabled FILTER SOLAR BOOST PUMP SOLAR VALVE HEATER HEATER BYPASS VALVE manual CELL FLOW SWITCH CHECK VALVE...

Страница 8: ...clude actuators sensors heaters etc All high voltage connections such as PCB input power pumps lights etc are made on the right side of the divider Grounding AgroundbusbarislocatedinthehighvoltagecompartmentoftheOnCommand Connectagroundwirefromthe primaryelectricalpaneltothisgroundbusbar Alsousethisgroundbartogroundeachpieceofhighvoltage 120 or 240VAC equipment that is connected to the OnCommand c...

Страница 9: ...5A at 120V Refer to the diagram below for typical relay wiring WARNING Do not use the OnCommand to control an automatic pool cover Swim mers may become entrapped underneath the cover 6 240 VAC Load 120 VAC Load Wiring relays for 240 VAC Pool Equipment Wiring relays for 120 VAC Pool Equipment 120 VAC Load Wiring GFCB for 120 VAC Pool Equipment ...

Страница 10: ...eeltooneoftheAUXoutputs Hayward Variable Speed Filter Pump Proper installation of the Hayward TriStar Variable Speed Control VSC includeshighvoltageinputwiring communicationwiring andmenuconfiguration settings Refertothe following diagram for proper input wiring to the VSC Wiring from a 240V breaker must connect through the OnCommand sFilterrelay TheFilterrelayisusedtosupplyinputpowertotheVSCpumpc...

Страница 11: ...h 24V control circuits Refer to the diagram on the following page for a generic connection The manualssuppliedwithmostheatersalsoincludespecificwiringinstructionsforconnectingtheheatertoanexternal control usuallyidentifiedas 2 wire remotecontrol Formillivoltorlinevoltageheaters contactGoldlineTech support 908 355 7995 Refertothediagramsandtheinformationonthefollowingpagesformoredetailsonthe connec...

Страница 12: ...nd to terminals 1 2 see diagram 3 Leave jumper attached to terminals 4 5 4 Move BYPASS dipswitch on heater circuit board to ON position up 5 Turn heater power back on 6 Switchheatertoeither Pool or Spa itdoesn tmakeanydifferencewhichisselected theOnCommandwill take control 7 Heater display should be bO for bypass On 8 HeaterwillfirewheneverOnCommandrequests whenOnCommand Heater LEDisilluminated 9 ...

Страница 13: ...ode button to spa mode 3 Set the temperature to the maximum 4 Push the mode button to OFF 5 Lastly plug the prewired connector in the P7 position on the board IMPORTANT The heater will display OFF when it is being remotely controlled by the OnCommand Some homeowners see the OFF display and thinking this is a mistake change the mode to POOL or SPA which then disables the remote control by the OnCom...

Страница 14: ...he maximum wiring distance is 500 feet 160 meters Note that the terminals on both the VSC interface board and the OnCommand main board are numbered The terminal connections should be matched between both terminal blocks connect 1 to 1 2 to 2 etc The communications cable should be routed through the knockout hole on the left side of the VSC enclosure and a watertight fitting should be used to keep ...

Страница 15: ...r temperature andsolartemperature areincluded IftheOnCommandisbeingusedtocontrolasolarheatingsystem thesolar sensorisrequired Thesensorsareprovidedwitha15ft cable Ifalongercableisrequired contacttheGoldline Technical Support department for information on suitable cable types and splices See page 2 and the diagram belowforinstallationinformation BaseStation Plug in the pigtail connector from the wi...

Страница 16: ...gurationMenu Forexample insteadoftheLightsbuttonturningonandoffthepoollight only thebuttoncanbeprogrammedtoturnonthepoollight turnonthebuglight turnoffthepoolcleaner andturn on the music all at the same time This convenient feature can be assigned to either one of theAux buttons the LightsbuttonortheValve3automatedfunction Beforeassigningandconfiguringallthedesiredfunctionsandtheircontrolparameter...

Страница 17: ...emperature will return to the group setpoint that was originally programmedintheConfigurationMenu Tochangethesetpointwhilethegroupisrunning gototheSettingsmenu andpressthe buttonwhile GroupControl isdisplayed Thesetpointwillchangeandberetainedasthenew normalheatersetpoint Super Chlorinate requires external chlorinator IfaHaywardSwimpureorGoldlineAquaRitechlorinatorisused theOnCommandcanbeprogramme...

Страница 18: ...ion menu items Press BOTH buttons SIMULTANEOUSLY for 5 seconds to unlock NOTE The configuration menu automatically locks after 2 minutes of no buttons being pressed to prevent unauthorized people from changing the control logic inadvertently and possibly damaging the pool equipment or causing a call back to fix the configuration Configuration Menu Items Eachitemneedstobeprogrammedandmaycontainaddi...

Страница 19: ...rammed in increments of 5 minutes from Manual On Off 0 minutes to 21 00 21 hours The filter is forced on during this time period Spa Spillover When spa spillover is Enabled and Pool and Spa the homeowner will be able to rotate through Pool Only both suction and return valves switched to pool Spa Only both suction and return valves switched to spa and Spillover suction valve switched to pool and re...

Страница 20: ... be off On off and speed is controlled by commands sent to the pump Lowest Speed This is the lowest speed that the variable speed pump is allowed to run at It is used as the lower limit in the Low Speed Settings Menu Set lowest speed from 10 default to 50 Highest Speed This is the highest speed that the variable speed pump is allowed to run at It is used as the upper limit in the High Speed Settin...

Страница 21: ...ting will be used Heater Cooldown This feature ensures that the heater cools down before water circulation is stopped When enabled the OnCommand will continue to run the filter pump for 5 minutes after the heater turns off During this period the filter pump LED will flash and also a Heater Cooldown X XX remaining message will scroll on the display When the filter pump is running and the heater is ...

Страница 22: ...urn on when the water temperature is less than the desired temperature settingAND the solar sensor is hotter than the water The desired temperature is in the Settings Menu If applicable the homeowner will be prompted to enter separate pool and spa desired temperature settings Depending on the position of the pool spa suction valve the proper temperature setting will be used Solar Extend If Enabled...

Страница 23: ... and Lights Freeze Protection will not be necessary and should be disabled If no pool lights are used the lights relay can be used to control other pool devices that may require these options The function of each option is shown below Manual On Off default the lights relay will alternate between turning on and off when the LIGHTS button is pressed There is no automatic control logic Countdown Time...

Страница 24: ...e push of the Lights button When setting up a Group function refer to page 13 for specific programming information There are two Group menus the first menu determines how the group command will be initiated Manual On Off Countdown Timer or Timeclock and the second menu selects the desired functions and their respective control parameters Lights Freeze Protection This function helps protect equipme...

Страница 25: ... the OnCommand to control an automatic pool cover Swim mers may become entrapped underneath the cover Aux1 Function Manual On Off default the aux relay will alternate between turning on and off when the aux button is pressed There is no automatic control logic Countdown Timer the aux relay will turn on when the AUX button is pressed and then will turn off automatically after a programmed time see ...

Страница 26: ...ush of the Aux1 button When setting up a Group function refer to page 13 for specific programming information There are two Group menus the first menu determines how the group command will be initiated Manual On Off Countdown Timer or Timeclock and the second menu selects the desired functions and their respective control parameters Aux1 Freeze Protection This function protects the pool plumbing a...

Страница 27: ...nction is initiated and shuts off when the Group function is terminated See Valve3 Group section for operation information for the Group function Valve3 Filter the valve operates whenever the Filter relay is on Valve3 Lights the valve operates whenever the Lights relay is on Valve3 Aux1 the valve operates whenever the Aux1 relay is on Valve3 Aux2 the valve operates whenever the Aux2 relay is on Va...

Страница 28: ...evious next configuration menu Toggle between 7 day default and Weekend Weekday time options This selection affects ALL of the timeclock logic in the OnCommand If 7 day is selected each timeclock will have one set of turn on turn off settings that operate every day of the week If Weekend Weekdays option is selected then the user can enter one set of turn on turn off times for the weekend fixed as ...

Страница 29: ...Spa Heater Thefilterpumpisrunning Ifthepoolhassolarheatandthesolarpriorityfeatureisenabled ConfigurationMenu SolarConfig then solar must be off in order for the heater to fire The easiest way to force solar off is to go to the Settings Menu Pool Solar Spa Solar and temporarily lower the temperature settings below the current water temperature 2 Check that the heater is running If not then check Po...

Страница 30: ...emode pushtheSERVICEbuttononceonthemainunitkeypad Thiswillinitiallyturnalloutputs offandthenallowyoutoturnoutputson offmanuallyatthemaindisplay only In servicemode thebuttonson theoptionalspasideremotewillturnoutputsoff butwillnotturnanyoutputon Heatercontroloutputsandsolar control outputs are prevented from turning on if the water temperature exceeds 104ºF 40ºC Pushing the SERVICE button again wi...

Страница 31: ...process of installation 2 Damageresultingfromimproperinstallationincludinginstallationonpoolslargerthantheproductrating 3 Problemsresultingfromfailuretoinstall operateormaintaintheproduct s inaccordancewiththerecommen dationscontainedintheownersmanual s 4 Problemsresultingfromfailuretomaintainpoolwaterchemistryinaccordancewiththerecommendationsinthe ownersmanual s 5 Problemsresultingfromtampering ...

Страница 32: ...enu spa heater temperature pool heater temperature spa solar temperature pool solar temperature superchlorinate spa chlorinator setting pool chlorinator setting spa high low speed pool high low speed day and time backlit display light beeper teach wireless remote wireless channel timers menu pool filter pump spa lights aux1 aux2 valve3 superchlorinate diagnostic menu salt level water sensor air se...

Отзывы: