background image

Low Voltage Wiring

Valve Actuators

The OnCommand can control up to three automatic valve actuators.  Two of the valve outputs are dedicated to the

pool/spa suction (Valve2) and return (Valve1) valves.  Valve3 is for general purpose use (solar, water feature, in-

floor cleaner, etc.).

For installations with solar heating, Goldline offers the AQ-SOL-KIT-xx solar kit that contains a valve, actuator,

and extra temperature sensor. The “xx” indicates the valve type from the choices below:

-1P

1.5” Positive Seal

-2P

2” Positive Seal

The OnCommand is compatible with standard valve actuators manufactured by Hayward, Pentair/Compool, and

Jandy.  See diagram on page 5 for the location of valve connectors.

Heater Control

The OnCommand provides a set of low voltage dry contacts that can be connected to most gas heaters or heat

pumps with 24V control circuits.  Refer to the diagram on the following page for a generic connection.  The

manuals supplied with most heaters also include specific wiring instructions for connecting the heater to an external

control (usually identified as “2-wire” remote control). For millivolt or line voltage heaters, contact Goldline Tech

support, 908-355-7995.  Refer to the diagrams and the information on the following pages for more details on the

connection to several popular heaters.

Generic Heaters

1. Wire heater to 120/240V power source per the instructions in the heater manual.  The OnCommand does

NOT control the power going to the heater.

2. Wire the OnCommand dry contact heater output per the diagram below.  Many internal parts of the heater can

get very hot--see the heater manufacturer’s recommendations on the minimum temperature rating for wires.  If

no guidance is given, use 105°C rated wire.

3. Set any ON/OFF switch on the heater to ON.
4. Set the thermostat(s) on the heater to the maximum (hottest) setting.

8

Solar Config.

+ to view/change

Solar

Disabled

Solar-Extend 

Disabled

Solar Priority

Disabled

Push to access solar options

Toggle between Enabled and Disabled (default) Solar

Toggle between Enabled and Disabled (default) Solar Extend

Toggle between Enabled and Disabled (default) Solar Priority

Move to previous/next configuration menu

Move to next menu item or previous/next configuration menu

Move to next menu item

Move to next menu item

if “Solar” is enabled

if “Solar” is enabled

Allow Low Speed 

Disabled

Toggle between Enabled and Disabled (default) 
Move to next menu item or previous/next configuration menu

if “Solar” is enabled and
“1-speed Filter” is not selected

Solar

If the solar control logic is “Enabled”, several additional steps must be taken to ensure proper operation
of the solar system.  If the solar is operated by a valve, then the Valve3 output must be setup for solar
logic.   If the solar is operated by a pump, then one of the AUX relays must be set up for solar logic.
Also, the “solar” temperature sensor must be installed.  This sensor is typically mounted near the
collector array and is used to sense whether sufficient solar heat is available.

If solar is “Enabled”, the valve or solar pump relay will turn on when the water temperature is less than
the desired temperature setting AND the solar sensor is hotter than the water.  The desired temperature
is in the “Settings Menu”.  If applicable, the homeowner will be prompted to enter separate pool and
spa desired temperature settings.  Depending on the position of the pool/spa suction valve, the
proper temperature setting will be used.

Solar Extend

If “Enabled”, the filter extend logic keeps the filter pump running beyond the normal turn-off time if
solar heat is still available.  When solar heat is no longer available, both the solar valve/pump and filter
pump will turn off simultaneously.  Solar extend will NOT cause the filter pump to turn on, it will only
delay the turn off time when solar is operating.

Solar Priority

If both “Solar Control” and “Heater Control” are enabled, the Solar Priority feature will keep the
conventional heater off whenever solar heat is available.  This provides the most cost effective way of
heating the pool.  When solar heat is not available, the conventional heater will operate normally.

Allow Low Speed

This menu only appears if the pool filter is configured for 2-speed or variable speed operation.  During
default operation, high speed mode is used whenever the solar heater is on.  If Allow Low Speed is
enabled, low speed pump operation will be allowed during solar heating except for the first 3 minutes
after solar heat turns on.

19

Ignition/Valve

Heater

Kill Switch

Thermostat

Содержание ONCOM

Страница 1: ...Hayward OnCommand Automation Installation Manual ONCOM ONCOM ACT ONCOM RC ONCOM ACT RC www haywardnet com for models ...

Страница 2: ...arked Earth Ground is located inside the wiring compartment To reduce the risk of electric shock this terminal must be connected to the grounding means provided in the electric supply service panel with a continuous copper wire equivalent in size to the circuit conductors supplying the equipment A wire connector is provided on this unit to connect a minimum 8AWG 8 4 mm solid copper conductor betwe...

Страница 3: ...emote Control 2 Base Station 3 Optional ValveActuators 3 2 Plumbing Plumbing Configuration 4 3 Electrical Grounding 5 Wiring Input Wiring 5 High Voltage Pool Equipment 6 Low Voltage Wiring 8 4 Configuration Configuration Menu 13 5 System Startup Before Startup 26 and Checkout Heater Checkout 26 Service Mode 27 6 Warranty OnCommand Limited Warranty 28 ...

Страница 4: ...ndheld Wireless Remote Control AQL2 SS RF Wireless Spa Side Remote Control Included with ONCOM RC ONCOM ACT RC AQL2 BASE RF Base Station required if usingAQL2 SS RF included with ONCOM RC ONCOM ACT RC AQR Aqua Rite chlorination unit AQL DIM Light Dimmer Relay refer toAQL DIM manual to ensure dimmer wattage specifications match lighting wattage GV A 24 ValveActuator V A xx Valve Actuator xx 1P 1 5 ...

Страница 5: ...insulation and whitepaint Air Sensor Mount the air sensor outdoors IMPORTANT Mount the air sensor out of direct sunlight Solar Sensor For solar applications mount the sensor near the solar collector array so that it is exposed to the same sunlight as the collectors Use additional cable 20AWG if necessary Wireless Remote Controls A single Base Station must be installed on the OnCommand in order to ...

Страница 6: ...station andthentightenthenutfromtheinside AlsorefertotheBaseStationinstallationmanualandthediagram on page 12 Optional Valve Actuators included with ONCOM ACT ONCOM ACT RC ForoptionalactuatorsusedwiththeOnCommand notethattheinternalcamsintheactuatormayalsohavetobe adjusted depending on the way the actuator is mounted on the valve and the desired valve action RETURN SUCTION OUT Common IN Common OUT...

Страница 7: ...efilterpump is on and the system is in the pool only operating mode 6 Theplumbingdiagramaboveisintendedtobeusedasageneralguidelineandisnotacompleteplumbing schematicforthepool 7 Theairsensormustbeinstalledifthefreezeprotectionfeatureisenabledforthefilter valvesorauxoutputs orifthechlorinatorisenabled FILTER SOLAR BOOST PUMP SOLAR VALVE HEATER HEATER BYPASS VALVE manual CELL FLOW SWITCH CHECK VALVE...

Страница 8: ...clude actuators sensors heaters etc All high voltage connections such as PCB input power pumps lights etc are made on the right side of the divider Grounding AgroundbusbarislocatedinthehighvoltagecompartmentoftheOnCommand Connectagroundwirefromthe primaryelectricalpaneltothisgroundbusbar Alsousethisgroundbartogroundeachpieceofhighvoltage 120 or 240VAC equipment that is connected to the OnCommand c...

Страница 9: ...5A at 120V Refer to the diagram below for typical relay wiring WARNING Do not use the OnCommand to control an automatic pool cover Swim mers may become entrapped underneath the cover 6 240 VAC Load 120 VAC Load Wiring relays for 240 VAC Pool Equipment Wiring relays for 120 VAC Pool Equipment 120 VAC Load Wiring GFCB for 120 VAC Pool Equipment ...

Страница 10: ...eeltooneoftheAUXoutputs Hayward Variable Speed Filter Pump Proper installation of the Hayward TriStar Variable Speed Control VSC includeshighvoltageinputwiring communicationwiring andmenuconfiguration settings Refertothe following diagram for proper input wiring to the VSC Wiring from a 240V breaker must connect through the OnCommand sFilterrelay TheFilterrelayisusedtosupplyinputpowertotheVSCpumpc...

Страница 11: ...h 24V control circuits Refer to the diagram on the following page for a generic connection The manualssuppliedwithmostheatersalsoincludespecificwiringinstructionsforconnectingtheheatertoanexternal control usuallyidentifiedas 2 wire remotecontrol Formillivoltorlinevoltageheaters contactGoldlineTech support 908 355 7995 Refertothediagramsandtheinformationonthefollowingpagesformoredetailsonthe connec...

Страница 12: ...nd to terminals 1 2 see diagram 3 Leave jumper attached to terminals 4 5 4 Move BYPASS dipswitch on heater circuit board to ON position up 5 Turn heater power back on 6 Switchheatertoeither Pool or Spa itdoesn tmakeanydifferencewhichisselected theOnCommandwill take control 7 Heater display should be bO for bypass On 8 HeaterwillfirewheneverOnCommandrequests whenOnCommand Heater LEDisilluminated 9 ...

Страница 13: ...ode button to spa mode 3 Set the temperature to the maximum 4 Push the mode button to OFF 5 Lastly plug the prewired connector in the P7 position on the board IMPORTANT The heater will display OFF when it is being remotely controlled by the OnCommand Some homeowners see the OFF display and thinking this is a mistake change the mode to POOL or SPA which then disables the remote control by the OnCom...

Страница 14: ...he maximum wiring distance is 500 feet 160 meters Note that the terminals on both the VSC interface board and the OnCommand main board are numbered The terminal connections should be matched between both terminal blocks connect 1 to 1 2 to 2 etc The communications cable should be routed through the knockout hole on the left side of the VSC enclosure and a watertight fitting should be used to keep ...

Страница 15: ...r temperature andsolartemperature areincluded IftheOnCommandisbeingusedtocontrolasolarheatingsystem thesolar sensorisrequired Thesensorsareprovidedwitha15ft cable Ifalongercableisrequired contacttheGoldline Technical Support department for information on suitable cable types and splices See page 2 and the diagram belowforinstallationinformation BaseStation Plug in the pigtail connector from the wi...

Страница 16: ...gurationMenu Forexample insteadoftheLightsbuttonturningonandoffthepoollight only thebuttoncanbeprogrammedtoturnonthepoollight turnonthebuglight turnoffthepoolcleaner andturn on the music all at the same time This convenient feature can be assigned to either one of theAux buttons the LightsbuttonortheValve3automatedfunction Beforeassigningandconfiguringallthedesiredfunctionsandtheircontrolparameter...

Страница 17: ...emperature will return to the group setpoint that was originally programmedintheConfigurationMenu Tochangethesetpointwhilethegroupisrunning gototheSettingsmenu andpressthe buttonwhile GroupControl isdisplayed Thesetpointwillchangeandberetainedasthenew normalheatersetpoint Super Chlorinate requires external chlorinator IfaHaywardSwimpureorGoldlineAquaRitechlorinatorisused theOnCommandcanbeprogramme...

Страница 18: ...ion menu items Press BOTH buttons SIMULTANEOUSLY for 5 seconds to unlock NOTE The configuration menu automatically locks after 2 minutes of no buttons being pressed to prevent unauthorized people from changing the control logic inadvertently and possibly damaging the pool equipment or causing a call back to fix the configuration Configuration Menu Items Eachitemneedstobeprogrammedandmaycontainaddi...

Страница 19: ...rammed in increments of 5 minutes from Manual On Off 0 minutes to 21 00 21 hours The filter is forced on during this time period Spa Spillover When spa spillover is Enabled and Pool and Spa the homeowner will be able to rotate through Pool Only both suction and return valves switched to pool Spa Only both suction and return valves switched to spa and Spillover suction valve switched to pool and re...

Страница 20: ... be off On off and speed is controlled by commands sent to the pump Lowest Speed This is the lowest speed that the variable speed pump is allowed to run at It is used as the lower limit in the Low Speed Settings Menu Set lowest speed from 10 default to 50 Highest Speed This is the highest speed that the variable speed pump is allowed to run at It is used as the upper limit in the High Speed Settin...

Страница 21: ...ting will be used Heater Cooldown This feature ensures that the heater cools down before water circulation is stopped When enabled the OnCommand will continue to run the filter pump for 5 minutes after the heater turns off During this period the filter pump LED will flash and also a Heater Cooldown X XX remaining message will scroll on the display When the filter pump is running and the heater is ...

Страница 22: ...urn on when the water temperature is less than the desired temperature settingAND the solar sensor is hotter than the water The desired temperature is in the Settings Menu If applicable the homeowner will be prompted to enter separate pool and spa desired temperature settings Depending on the position of the pool spa suction valve the proper temperature setting will be used Solar Extend If Enabled...

Страница 23: ... and Lights Freeze Protection will not be necessary and should be disabled If no pool lights are used the lights relay can be used to control other pool devices that may require these options The function of each option is shown below Manual On Off default the lights relay will alternate between turning on and off when the LIGHTS button is pressed There is no automatic control logic Countdown Time...

Страница 24: ...e push of the Lights button When setting up a Group function refer to page 13 for specific programming information There are two Group menus the first menu determines how the group command will be initiated Manual On Off Countdown Timer or Timeclock and the second menu selects the desired functions and their respective control parameters Lights Freeze Protection This function helps protect equipme...

Страница 25: ... the OnCommand to control an automatic pool cover Swim mers may become entrapped underneath the cover Aux1 Function Manual On Off default the aux relay will alternate between turning on and off when the aux button is pressed There is no automatic control logic Countdown Timer the aux relay will turn on when the AUX button is pressed and then will turn off automatically after a programmed time see ...

Страница 26: ...ush of the Aux1 button When setting up a Group function refer to page 13 for specific programming information There are two Group menus the first menu determines how the group command will be initiated Manual On Off Countdown Timer or Timeclock and the second menu selects the desired functions and their respective control parameters Aux1 Freeze Protection This function protects the pool plumbing a...

Страница 27: ...nction is initiated and shuts off when the Group function is terminated See Valve3 Group section for operation information for the Group function Valve3 Filter the valve operates whenever the Filter relay is on Valve3 Lights the valve operates whenever the Lights relay is on Valve3 Aux1 the valve operates whenever the Aux1 relay is on Valve3 Aux2 the valve operates whenever the Aux2 relay is on Va...

Страница 28: ...evious next configuration menu Toggle between 7 day default and Weekend Weekday time options This selection affects ALL of the timeclock logic in the OnCommand If 7 day is selected each timeclock will have one set of turn on turn off settings that operate every day of the week If Weekend Weekdays option is selected then the user can enter one set of turn on turn off times for the weekend fixed as ...

Страница 29: ...Spa Heater Thefilterpumpisrunning Ifthepoolhassolarheatandthesolarpriorityfeatureisenabled ConfigurationMenu SolarConfig then solar must be off in order for the heater to fire The easiest way to force solar off is to go to the Settings Menu Pool Solar Spa Solar and temporarily lower the temperature settings below the current water temperature 2 Check that the heater is running If not then check Po...

Страница 30: ...emode pushtheSERVICEbuttononceonthemainunitkeypad Thiswillinitiallyturnalloutputs offandthenallowyoutoturnoutputson offmanuallyatthemaindisplay only In servicemode thebuttonson theoptionalspasideremotewillturnoutputsoff butwillnotturnanyoutputon Heatercontroloutputsandsolar control outputs are prevented from turning on if the water temperature exceeds 104ºF 40ºC Pushing the SERVICE button again wi...

Страница 31: ...process of installation 2 Damageresultingfromimproperinstallationincludinginstallationonpoolslargerthantheproductrating 3 Problemsresultingfromfailuretoinstall operateormaintaintheproduct s inaccordancewiththerecommen dationscontainedintheownersmanual s 4 Problemsresultingfromfailuretomaintainpoolwaterchemistryinaccordancewiththerecommendationsinthe ownersmanual s 5 Problemsresultingfromtampering ...

Страница 32: ...enu spa heater temperature pool heater temperature spa solar temperature pool solar temperature superchlorinate spa chlorinator setting pool chlorinator setting spa high low speed pool high low speed day and time backlit display light beeper teach wireless remote wireless channel timers menu pool filter pump spa lights aux1 aux2 valve3 superchlorinate diagnostic menu salt level water sensor air se...

Отзывы: