-2-

-3-

1

          

250 VAC 200mA Slow Blow Fuse 

             Fused power connection for circuit protection.

2

          

Lithium Battery

             On board clock back up.
             

CAUTION! DANGER OF EXPLOSION IF BATTERY IS INCORRECTLY  

             REPLACED. REPLACE ONLY WITH THE SAME OR EQUIVALENT    
             TYPE RECOMMENDED BY THE MANUFACTURER. DISPOSE OF USED  
             BATTERIES ACCORDING TO THE MANUFACTURER'S INSTRUCTIONS.

3

          Power Transformer

             Linear power supply for reliability and low noise.

4

          120 VAC Power Supply Terminals

             2-position Euro style pluggable connector for 120 VAC, 60Hz. Line to  
             neutral power connection.

5

          Auxiliary Input Status LED

             Indicates alarm condition for the auxiliary input.

6

          Membrane Switch Pin Connector

             Connection point for push button panel.

7

          Auxiliary Input Contacts

             Contact closure or pull-to-ground (10mA max.)

8

          Upstream RS232 Input Jack

             Connection point for Upstream RS232 network.

COMPONENT LOCATIONS

Figure 1

BACK

FRONT

  

9

          Upstream RS485 Connection Point

             5-position Euro style pluggable connector for upstream RS-485           
             network. 2 or 4-wire selectable.

10       

Downstream RS485 Connection Point

             5-position Euro style pluggable connector for downstream RS-485    
             network. 2 or 4-wire selectable.

11

        12 VDC Power Port

             Alternate 12 VDC connection point for use with plug in wall mount    
             transformer or power supply. (Auxiliary input is disabled if 12VDC    
             power is used)

12

        Membrane Switch Ribbon Cable

            

             

13

        Infrared Port

             Palm Pilot OS® communications port.

14

        Tri Color LED

             Green = Normal Operation. No network devices are in warning or alarm  
             mode.
             Yellow = Warning. One or more network devices are in warning mode.
             Red = Alarm. One or more network devices are in alarm mode or the  
             auxiliary input is active.

15       

Liquid Crystal Display

             High resolution LCD with adjustable backlight.

Содержание H8932

Страница 1: ...arge backlit LCD easy to read Palm OS Infrared interface instantly upload data from all Veris devices to a palm pilot or use a Modbus network Modbus protocol communications one digital input standard Upstream communications selectable RS485 RS232 or infrared Multi color LED provides quick system status Thisproductisnotintendedforlifeorsafetyapplications Thisproductisnotintendedforinstallationinhaz...

Страница 2: ... 10mA max 8 Upstream RS232 Input Jack Connection point for Upstream RS232 network COMPONENT LOCATIONS Figure1 BACK FRONT 9 Upstream RS485 Connection Point 5 position Euro style pluggable connector for upstream RS 485 network 2 or 4 wire selectable 10 Downstream RS485 Connection Point 5 position Euro style pluggable connector for downstream RS 485 network 2 or 4 wire selectable 11 12 VDC Power Port...

Страница 3: ...etwork Display C to threaded studs using four 6 32 screws D provided 4 Connect membrane switch ribbon cable to membrane switch pin connector H8930 Component List A Face Plate with membrane switch ribbon cable B Four threaded stand offs C Network Display D Four 6 32 screws H8936 Assembly Example NETWORK DISPLAY FACEPLATE A BOX LID or PANEL NETWORK DISPLAY C 4 ea 6 32 SCREWS D 4 ea THREADED STAND OF...

Страница 4: ...hupstreamconnection enabled Wheninfraredcommu nicationsaredesired donotenable upstreamRS232orRS485port NOTE Connectingmultiplenetworkdisplaysinseriesonthedownstreamnetworkisnotrecommended Othermodbusdevicesmustrespondtothe ReportSlaveID command 11h toallowpass throughcommunicationsfromtheupstreamnetwork Control Panel or PC Next Network Display On to additional Network Displays Network Display Othe...

Страница 5: ...ared leave Upstream RS485 and RS232 port connections disabled 2 Connect downstream RS485 device daisy chain 3 Make power connection Use either 120 VAC 2 wire or 12VDC as shown below ELECTRICAL INSTALLATION PowerWiringOption 1 120VAC PowerWiringOption 2 12VDC Internalfusingisnotactiveonthe12VDCinput Donotconnectbothpoweroptionsatthesame time ...

Страница 6: ...meters for setup To initialize a system the find meters sub menu function must be run see page 7 The password is SELECT DOWN DOWN SELECT UP UP SETUP To initialize a system the SETUP COMMUNICATIONS and FIND METERS actions must be performed see next page UP DOWN To Enter SELECT DOWN DOWN SELECT UP UP UP SELECT DOWN METER Show next submenu Show previous submenu Return to monitoring Go to submenu or s...

Страница 7: ...on the network Exit the search by pressing any key do not exit until all active addresses have been counted Unsupported devices will be designated as unknown device and parameters will not be displayed See supported devices page 11 4 REVIEW METERS Select REVIEW METERS to review all devices on the network Status LED and Relay Operation The Status LED displays the condition of the alarm registers on...

Страница 8: ...p to automatically cycle through all parameters on all devices on the network or display a selected parameter continuously Monitoring Mode Button Functions Go to next parameter set Go to previous parameter set Go to next meter Hold reading display will flash For use in automatic cycle mode See set up operations The current reading will not be updated This allows time to manually record the reading...

Страница 9: ... 9 QUICK REFERENCE MENUTREE MONITORING ...

Страница 10: ... position Euro style pluggable connector RS 232 DCE no handshaking DB 9 connection pin 2 Transmitted Data from H8936 pin 3 Received Data into H8936 pin 5 Ground Infrared Infrared port located above STATUS LED Bi directional transmit and receive 875nm 30 degree viewing angle 12 nominal range IrDA 1 0 Physical Layer Compliant DownstreamNetworkCommunications Interface RS 485 Protocol Modbus RTU Duple...

Страница 11: ...network devices are in alarm mode or the auxiliary input is active Supported Modbus Devices Enercept Full Data Stream Power Meter H8036 Enercept Energy Only Power Meter H8035 Enercept Multi Circuit Monitor H8238 Hawkeye Branch Current Monitor H704 42 H663 H8160 Series Energy Meter with H8163 CB Supported Modbus Commands Read Holding Register 03h Preset Single Register 06h Report Slave ID 11h ...

Отзывы: