19
Overview
Specific Density
If the specific gravity of the medium differs from 1 kg/dm
3
, you can enter the real density of the medium in P112. When this
option is used, in menu P102, the ‘true’ height of the tank must be entered.
P112
Write Protection
The Series 2000 with HART-Protocol can be protected for writing (Write Protection). This is possible for two kinds of
writings:
- Changes via the Display (“Lo.Pr” = Local Protection).
- Changes via external HART configuration software by the
Hand-held terminal
or the
P.C
. (“Co.Pr.”= Communication
Protection).
Standard, the transmitter is set to no-write protection.
Adjustment Local Protection
1. Push [PROG] till “100” appears on the display.
2. Push
h
/ SPAN 13 times until “113” appears on the display.
3. Push [PROG] to confirm. (“Lo.Pr.” appears on the display).
4. Push
h
/
i
for adjusting to “ON” or “OFF”.
5. Push [PROG] to confirm.
Adjustment Communication Protection
1. Push [PROG] till “100” appears on the display.
2. Push
h
/ SPAN 13 times untill “113” appears on the display.
3. Push [PROG] to confirm. (“Lo.Pr.” appears on the display).
4. Push once more at [PROG]. (“Co.Pr.” appears on the display).
5. Push
h
/
i
for adjusting to “ON” or “OFF”.
6. Push [PROG] to confirm.
N.B.
When Lo.Pr. is set to “ON”, the display shows 104, 105, 107, 108, 109 and 111 and the adjusted values of the
parameters. Afterwards “PROT” (Protected) is shown.
Both protections can be adjusted at the same time, independent from each other.
P113
Response Time From Push Buttons
This option can only be used from software version 8.01. The response time from the push buttons can be adjusted from
0,0 till 5,0 seconds.
P114
Service Menu
Permission from manufacturer needed to access menu.
P115
Service Menu
Permission from manufacturer needed to access menu.
P116
Series 2000 HART