2.0 INSTALLATION
2.6 Piping Line Flush
NOTE: VALVES SHOWN
SUPPLIED BY OTHERS
1) Close valves on chiller. Remove
protective cap from purge valves supply
and return, and connect hose to each of
the ¾” GHT (garden hose thread)
connections.
NOTE: TYPICAL SETUP SHOWN
2)
Open both supply and return purge
valves and flush system with city water
until water runs clear, continue to flush
for an additional 20 minutes.
NOTE: DO NOT OPEN
ISOLATION VALVES DURING
FLUSHING PROCESS.
OPC
Typical Connection size
Model
supply & return
12
1.5" NPT
Wye Strainer
Return pressure gauge
Supply valve
Return valve
Supply line purge valve
Supply tank drain valve
Return valve line purge
Hose barbs supplied by others