Gas Fired Boiler
14
Harsco Industrial, Patterson-Kelley Technical Service 1.877.728.5351
3.4.2 Three Phase Power Supply Connection (SC-3000 & SC-4000 Only)
Main Power Connection Box
Check the rating nameplate of the SC-3000 or SC-4000 boiler to determine the required electrical service:
208-240VAC, three phase, 60 hertz
440-480VAC, three phase, 60 hertz
The incoming three phase power for the SC-3000 & SC-4000 boilers is connected to the over-current safety
device (rated for 20 Amps) and the Ground terminal located in the main power connection box.
Figure 3.4.2
shows the Low Voltage (TB1) and High Voltage (TB2) terminal blocks, plus the
Main Power Connection Box
on the SC-3000 & SC-4000 with the front door hidden for clarity:
Terminal 1 = HOT L1
Terminal 3 = HOT L2
Terminal 5 = HOT L3
Terminal G = GROUND
The
Main Power Connection Box
features a
Control Transformer
which steps down two hot leads from the
incoming three-phase power in order to supply 110-120VAC single phase power to the boiler’s control system.
Be aware that SC-3000 & SC-4000 boilers ordered in the 240V configuration, are pre-wired from the factory for
operation with 240 VAC three phase incoming power.
If 208 VAC three phase power is supplied to the boiler, the internal control transformer
must be re-wired
for
operation at this lower voltage. The wire
in terminal X3 on the load side of the internal control transformer must
be moved to terminal X4. This supplies the
120 VAC power to the controls from the 208 VAC main voltage.
Refer to
Section
6.1.4
for proper wiring and configuration of the internal control transformer.
Control
Transformer
NOTE:
The
hot
lead
terminals
can
accommodate
maximum
12AWG
wire.
The
ground
terminal
can
accommodate
maximum
8
AWG
wire.
CAUTION:
Do
not
over
‐
tighten
the
hot
lead
terminal
screws.
Maximum
tightening
torque
=
13
in
‐
lbs!
Main
Power
Connection
Box
High
Voltage
(TB2)
Terminal
Block
Low
Voltage
(TB1)
Terminal
Block
Figure
3.4.2
Содержание SC-2000
Страница 50: ...Gas Fired Boiler Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 50...
Страница 52: ...Gas Fired Boiler Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 52...
Страница 54: ...Gas Fired Boiler Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 54...
Страница 65: ...Gas Fired Boiler Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 65 7 Limited Warranty...
Страница 66: ...Gas Fired Boiler Harsco Industrial Patterson Kelley Technical Service 1 877 728 5351 66 Boiler Fire Test Report...