ENVI
®
Control
9
Display
Description
Units
Open/Shorted
Sensor Indication
Supply Temp
Outlet / Supply Temperature
°F
14°F (Open) / 244°F(Shorted)
Return Temp
Inlet / Return Temperature
°F
14°F (Open) / 244°F(Shorted)
DHW Temp
Domestic Hot Water Temperature at the location of the
sensor(field installed)
°F
14°F (Open) / 244°F(Shorted)
Flue gas Temp
Flue Gas Temperature
FD boiler - thermal disc switch breaks the display will
indicate 50F
°F
50°F (Open) / 280°F(Shorted)
HX Temp
Heat Exchanger Temperature available on the MACH line
C1500 thru to the C4000
°F
14°F (Open) / 244°F(Shorted)
Outside Temp
Outside Air Temperature at the location of the sensor
(field installed)
°F
-40°F / 176°F
CH set Temp
Comfort Heat Setpoint Temperature
°F
N/A
DHW set Temp
Domestic Hot Water Setpoint Temperature
°F
N/A
Header Temp
Header Temperature at the location of the sensor(field
installed)
°F
244°F / 244°F
Flame signal
Flame Signal (versions
49A7 and earlier were “YES/NO”)
μA
< 1.7
μA = Flame Not Detected
> 1.7
μA = Flame Detected 0-10
Fan speed
Fan Speed
RPM
0-9999
Analog in
Analog Input
N/A
Not Currently Used
Analog out
Analog Output
N/A
Not Currently Used
Ignitions
Number of Ignitions
#
0-99999
Burn Hi HR
Hours at High Fire (75% to 100%)
HRS
0-99999
Burn MD HR
Hours at Medium Fire (45% to 75%)
HRS
0-99999
Burn LO HR
Hours at Low Fire (20% to 45%)
HRS
0-99999
Water press
Water Pressure
N/A
Not Currently Used
Water level
Water Level Sensor Status
Aux LWCO status on FD boilers (if installed)
Off/On
0 = Low Water Cutoff
1 = Low Water Cutoff Detects Water
Low gas press
Low Gas Pressure Sensor Status
Off/On
0 = Low Gas Pressure Switch Open
1 = Low Gas Pressure Switch Closed
Air pressure
Air Pressure Switch Status
Off/On
0 = Air Pressure Switch Open
1 = Air Pressure Switch Closed
Blocked flue
Blocked Flue Switch Status
Off/On
0 = High Exhaust Back Pressure
Switch Open
1 = High Exhaust Back Pressure
Switch Closed
CH pump
Comfort Heat Pump Relay Status
Off/On
0 = CH Pump relay Off
1 = CH Pump relay On
DHW pump
Domestic Hot Water Pump Relay Status
Off/On
0 = DHW Pump relay Off
1 = DHW Pump relay On
Air damper
Air Damper Relay Status
Off/On
0 = Air Damper relay Off
1 = Air Damper relay On
Hi gas pressure
Hi Gas Pressure Switch Status
Off/On
0 = Hi Gas Pressure Switch Open
1 = Hi Gas Pressure Switch Closed