J.2.4.
Power Output Calibration
Connect the transmitter into a load with
the capability of accurately measuring the
power output. This is best done with a cal-
orimetric dummy load, where the water
temperature rise is measured against a
known flow rate. A second choice is a
dummy load and an RF ammeter of known
accuracy.
Operate the transmitter at a convenient
power level within the capabilities of the
test setup.
Calibrate the Power Output meter to the
same reading as measured externally using
R85 on the Controller board.
J.3.
Overload Adjustment Procedures
J.3.1.
Power Supply Current Overload
Check the present Power Supply Current
reading against the value on the factory test
data sheet for the same operating condi-
tions. If the present reading is significantly
higher, it will be advisable to investigate the
cause before proceeding with the following
overload adjustment.
The overload threshold can be set to the
same value as recorded on the factory test
data sheet, or by checking the trip threshold
by modulating it with a tone according to
the following procedure.
For setting the overload under modulating
conditions, operate the transmitter at 110%
of its rated power output (5500 watts for
GATES FIVE, 2750 watts for a GATES
TWO, and 1100 watts for a GATES ONE).
Modulate with 20 Hz to 100%. Increase
the audio level 0.5dB (6%).
Adjust R11 counterclockwise until the
transmitter faults, then 1/3 of a turn clock-
wise from this trip point.
J.3.2.
Underdrive Fault
For the Underdrive fault, a comparison is
made between the RF Drive level reading
and a threshold which is a function of power
level. The RF Drive level reading is what is
adjusted during the alignment procedure.
The RF Drive level reading should always
be somewhat higher than the Underdrive
Set reading.
If you are replacing the Controller board,
and already know that the actual RF Drive
level is okay, you will only need to duplicate
your normal reading for High power.
A more in depth check of the overload
function requires verifying the correct RF
drive amplitude (26-32 Vpp) is present
across R13, R14, R23, R24, R33, R34, R43
and R44 for each PA module. For the pro-
cedure on checking the drive on the PA
module(s), refer to Section H.
After verifying the actual RF drive to be
in the normal range, modulate the transmit-
ter to 100% with 400 Hz at 110% power
output (5500 watts for GATES FIVE, 2750
watts for a GATES TWO, and 1100 watts
for a GATES ONE).
Adjust R143 clockwise until the transmit-
ter trips to the next lower power level and
displays the Underdrive fault. Then rotate
R143 counterclockwise from the trip point
about 2 turns.
J.3.3.
VSWR Detector
You may set the VSWR trip threshold
using the value recorded on the factory test
data sheets, or may use a more involved
process which actually causes the overload
circuit to operate.
With the transmitter on, and NO modula-
tion applied, set the LOW power control all
the way to zero power output.
Use a clip lead to short across R18 on the
Output Monitor board. This will cause the
VSWR detector to not be nulled when you
bring up RF power.
Gradually increase the power output, and
watch the VSWR Detector Null reading
come up from zero. Adjust R14 so that the
transmitter trips off when the VSWR Detec-
tor Null reading reaches 7.5 on the Mul-
timeter.
J.4.
Troubleshooting the Controller
Numerous components are duplicate
types in control, status, metering, and over-
load functions. This can be advantageous
in terms of isolating a problem and getting
back on the air in the event of a component
failure.
The Chart of Functions lists the IC types
used and their functions. Those designated
by an asterisk (*) are for status indications
or metering, and not necessary to the opera-
tion of the transmitter at any power level.
Therefore, any of these could be transferred
to a needed function where a failure oc-
curred if no replacement was immediately
available.
J.4.1.
Symptom: Will Not Respond To
An On Command
(None of the status LED’s on the power
level switches illuminate.)
Possible Causes:
J.4.1.1.
Controller Supply Failure
Check the status of the +/-12 volt indica-
tors. Measure the +/-12 volts on the Con-
troller board. Feel the regulators U32 and
U33. If one is hot, it probably means there
is a shorted component loading the supply
down on the Controller.
J.4.1.2.
Failed flip flop circuitry
Check the operation of U4, U5, and U6 or
replace them. Also check or replace NOR
gates U7, U8, U9, U10, U11, and U12. A
logic zero on the outputs of the NOR gates
will hold the flip flops in an OFF mode.
J.4.2.
Symptom: PDM Power Level Sig-
nal Cannot Be Controlled
Possible causes:
Check to see if there is a PDM Kill or
overload condition. Check or replace U19.
J.4.3.
Symptom: Multimeter Is Pinned
Far Left or Right
Check to see if it matters which position
the meter switch is in. If it does not, replace
U20 on the Controller. Otherwise, both U20
and U21 are suspect.
J.4.4.
Symptom: Some Remote Control
Functions Do Not Work
Possible causes:
Optical Isolator Failure. Failures in this
area would probably inhibit only those in-
puts with defective optical isolators. Ohm-
meter test the input side of U1, U2, and U3
on the Controller board. These should test
as diodes. Otherwise, measure across each
optical isolator input on the Controller to
see if a voltage is being applied as the
remote control circuits are activated.
U1*
ILQ-1
Remote LOW through
FOUR power level
control
U2*
ILQ-1
Remote FIVE, SIX, OFF,
and EXT KILL control
U3*
ILQ-1
Remote Raise, Lower,
and Indicator Reset
U4
74C74
LOW and TWO power
selection flip flop
U5
74C74
T H R E E a n d F O U R
power selection flip
flop
U6
74C74
FIVE and HIGH power
selection flip flop
U7
CD4048
L OW
p ow e r l eve l
selection
U8
CD4048
T W O
p ow e r l eve l
selection
U9
CD4048
THREE power level
selection
U10
CD4048
F O U R p ow e r l eve l
selection
U11
CD4048
F I V E p ow e r l eve l
selection
Chart of Functions
(Continued on next page)
Rev.AE: 03-05-2002
888-2314-001
J-3
WARNING: Disconnect primary power prior to servicing.
Содержание Gates Five 994 9204 002
Страница 4: ......
Страница 6: ...iv 888 2314 001 Rev X WARNING Disconnect primary power prior to servicing...
Страница 8: ...vi 888 2314 001 Rev X WARNING Disconnect primary power prior to servicing...
Страница 28: ...2 12 888 2314 001 Rev AC 2 29 00 WARNING Disconnect primary power prior to servicing...
Страница 40: ...Figure 5 1 PDM Flow Diagram 5 2 888 2314 001 Rev T Jan 1996 WARNING Disconnect primary power prior to servicing...
Страница 42: ...Figure 5 2 PDM Loop 5 4 888 2314 001 Rev T Jan 1996 WARNING Disconnect primary power prior to servicing...
Страница 43: ...Figure 5 3 RF Flow Rev T Jan 1996 888 2314 001 5 5 WARNING Disconnect primary power prior to servicing...
Страница 76: ...C 6 888 2314 001 Rev AE 03 05 2002 WARNING Disconnect primary power prior to servicing...
Страница 82: ...E 4 888 2314 001 Rev AE 03 05 2002 WARNING Disconnect primary power prior to servicing...
Страница 88: ...F 6 888 2314 001 Rev AE 03 05 2002 WARNING Disconnect primary power prior to servicing...
Страница 96: ...H 2 888 2314 001 Rev AA 8 18 1999 WARNING Disconnect primary power prior to servicing...
Страница 104: ...K 2 888 2314 001 Rev AE 03 05 2002 WARNING Disconnect primary power prior to servicing...
Страница 105: ...Figure K 1 Interface Board Rev AE 03 05 2002 888 2314 001 K 3 WARNING Disconnect primary power prior to servicing...
Страница 108: ...L 2 888 2314 001 WARNING Disconnect primary power prior to servicing...