Operation data setting table 

This data setting table is suit for heat pump with heating and cooling function. If heat 
pump without cooling function, parameter 0,2,3,4,5 will not work. 
 

Digit 

Meaning 

Range 

Default 

Adjust (yes/no) 

00 

Return water temp.  
Setting (cooling mode) 

8-28°C 

12°C 

yes 

01 

Return water temp.  
Setting (heating mode) 

15-40°C 

27°C 

yes 

02 

Total working time of  
compressor after frosting 

30-90MIN 

90MIN 

Adjusted by technicians 

03 

Setting initialization temp for 
defrosting 

-30-0°C 

-30°C 

Adjusted by technicians 

04 

Temp. of exit defrost under heating 
mode 

2-30°C 

2°C 

Adjusted by technicians 

05 

Max. time of defrost under heating 
mode 

1-12MIN 

1MIN 

Adjusted by technicians 

06 

Electronic expansion valve mode 

0(Manuel)1(AUTO) 

Adjusted by technicians 

07 

Automatic restarting after power off 

0-1 

1(record) 

Adjusted by technicians 

08 

Mode (cooling only/heat 
pump/auxiliary electrical 
heating/hot water) 

0-3 

3(hot water)  Adjusted by technicians 

09 

Water pump keep running or stop 
after compressor stop for 30s 

0(keep 

running)1(stop) 

Adjusted by technicians 

Auto mode (return water temp) 

8-60°C 

40°C 

Adjusted by technicians 

Setting of EEV (heating mode) 

-F(-15°C)~F(-15°C) 

5°C 

Adjusted by technicians 

Electronic expansion valve manual 
steps 

10-50 

35 

Adjusted by technicians 

Setting of EEV (cooling mode) 

-F(-15°C)~F(-15°C) 

5°C 

Adjusted by technicians 

Maximum temperature setting 

30-70°C 

4°C 

Adjusted by technicians 

Delta T setting 

1-20°C 

2°C 

Adjusted by technicians 

Ambient temp. protection (Min.) 

-15°C-15°C 

8°C 

Adjusted by technicians 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание QBIC

Страница 1: ...Imported by Zwembad BVBA Industrieweg 9 3190 Boortmeerbeek Belgi www harmopool eu Swimming pool heat pump QBIC Model ZVWX5010 ZVWX5020 ZVWX5030 Instruction manual...

Страница 2: ...tion 8 Installation of the bypass 8 Electrical wiring 9 Start up procedure 10 Daily use of the heat pump 10 Condensation 10 Guidelines 11 Water chemistry 11 Winter ready 11 Spring start up 12 Owner in...

Страница 3: ...with these recommendations will void warranty The swimming pool heat pump unit heats the swimming pool water and keeps the temperature constant Characteristics Durable the heating exchanger is made o...

Страница 4: ...220 240 1 50 220 240 1 50 Controller Digital control Condenser Titanium heat exchanger Compressor Quantity 1 1 1 Compressor Rotary Rotary Rotary Refrigerant R410a R410a R410a Weight refrigerant 700g 8...

Страница 5: ...5 Dimensions of the heat pump Model Size mm ZVWX5010 ZVWX5020 ZVWX5030 A 670 G 101 F 250...

Страница 6: ...ways keep the unit straight up If the unit has been tilted or put on his side allow 24h before starting the unit Location The unit may be installed virtually anywhere outdoors For indoor pools please...

Страница 7: ...er 30 meters could roughly be estimated at 0 6kw hour 2000 BTU for every 5 temperature difference between the pool water and the soil surrounding the pipe which translates to an operation time increas...

Страница 8: ...Installation of the bypass With the bypass set correctly your heat pump will deliver its best performance The bypass has to be built as shown below Install the bypass with all 3 valves entirely open S...

Страница 9: ...inside the heat pump All heat pumps require a single phase connection Grounding the heat pump is required to protect you against electrical shocks caused by an eventual short circuit inside the heat...

Страница 10: ...the unit and that is switched off when the water flow becomes too low e g when the filter pump is switched of Time Delay the unit is equipped with a built in 3 minute start delay to protect electrical...

Страница 11: ...pump A check valve must be installed between the heat pump and the chemical feeder to prevent back siphoning of chemically saturated water into the heat pump where it will damage the components Winte...

Страница 12: ...pouring down onto the unit 6 Do not use the heat pump if any part has been under water Immediately call a qualified professional technician to inspect the heat pump and replace any part of the contro...

Страница 13: ...setting Press to alter Press SET again to confirm Press M again 9 0 Press SET to enter water pump setting Press to alter Press SET again to confirm Press M again A 40 Press SET to enter return water t...

Страница 14: ...ter from 00 G see the Operation Parameter Table o Under parameter setting press or to set data o Please note no motion on the display for 10s the LCD will display water in water out temp under running...

Страница 15: ...s M for 5 seconds to check the current status of the unit You can check water in water out temp condenser temp and ambient temp Please note no motion on the display for 10s The LCD will display water...

Страница 16: ...technicians 06 Electronic expansion valve mode 0 Manuel 1 AUTO 1 Adjusted by technicians 07 Automatic restarting after power off 0 1 1 record Adjusted by technicians 08 Mode cooling only heat pump aux...

Страница 17: ...ther systems to prevent damage from freezing o You should discharge the water at the bottom of the heat pump if the unit will not work for an extended period of time You should check the unit thorough...

Страница 18: ...time freezing protection in winter PP 07 Ambient temp too low The second time freezing protection in winter PP 07 Ambient temp too low Coil sensor failure cooling mode PP 08 The sensor is open or sho...

Страница 19: ...19 Wiring diagram Model ZVWX5010 ZVWX5020 ZVWX5030...

Страница 20: ...20 Warranty...

Отзывы: