VENTING 

The FireLuxe Gas Stove has been tested and listed for installation with 4” X 6 5/8” Simpson DuraVent GS, 

AmeriVent Direct, Security Secure Vent and Selkirk DT direct venting components.  For specific installa-

tion requirements, follow the installation instructions included by the venting manufacturer with the venting 

system components you have chosen.  The total vent length may not exceed 40 feet, including vertical rise 

and horizontal run.  The vent lengths are measured from the stove, not the floor.  The minimum vertical rise 

required is 2 feet.  The maximum allowed horizontal vent run is 20 feet when the venting includes at least 5 

feet of vertical rise.  The maximum allowed horizontal vent run for vertical rises of less than 5 feet is shown 

in the venting charts.  No more than three elbows may be used in any installation.  The venting charts in-

clude the use of one elbow.  For the second or third elbows that are included in the installation, add 4 feet to 

the actual horizontal run for each elbow to determine the equivalent horizontal run for the installation. 
The venting charts allow a simple way to determine the recommended initial settings for both the air inlet 

and exhaust restrictors.  These settings have been determined by extensive testing and will be a good start-

ing point while setting up the stove.  Small adjustments from these settings may be needed to account for 

specific installation variables.  Please see the instructions on pages 21 - 22 for how to adjust the restrictors.  

 

The letters (A-E) designate the position of the air inlet restrictor.  When ½ is added to the letter designation, 

this indicates that the position is halfway between adjacent letters.  The numbers (0-8) indicate the position 

of the exhaust restrictor.  When 

, ¼, 

, ½, or ¾ is added to the number designation, this indicates that the 

position is fractionally between adjacent numbers.  For example, 5¼ is one-fourth the way between 5 and 6. 
To use the charts, determine the horizontal run length and vertical rise length (in feet) for your installation.  

If more than one elbow is used, add 4 feet to the actual horizontal run length for each additional elbow to 

get the equivalent horizontal run for the chart. Note:  Remember that a maximum of three elbows is al-

lowed.  Select the venting chart for the fuel type (Natural Gas or Propane (LP) Gas) and find the box on the 

chart that corresponds to the vertical rise and actual horizontal run (or equivalent horizontal run, if two or 

three elbows are used) and read the settings for the inlet air restrictor (A-E) and exhaust restrictor (0-8).  

Examples are shown below and on page 9. 
The FireLuxe is shipped with a Simpson DuraVent GS starter section that is specifically designed for the 

FireLuxe.  Regardless of the venting brand you chose, you must use the provided DuraVent starter section.  

All of the venting brands listed for use with the FireLuxe are compatible with the provided starter section. 

For venting system installation details, refer to the instructions provided with the venting system you have 

chosen.  Each brand has specific installation requirements that must be followed to insure a safe and func-

tional venting system for your FireLuxe. 
Note:  The Fireluxe is shipped from the factory with restrictor settings for 2 feet of vertical rise and 1 foot 

of horizontal run and for the fuel type listed on the rating plate attached to the rear of the stove.   

E½ 

6¾ 

Example 1 

 

 

 

 

 

 

 

 

 

Fuel = Propane (LP) 
Vertical Rise = 15 feet 

 

 

 

Horizontal Run = 8 feet 
Elbows 

     

Equivalent Horizontal Run = 8 feet   

 

Air Restrictor Setting = E½   

 

 

Exhaust Restrictor Setting = 6¾ 

 

INLET AIR 

EXHAUST 

Содержание FireLuxe Direct Vent Gas Stove With Top Cooking Burner...

Страница 1: ...the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier INSTALLER Leave this manual with the appliance CONSUMER Retain this manual fo...

Страница 2: ...reil peut tre install dans une maison pr fabriqu e mobile d j install e demeure si kes r glements locaux le permettent Cet appareil doit tre uniquement avec las type de gaz indiqu sur la plaque signal...

Страница 3: ...RTANT SAFETY INFORMATION 4 SPECIFICATIONS 5 INSTALLATION 6 MASSACHUSETTS REQUIREMENTS 7 VENTING 8 ASSEMBLY 14 LIGHTING AND OPERATION 23 REMOTE CONTROL HANDSET OPERATION PROGRAMMING 26 MAINTENANCE 28 P...

Страница 4: ...of the appliance A commercially available hearth pad meets this requirement The appliance area must be kept clear and free from combustible materials gasoline and other flammable vapors and liquids T...

Страница 5: ...ppliance is equipped for use with the fuel type indicated on the rating plate Fuel conversion kits that include the necessary parts and instructions are available from your installer dealer or Harman...

Страница 6: ...must also insure that your installation provides adequate accessibility clearance for servicing and proper operation When the appliance is installed directly on carpeting or tile or other combustible...

Страница 7: ...ed professionals for the installation of hard wired carbon monoxide detectors In the event that the horizontally vented appliance is installed in a crawl space or attic the hard wired carbon monoxide...

Страница 8: ...e numbers 0 8 indicate the position of the exhaust restrictor When or is added to the number designation this indicates that the position is fractionally between adjacent numbers For example 5 is one...

Страница 9: ...EXHAUST INLET AIR E 7 Example 3 Fuel Natural Gas Vertical Rise 22 feet Horizontal Run 0 feet Elbows 0 Equiv Horizontal Run 0 feet Air Restrictor Setting E Exhaust Restrictor Setting 7 EXHAUST INLET A...

Страница 10: ...10 VENTING VERTICAL RISE IN FEET HORIZONTAL RUN IN FEET NATURAL GAS VENTING IF YOUR VENTING CONFIGURA TION FALLS ABOVE THIS DOT TED LINE SEE PAGE 12...

Страница 11: ...11 VENTING VERTICAL RISE IN FEET HORIZONTAL RUN IN FEET PROPANE LP GAS VENTING IF YOUR VENTING CONFIGURA TION FALLS ABOVE THIS DOT TED LINE SEE PAGE 12...

Страница 12: ...XISTING MASONRY OR CLASS A CHIMNEY The FireLuxe has been tested and found to be in compliance when using an existing chimney as the air con duit for the direct venting system This type of installation...

Страница 13: ...13 VENT TERMINAL CLEARANCES VENTING Venting terminals shall not be recessed into a wall or siding...

Страница 14: ...near to its installation position Like any cast iron stove it is best to pick the stove up while adjusting its position rather than dragging it on its legs This reduces the chances of damaging a leg...

Страница 15: ...urner The burner and log system is designed to facilitate correct placement of the logs Flat recessed areas on the burner top are keyed to each of the four main logs The rear logs also have locating p...

Страница 16: ...last Again place the flat base of the log in the corresponding recess in the burner top per the illustration below LEFT FRONT LOG RIGHT FRONT LOG There are three loose ember pieces Each ember piece ha...

Страница 17: ...he frame against the firebox while pushing down to be sure the frame is fully engaged in the frame retainer Hold the frame in place with one hand and engage the three glass frame latches by pulling ou...

Страница 18: ...alignment is obtained Take extra care with this procedure if your stove is enameled Just move in small increments as you line up the tabs and lower the front into place If you take your time you will...

Страница 19: ...king burner is located behind an access panel located on the right rear of the stove when looking from the stove front A single fastener secures the panel Simply remove fastener and the panel to acces...

Страница 20: ...g from the control module and be sure to place the module back it its original posi tion after the batteries and cover are installed CONTROL MODULE COVER AA BATTERIES VALVE ACCESS PANEL CONTROL MODULE...

Страница 21: ...heat shield as needed and remove Refer to the illustrations below PRIMARY AIR ADJUSTER Your FireLuxe gas stove was shipped from the factory equipped for the fuel type indicated on the rating plate tha...

Страница 22: ...n one full increment of adjustment should be used If no change in the flame appearance is noted after that consult with a Harman Stove Company rep resentative If after 20 30 minutes at high fire the f...

Страница 23: ...ge 2 This appliance is equipped with an ignition device that automatically lights the pilot When using the remote handset do not try to light the pilot by hand 3 Push the OFF button on the remote hand...

Страница 24: ...ate the valve on the back of the stove Turn the main valve knob to the OFF full clockwise position 3 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell g...

Страница 25: ...FOR ANY REASON WARNING CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION YOUNG CHILDREN SHOULD BE CAREFULLY SUP...

Страница 26: ...ration above The adjustment screw can be reached through the MAN knob See top illustration above 1 Turn the Man knob to the ON position 2 It is now possible to pierce through a film on the cover with...

Страница 27: ...TION SET OFF UP DOWN Radio Frequency Interference A frequency code is preset for the valve receiver and remote handset but can be changed if you are experiencing interference with other de vices To ch...

Страница 28: ...glass and frame aside on a padded surface If the glass is broken do this over spread out newspaper to catch all loose material The outside of the frame should be facing down to give ac cess 5 Carefull...

Страница 29: ...ve It is important that air flows freely through the convection air system and out the front and side air grills Do not place objects under the stove that will block the convection air inlet flow or i...

Страница 30: ...30 PARTS LIST This is a quick response thermocouple Replace it only with Part No 3 40 09906...

Страница 31: ...tning acts of God power failures and or surges rust corrosion and venting problems are not covered Damage and or repairs including but not limited to remote controls filters fuses knobs glass ceramic...

Страница 32: ...32 For replacement parts and customer service contact your Harman Stove dealer Manufactured by HARMAN STOVE COMPANY 352 MOUNTAIN HOUSE ROAD HALIFAX PA 17032 Ver 04 09 06...

Отзывы: