Harman Stove Company Conquest Gas Stove Скачать руководство пользователя страница 19

19

INSTALLATION   (Options)

Only For Qualified Installers

Optional  Blower

The Blower Kit (Part # 1-00-09102) includes a

blower assembly ready to bolt to the left side of the
stove and a blower chamber cover.

The blower has a variable speed control knob

to adjust the blower speed as desired. A special switch
is used to  automatically start the blower  when the
stove temperature is hot enough to blow warm air.
This switch will also stop the blower when the stove
temperature drops below the point that warm air is
available.

Installation

1. Open the left side panel.
2. Remove the four screws from the left side of the

firebox with a 

5

/

16

” socket.

3. Place the blower as shown and start the top

screw. This will hold the blower in place and
make it easier to install the other three screws.

4. Route the power cord rearward between the side

panel and the pedestal and plug into a 120 volt
outlet.

5. Open the right side panel and remove the two

screws on the right side of the firebox.

6. Use the two screws to fasten the blower cham-

ber cover plate to the firebox. This plate pre-
vents air from the blower escaping from the air
chamber.

7. Close side panels.

Operation

Turn the speed control knob clockwise until it

clicks.  This  is  the  full  speed  position.  Turning  the
knob farther  in the  clockwise direction  will gradu-
ally  reduce  the  blower  speed.  To  turn  the  blower

“OFF” turn the knob counterclockwise until it clicks.

Blower Assembly

Speed Control Knob

Blower Chamber Cover

Power Cord

This  blower is  equipped  with a  three-prong
(grounding) plug for protection against shock
hazard and should be plugged directly into a
properly  grounded  three-prong  receptacle.
Do  not  cut  or  remove  the  grounding  prong
from the plug.

Evaluation notes were added to the output document. To get rid of these notes, please order your copy of ePrint IV now.

Содержание Conquest Gas Stove

Страница 1: ...RYOURSAFETY FOLLOW INSTALLATIONDIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALSABOUT RESTRICTIONSAND INSTALLATION INSPECTION REQUIREMENTS INYOUR AREA CONTACT YOUR LOCAL AUTHORITY SUCH AS MUNICIPAL...

Страница 2: ...anual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids...

Страница 3: ...earances 8 Installation 9 Venting 10 Changing To Natural Gas 14 Option Installation Thermostat 18 Remote Control 18 Glass Grill 18 Blower 19 Maintainence 20 Wiring Diagram 22 Parts 24 Trouble Shooting...

Страница 4: ...suitable location for your Conquest Gas Stove Observing required clearances to combustible ma terials the proximity to a safe chimney or venting system location and the accessibility of the gas and e...

Страница 5: ...n the logs as shown at lower left 10 Push the control knob fully down and hold Immediately push the red piezo ignitor button to light the pilot It is normal to have to push the red button several time...

Страница 6: ...to OFF unless it is pushed in slightly Do not force it FLAME HEIGHT ADJUSTMENT The flame height adjuster can be accessed by openingthe right side panel Turn the adjuster clock wise to increase flame h...

Страница 7: ...in Input Rating Btu hr 0 4500 ft 0 1375 m 14900 14100 Orifices DMS 0 4500 ft 0 1375 m 37 53 Manifold Pressure in w c kPa 3 8 95 11 0 2 75 Min Manifold Pressure in w c kPa 1 1 27 2 8 7 Min Inlet Pressu...

Страница 8: ...UCTION Unit to corner walls 2 in Unit to side wall 8 in Unit to back wall 3 in Unit to alcove ceiling 16 in Maximum alcove depth 16 in Electrical Rating 120 Volts 60 Hz 7 AMP 8 3 2 2 16 8 8 16 Alcove...

Страница 9: ...e Requirements Correct gas pressure and the use of a properly sized gas supply line are essential for the safe and efficient performance of this appliance Make sure that the plumber or gas supplier ch...

Страница 10: ...ation 36 982 1282 Snorkel Termination 14 984 1284 Horizontal Square Termination 980 1280 Vertical Termination 991 1291 Vertical Termination High Wind 950 1250 Vinyl Siding Standoff 1222D Only availabl...

Страница 11: ...cond elbow Venting with 6 5 8 x 4 Pipe A combination of one 900 elbow and two 450 elbows is allowed Subtract three feet of total horizontal pipe length for each 450 elbow used This appliance must not...

Страница 12: ...sembly when measured from the horizontalcenter line ofthe regu lator 1 I The clearance to service regulator vent outlet must be a minimum of 6 feet 1 8 m 1 J The clearance to a non mechanical air sup...

Страница 13: ...be too long with black tips and too much draft will cause flames to be short and blue To adjust the damper burn the unit on High 10 minutes or more Adjust the vent damper to a posi tion in the ranges...

Страница 14: ...orifice from the kit Natural Gas Kit Part No 1 00 09112 NG Conversion label NG Orifice 37 NG Valve Conversion Module NG Conversion Instructions This kit is only for use in the Conquest direct vent gas...

Страница 15: ...ote If no conversion is made the box for the propane box must still be marked by the installer 7 Note The higher the orifice number the smaller hole in the tip For example a number 52 orifice has a la...

Страница 16: ...s and deflector plate Ember Placement After the logs are positioned place the embers as shown above There are two types of embers supplied One is a wool like material and the other like a nugget The w...

Страница 17: ...ee threaded holes In some cases it may be helpful to remove extra paint from the treads with a 1 4 20 tap 1 Screw the set screws down until the top of the screw is about the thickness of the tile belo...

Страница 18: ...ED WIRE GAUGES Maximum Wire Length Gauge 100 14 60 16 40 18 25 20 15 22 Thermostat Remote Control Kit The button on the remote control can be used to turn the fire on and off This remote uses the ultr...

Страница 19: ...tall the other three screws 4 Route the power cord rearward between the side panel and the pedestal and plug into a 120 volt outlet 5 Open the right side panel and remove the two screws on the right s...

Страница 20: ...the tab drops into the slot on the door frame 8 Reinstall air grill Cleaning the Glass The glass may be cleaned with ordinary house hold glass cleaner and a soft cloth or paper towel W ARNING Never c...

Страница 21: ...anufacturer s instructions may provide specific suggestions or detailson vent inspection Anysections that are taken apart for the inspection must be reassembled and sealed as required Cleaning the Log...

Страница 22: ...emperature Switch Power Cord Optional Blower Wiring Diagram 120 Volt Low Voltage Wiring Diagram Caution Label all wires prior to disconnection when servicing controls Wiring errors can cause improper...

Страница 23: ...ent Gas Fireplace Heater Radiateur Ventile Model Conquest 727 WHI RATINGS NATURAL PROPANE Input Rating Btu hr 0 4500 ft 0 1375 m 29000 29000 Min Input Rating Btu hr 0 4500 ft 0 1375 m 14900 14100 Orif...

Страница 24: ...73126 Burner plate weldment 19 2 00 73127 Burner clamp 20 2 00 73141 Air guide 21 3 31 00521 Relief door springs 22 2 00 73155 Relief door 23 3 44 73133 Relief door gasket 24 1 10 73130 Right side pan...

Страница 25: ...5 3 40 09106 50 turn down LP valve 6 3 31 08792 1 2 flare fitting 7 3 44 73174 Valve gasket 8 3 90 4273 Gas label 9 2 00 73125 Sealer plate 10 3 40 09210 A Hood orifice elbow 11 3 40 09210 B 53 hood...

Страница 26: ...onnect or replace Ignitor wire Yes No Bad OK OK Bad No Yes Turn on gas valve Is gas turned on Yes OK Purge gas line to stove No Replenish supply Bad OK Replace Piezo Ignitor Check Piezo Ignitor to mak...

Страница 27: ...d Check Milivolt output of thermocouple Should be 10 or more MV Check inlet pressure Bad Adjust pilot adjustment to achieve proper flame Replace Thermocouple Bad Replace Valve Pilot does not stay lit...

Страница 28: ...position Is Pilot lit no Light pilot Yes Check Thermopile voltage at terminals marked TP on valve Should be approximately 200 mv with switch on and approximately 400 mv with switch off too low Replac...

Страница 29: ...BE USED WITH THIS CONQUEST DIRECT VENT GAS Optional Blower Label This appliance has been converted for use at an altitude of_______Feet Natural Propane Orifice Size 37 54 Manifold Pressure 3 8 WC 11...

Страница 30: ...not limited to fire lightning acts of God power failures and or surges rust corrosion and venting problems are not covered Damage and or repairs including but not limited to remote controls filters f...