HARISON INDUSTRIAL DEHUMIDIFIER - USER'S MANUAL -  Model: HD-100BM 

2.2. INNER COMPONENT IDENTIFICATION AND WORKING PRINCIPLE 

  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Other main working components are: high efficient compressor, accumulator, magnetic 
flow control valve, evaporator coil, condenser coil, capillary tube, centrifugal fan, 
temperature sensor, humidity sensor and electrical wiring.  

 
a. Main working principle 

 
When dehumidifier is switched on, the compressor starts to work. The compressor draws in 
low-pressure and low-temperature refrigerant stream from evaporator, and compresses it 
into high-temperature and high-pressure gas. The  gas enters into condenser and is 
condensed into liquid, giving out heat. Then through capillary, the liquid is throttled into 
the evaporator, absorbs heat from the air and is evaporated into gas. The gas is drawn into 
the compressor through air intake pipe. Just in this way the refrigeration cycle is completed. 
Such a cycle repeats time and again, and refrigeration is achieved. 

 
b. Dehumidifying cycle 
 

The centrifugal fan makes wet air entering into the evaporator through air filter, then the air 
is cooled down. When the surface temperature of the evaporator is lower than the dew-point 
temperature of the air, the water content in the air is condensed and drained from the 
machine. The dehumidified air is then heated by the condenser and is discharged into the 
room by the centrifugal fan. Thus, the air goes through the cycle and the water in the air 
gets condensed so as to achieve dehumidification. 

 
c. Defrosting cycle 

 
When the environment temperature is lower ( 5

o

C - 18

o

C ) during running, the surface of 

the evaporator will be frosted due to lower temperature. The computer will judge and send 
the defrosting command automatically as the situation. After defrosting, the dehumidifier 

co

nd

ense

r

e

v

a

p

or

ator

filter

filter

capillary

ai

r st

ra

in

e

r

valve

compressor

accumulator

the flowing direction of refrigerant in defrosting cycle

the flowing direction of refrigerant in dehumidifying cycle

the flowing direction of air

Содержание HD-100BM

Страница 1: ......

Страница 2: ...nt identification 2 2 Inner component identification and working principle a Main working principle b Dehumidifying cycle c Defrosting cycle d Safety devices function e Technical parameters f Capacity curve 3 4 5 6 7 3 Installation 3 1 Delivery and storage 3 2 Installation environment 3 3 Power sources 3 4 Installing 7 7 7 8 4 Operation 8 5 Maintenance 9 6 Troubles and Countermeasures 10 ...

Страница 3: ...hive establishment warehouses etc For preventing instruments meters communication equipment commodity reference materials from getting damp rusty mildew rot and causing damage Its most special featured function is its high mobility enabled by those unique features of internal intergrated condensed water pump rigid construction larger wheel and handle Therefore it is the only model than can be move...

Страница 4: ...they meet the safety requirements listed by federal codes However the individual operating or working on any machinery is primarily responsible for Personal safety safety of other personnel and the machinery Correct utilisation of the machinery in accordance with relevant procedures The contents of this manual include suggested best working practices and procedures These are issued for guidance on...

Страница 5: ...uch a cycle repeats time and again and refrigeration is achieved b Dehumidifying cycle The centrifugal fan makes wet air entering into the evaporator through air filter then the air is cooled down When the surface temperature of the evaporator is lower than the dew point temperature of the air the water content in the air is condensed and drained from the machine The dehumidified air is then heate...

Страница 6: ...l parameters Model HD 100BM Dehumidification Capacity Kg h 4 2 30oC 70 Rated Airflow CMH 850 Power source V 1Ph 220V 50Hz Nominal rated power kW 1 65 Rated current A 7 8 Noise level dB A 57 Overall dimensions W x D x H mm 568 x 436 x 1110 Weight Kg 64 Note Nominal working condition 27 0o C DB 21 2o C WB Low temperature working condition 5 0o C DB 2 1o C WB Notice Please use this unit under the spe...

Страница 7: ... frost and rain Inspection Remove the shipment packing and inspect unit to ensure that no damage has occurred during transportation and storage Any visible damage must be reported to nearest Harison representative 3 2 Installation Environment 1 The unit should be installed stably There should be one meter of space in front of the inflow and outflow There should be no large obstacle around it 2 The...

Страница 8: ...en connect the dehumidifier with power source and start dehumidifier as normal 4 OPERATION Control panel Instruction of keys 1 ON OFF Press ON OFF the unit runs in a circulation ON OFF ON 2 Humidity up and down Press humidity up and down for once the set humidity increase or decrease for 1 Press the key for 1 5 seconds and the setting value increase or decrease by 1 continuously with the speed 5 p...

Страница 9: ...ges the system temperature automatically to defrost When defrosting the defrosting indicator lights on the fan motor runs but compressor shuts off automatically 4 When pressing the memory key the controller will record current humidity even if power off And the unit will run under previous mode after power supplied again 5 The humidity display window displays the humidity from 30 to 90 6 Keep unpl...

Страница 10: ...c Contact dealer and repair it Water leakage Machine inclined backward Drain pipe is blocked Level the unit Remove the front panel and wipe off dirt from the pipe POWER PROTECTION light flashes The temperature sensor is open circuit or short circuit Replace the temperature sensor Machine can not defrost The temperature sensor is loosening The valve is damaged Fix the temperature sensor well Replac...

Страница 11: ...Assembled in Thailand ไทย ...

Отзывы: