HI 2151 SERIES WEIGHT CONTROLLERS REMOTE I/O OPTION
5-22
Block Write
Command Number
57: BCD Output
Configuration
Block Write
Command Number
58: Configuration of
Analog Output
NOTE:
This command is only active if this option is installed in the HI 2151WC
BLOCK WRITE COMMAND NUMBER 57: BCD Output Configuration
START
WORD DEFINITIONS:
#WORDS
WORD
Command number: A value of 57 (decimal)
bit 0
1
bit 1
0
bit 2
0
bit 3
1
bit 4
1
bit 5
1
bit 6
0
bit 7
0
Format of output:
bit 8
If set, will update BCD output when “print” button or remote
function is activated.
bit 9
Reserved for future use
bit 10
If set, will output weight data currently displayed
bit 11
If set, will output Tare Value
bit 12
If set, will output Net Weight
bit 13
If set, will output Gross Weight
bit 14 - 15
Reserved for future use
1
0
TOTAL NUMBER OF WORDS
1
TABLE 5-24: BLOC WRITE COMMAND NUMBER 57: BCD OUTPUT CONFIGURATION
BLOCK WRITE COMMAND NUMBER 58: Configuration of Analog Output
START
WORD DEFINITIONS:
#WORDS
WORD
Command number: A value of 58 (decimal)
bit 0
0
bit 1
1
bit 2
0
bit 3
1
bit 4
1
bit 5
1
bit 6
0
bit 7
0
Weight parameter to be transmitted
bits 8 - 15
A value from 0 to 4 (0 = Gross, 1 = Net, 2 = Rate-of-Change,
3 = Peak Force, 4 = Totalized Amount)
1
0