Hanwell Smart Receiver 2 (SR2)
Instruction Manual
IM6001 - 3
Page 6 of 22
hanwell.com
3
Copy of Document GD6014
Hanwell Document
GD6014 – Hanwell EMS Pre-Requisites
should have been supplied when
the SR2 was ordered, so that the pre-requisites could be completed in advance. The contents
of it are reproduced here in case the original has been lost.
This Section lists the pre-requisites – physical and virtual – needed to install and configure an
SR2 for operation on a network. The required information can, in most cases, be obtained
from your IT Department.
Note:
The network information must be available prior to the commissioning of the System.
3.1
Physical Pre-requisites
The following pre-requisites assume that a final location for the SR2(s) has been identified
following a Radio Survey. If this is not the case, then the following should be factored in when
deciding the SR2’s final location.
There should be:
A 24-hour mains power outlet within 1.5m of the planned location.
An enabled 10/100 Base T LAN socket at the planned location.
Note:
If this is greater than 1m from the planned location, a suitable straight through
CAT5 lead is required. This can, in most cases, be supplied by your IT department.
A suitable wall structure on which the SR2 can be mounted so that the antenna is
vertical.
The planned location should NOT:
Be in an area subjected to high temperature or humidity levels.
Have any metallic objects within 0.3 metres of the antenna in any direction;
this
includes any structures hidden within walls, pillars etc
.
Содержание IM6001