VPIFb

FEB 2008

TROUBLESHOOTING GUIDE FOR VPIF

Problem/Complaint

Check /Solution

Valve stuck

– Wire size/gauge to small

– Supply power not adequate 

– Cable connectors wired incorrectly

– Check signal polarity - #3 and #4, #5 and #6 wires

– Excessive dir t in valve; Use MOV T tool to check for rough      

   movement

No Valve Position Feedback or Display 25%

– Check 24 VDC power supply  

– Check signal polarity - #3 and #4, #5 and #6 wires

– Cable connectors wired incorrectly 

– VPIF in the Local and Remote Feedback Mode

No visual data on LED Display 

– Check 24 VAC supply power is good (+/-5%)

– Cable connectors wired incorrectly

Valve % open span is ver y limited

– Recalibrate SMV

VPIF indicates % open greater than 100.0%

– Recalibrate SMV

– +/- 3% is within tolerance

VPIF indicates % open less than 0.0%

– Recalibrate SMV

– +/- 3% is within tolerance

VPIF LED Display value is greater than or less 

than what is indicated by the system controller 
or PLC

– If reading between the two devices are /- 3%, this 

is normal

System computer or PLC displays open for SMV 
valve position feedback

– VPIF configured in wrong feedback mode

– Cable connectors wired incorrectly

– Check signal polarity - #3 and #4, #5 and #6 wires

VPIF % open 10

ths

 position is not stable 

– +/- 3% is within tolerance

VPIF % open is not stable

– Check wiring is sufficient size for the distance from 24 VAC 

power supply and number of valves connected to the 24 VAC 
power supply

– Check 24 VAC power source  

– System controller or PLC operation is erratic

– RFI/EMI inter ference

Содержание VPIF

Страница 1: ...rs in any direction from the valve VPIEC Extension Cables are available where more length is required KEY FEATURES Provides local indication of the SMV valve position Facilitates SMV recalibration Ver...

Страница 2: ...onnect cables If the VPIF is mounted on the valve the 8 cable and the 2 cable with pigtails can be connected together for a total of 10 to the customer supplied junction box If the VPIF is mounted sep...

Страница 3: ...the valve from open and closed 1 Secure the refrigeration system to allow the valve to open and close fully without causing undesirable system problems to occur 2 Mount and secure the motor on the se...

Страница 4: ...with valve position display No jumper connection standard Place jumper on one post for future use CHANGING THE FEEDBACK MODE Tools required 2mm hex key Phillips head screwdriver and needle nose plier...

Страница 5: ...5 VPIFb FEB 2008 MODEL VPIF WIRING Figure D...

Страница 6: ...each foot to aid in correct wire connections To a d d a q u i c k d i s c o n n e c t c o n n e c t o r on Sealed Motor Valve power head use Kit number 75 1211 which includes a field solder male cable...

Страница 7: ...ate SMV VPIF indicates open greater than 100 0 Recalibrate SMV 3 is within tolerance VPIF indicates open less than 0 0 Recalibrate SMV 3 is within tolerance VPIF LED Display value is greater than or l...

Страница 8: ...cted life of seven to ten years is typical This should be understood as only a suggested replacement time period Actual ambient conditions contaminants quality of electric current voltage etc may nece...

Отзывы: