FEEDBACK MODES
There are two feedback modes for the VPIF, “Local
Display Only” or “Local Display and Remote Feedback”.
To change the setting, the VPIF must be opened and
manually set to the proper system requirements.
Improper settings can result in damage to the system
controller and/or VPIF.
The VPIF is shipped from the factor y with the jumper
in the “Local Display and Remote Feedback” mode.
1)
Local Display Only -
This mode is used when the
controller is not equipped with a valve position
display. The VPIF always displays valve position
in the AUTO, OPEN or CLOSE switch positions.
(Jumper on pins 1 and 2).
3)
Local Display and Remote Feedback
– With
switch in AUTO, valve position is read at both
the VPIF and controller (with valve position
display). With switch in OPEN or CLOSE
position, valve position is displayed on both the
VPIF
and
customer or Hansen controllers with
valve position display. (No jumper connection
standard. Place jumper on one post for future
use).
CHANGING THE FEEDBACK MODE
Tools required: 2mm hex key, Phillips head screwdriver
and needle nose pliers.
To c h a n g e t h e f e e d b a c k m o d e , m o v e t h e
two position jumper to the appropriate setting. Take
care not to touch the electronic components as static
electricity may damage the electronic circuits.
1. Remove power and control signal lines from the
VPIF by removing the external quick disconnect
connector labeled “TO CONTROLLER”.
2. Remove the clear cover from the VPIF.
3. Remove the black acr ylic plastic faceplate by
removing the four buttonhead hex keyed screws.
Use a 2mm hex key.
4. Rotate the bottom of the plastic plate to the left.
Only lift the plate enough to clear the side of the
housing.
Refer to Figure C.
5. Use needle nose pliers to make the required
changes.
6. Assemble unit in reverse order.
Local Display Only Mode
: Jumper on pins 1 and 2
Local Display and Remote Feedback Mode
: No
jumper connection (standard). Place jumper on one
post for future use.
VPIF FACEPLATE
Figure C