FEEDBACK MODES

There are two feedback modes for the VPIF, “Local 

Display Only” or “Local Display and Remote Feedback”. 

To change the setting, the VPIF must be opened and 

manually set to the proper system requirements. 
Improper settings can result in damage to the system 
controller and/or VPIF.  

The VPIF is shipped from the factor y with the jumper 

in the “Local Display and Remote Feedback” mode.

1)  

Local Display Only - 

This mode is used when the 

controller is not equipped with a valve position 
display.  The VPIF always displays valve position 

in the AUTO, OPEN or CLOSE switch positions. 

(Jumper on pins 1 and 2).

3) 

Local Display and Remote Feedback 

 – With 

switch  in  AUTO,  valve  position  is  read  at  both 
the VPIF and controller (with valve position 
display).  With switch in OPEN or CLOSE 
position, valve position is displayed on both the 
VPIF 

and

 customer or Hansen controllers with 

valve position display.  (No jumper connection  
standard. Place jumper on one post for future 
use).

CHANGING THE FEEDBACK MODE

Tools required: 2mm hex key, Phillips head screwdriver 

and needle nose pliers.

To   c h a n g e   t h e   f e e d b a c k   m o d e ,   m o v e   t h e 

two position jumper to the appropriate setting. Take 
care not to touch the electronic components as static 
electricity may damage the electronic circuits.

1.  Remove power and control signal lines from the 

VPIF by removing the external quick disconnect 
connector labeled “TO CONTROLLER”. 

2.  Remove the clear cover from the VPIF.

3.  Remove the black acr ylic plastic faceplate by 

removing the four buttonhead hex keyed screws. 
Use a 2mm hex key.

4.  Rotate the bottom of the plastic plate to the left. 

Only lift the plate enough to clear the side of the 

housing.  

Refer to Figure C.

5.  Use  needle  nose  pliers  to  make  the  required 

changes. 

6.  Assemble unit in reverse order.

Local Display Only Mode

: Jumper on pins 1 and 2

Local Display and Remote Feedback Mode

:   No 

jumper connection (standard). Place jumper on one 
post for future use.

VPIF FACEPLATE

Figure C

Содержание VPIF

Страница 1: ...rs in any direction from the valve VPIEC Extension Cables are available where more length is required KEY FEATURES Provides local indication of the SMV valve position Facilitates SMV recalibration Ver...

Страница 2: ...onnect cables If the VPIF is mounted on the valve the 8 cable and the 2 cable with pigtails can be connected together for a total of 10 to the customer supplied junction box If the VPIF is mounted sep...

Страница 3: ...the valve from open and closed 1 Secure the refrigeration system to allow the valve to open and close fully without causing undesirable system problems to occur 2 Mount and secure the motor on the se...

Страница 4: ...with valve position display No jumper connection standard Place jumper on one post for future use CHANGING THE FEEDBACK MODE Tools required 2mm hex key Phillips head screwdriver and needle nose plier...

Страница 5: ...5 VPIFb FEB 2008 MODEL VPIF WIRING Figure D...

Страница 6: ...each foot to aid in correct wire connections To a d d a q u i c k d i s c o n n e c t c o n n e c t o r on Sealed Motor Valve power head use Kit number 75 1211 which includes a field solder male cable...

Страница 7: ...ate SMV VPIF indicates open greater than 100 0 Recalibrate SMV 3 is within tolerance VPIF indicates open less than 0 0 Recalibrate SMV 3 is within tolerance VPIF LED Display value is greater than or l...

Страница 8: ...cted life of seven to ten years is typical This should be understood as only a suggested replacement time period Actual ambient conditions contaminants quality of electric current voltage etc may nece...

Отзывы: