background image

3

K109i

AUG 2015

When a dual pressure-relief system is being put into service, 
the three-way valve stem should be positioned so that only 
one valve is exposed to pressure. While the valve can be 
either frontseated (front port is closed) or backseated (back 
port is closed), the backseated position is recommended 
because it takes pressure off the packing and reduces the 
possibility of packing leaks.
Vent the relief valve exit to a safe outdoor location in an 
approved manner away from people and building openings. 
Do not install valves in a refrigerated space unless 
precautions are taken to prevent moisture migration into 
the valve body or the relief vent line. Avoid trapped ice 
build-up between valves and other equipment.
Only apply thread sealing compound to external pipe threads 
and use a modest amount to avoid getting compound inside 
the valve. Use brackets or hangers to support the pipe and 
prevent the valve from being overly stressed. Do not put 
undue stress on the valve by using it to stretch or align pipe.
Pressure test all valves and related piping for leaks. When 
testing a dual pressure-relief system, the three-way valve 
stem should be in the mid position (only during testing), 
ensuring that all valves are properly leak tested. Do not 
discharge valves prior to installation or when pressure 
testing. Never attempt to reset or change the valve setting. 

Always replace pressure-relief valves once they have 
discharged.

SERVICE AND MAINTENANCE

These tamper-resistant pressure-relief valves are accurately 

factory set and do not require any field adjustments 
whatsoever. They are intended for one time over-pressure 

operation and must be replaced immediately af ter 
discharging because setting or seat tightness may be 
altered. Annually, relief valves must be visually inspected for 
corrosion or accumulation of scale and for leaks. Pressure-

relief valves must be removed and replaced with new valves 
at least every five years. Even when simply replacing an 

existing valve, a review of requirements per current local 
and national code is advisable.

NAMEPLATE INFORMATION

The nameplate, located on the side of Hansen pressure- 

relief valves, contains important information about the 
valve pressure setting, capacity and date of manufacture. 

The date code traces the month and year the valve  

was built. This is a helpful guide in establishing an 
approximate date of service. Example: A valve with Date 
Code 0418001 13B, indicates that it was valve number 001 
built on April 18 of 2013 to revision level B. See nameplate 
below for location of data.

MATERIAL SPECIFICATIONS

Body:  Ductile iron, ASTM A395
Piston:  Stainless steel
Spring:  Stainless steel
Seat Insert:  Stainless steel
Seat Discs:  Premium grade virgin Teflon

®

 (PTFE)

Cap: Steel
Cap O-ring:  Neoprene
Maximum Temperature Rating:  240˚F (115˚C)
Safe Working Pressure:  400 psig (28 bar)
Setting Range:  150 to 400 psig (10.4 to 28 bar)

INSTALLATION

Installation should be performed by trained and qualified 
personnel only. Hansen pressure-relief valves come with 
an installation date tag to identify the number of years the 
valve has been in service. The H5600 “R” series capacity 
valves have green installation date tags, while all others 
are blue. When installing the pressure-relief valve, remove 
the knockouts corresponding to the current year and month. 
Use a pen to push the knockout partially through the tag 
and tear-away from other side.
Pressure-relief valves for ammonia refrigeration are subject 
to preventative inspection and maintenance or periodic 
replacement Risk Management Program (RMP). 

Relief 

valves must be replaced after 5 years of service in 
application. 

However, once a valve discharges it 

must

 

be replaced as soon as possible. Self-reseating is not 

dependable because of dirt.
Protect pressure-relief valves from dirt and moisture. 
Match capacity on valve nameplate to system document 
as specified by system designer and based upon protected 
vessel volume. Mount valve directly at the vapor space of 
pressure vessel or on connecting non-valved vapor piping 
as close to the vessel as possible. Pressure-relief valves 
should be installed upright, although horizontal installation 

is possible.
Remove plastic shipping cap from outlet of pressure-relief 
valve. Connect to vent line piping to protect outlet of valve 
from water and debris. Plastic shipping cap will not protect 

outlet of valve from falling water or debris. Vent line piping 

must have drain line at low point to drain condensate from 
line per ASME Boiler and Pressure Vessel Code, Section 
VIII, Division 1.

GENERAL PRECAUTIONS

Never expose your face or body to a connected relief valve 

exit or piping.

Make sure the valve setting and capacity (see Nameplate 
Information Section) meet the requirements per system 
design in accordance with local and national regulations. 
Be sure to isolate the valve and related piping from the 
refrigeration system and pump out pressure to zero before 
attempting to install or replace any pressure-relief valve. 

Avoid residual refrigerant when doing so.

Remove the shipping caps from both the inlet and outlet 
before installation. Install the pressure-relief valve to the 
pressure vessel at a location above the liquid refrigerant 
level. These valves are for gas relief only. Do not install 
shut-off valves in line with pressure-relief valves. Install 
valves in locations where they will not be damaged by 
moving equipment such as lift trucks, etc. Install valves 
in a manner that enables them to be replaced.

1
2

3

6

4

5

  MANUFACTURE AND VALVE

  MONTH AND DAY OF

  INLET AND OUTLET SIZE

  AIR CAPACITY ACCORDING

  YEAR OF MANUFACTURE

  SET PRESSURE

6

5

4

3

  CATALOG NUMBER

  TO THE SET PRESSURE

1

2

 inch

Code:

Date

Capacity

Pressure

Size

..

Set

I n l e t

..

..

Cat. No.

..

O u t l e t

U.S.A.

  AND CURRENT REVISION

  NUMBER

  LETTER

Отзывы: