background image

2

K109i 
AUG 2015

*

* This factor is not suitable when combustible materials 

are within 20 feet (6.1 m) of the pressure vessel; refer to 

relevant codes for corrected sizing method.

Example: 

To determine the minimum required capacity 

of a relief valve for a vessel containing ammonia that 

measures 16 feet in length and 6 feet in outside diameter, 
the equation would be as follows: 0.5 x 6 x 16 = 48 lb/min.

Step 2: 

Determine the pressure setting needed. This 

should be at or below the design pressure of the vessel. 

The relief setting should also be at least 25% above the 

maximum expected operating pressure to avoid “weeping” 

of relief valves. The setting may be below (never above) the 
design pressure of the vessel, but it is sometimes best to 

match vessel design pressure and relief setting to minimize 
the likelihood of a discharge.

Step 3: 

Refer to the Valve Capacity Ratings below and 

select the valve with the required capacity (C) at the desired 
pressure setting.

VALVE SIZING AND SELECTION

Step 1:

 Use the formula below, per ANSI/ASHRAE 15 

Safety Standard for Refrigeration Systems to calculate the 
minimum required discharge capacity in pounds of air per 
minute. When selecting a dual pressure-relief valve system, 
be aware that each individual valve must have sufficient 

capacity to protect the vessel.

C=fDL

C = 

 

m i n i m u m   r e q u i r e d   d i s c h a r g e   c a p a c i t y   o f 

 

the relief device in pounds of air per minute.

f = 

 

f a c t o r   f o r   a m m o n i a   r e f r i g e r a n t   i s   0 . 5 * *, 

factor for R-22 and R-134a refrigerants is 1.6**, for 

other refrigerants see ANSI/ASHRAE 15 or contact 

factory.

D = 

outside diameter of vessel in feet. 

L =    

length of vessel in feet. 

 

 

 

O

N

T

A

C

R

I

A

Y

T

I

C

A

P

A

C

)

g

i

s

p

(

S

G

N

I

T

T

E

S

E

R

U

S

S

E

R

P

D

R

A

D

N

A

T

S

0

5

1

5

7

1

0

0

2

5

2

2

0

5

2

5

7

2

0

0

3

5

2

3

0

5

3

0

0

4

R

0

0

6

5

H

R

2

0

6

5

H

n

i

m

/

b

l

5

.

0

1

2

.

2

1

8

.

3

1

4

.

5

1

0

.

7

1

6

.

8

1

2

.

0

2

8

.

1

2

5

.

3

2

7

.

6

2

m

f

c

s

0

4

1

2

6

1

3

8

1

5

0

2

6

2

2

8

4

2

9

6

2

0

9

2

2

1

3

5

5

3

R

2

3

6

5

H

n

i

m

/

b

l

2

2

5

2

9

2

2

3

6

3

9

3

2

4

6

4

9

4

6

5

m

f

c

s

2

9

2

7

3

3

2

8

3

7

2

4

2

7

4

7

1

5

1

6

5

6

0

6

1

5

6

1

4

7

R

3

3

6

5

H

n

i

m

/

b

l

8

2

3

3

7

3

1

4

6

4

0

5

4

5

9

5

3

6

2

7

m

f

c

s

7

7

3

5

3

4

2

9

4

0

5

5

8

0

6

5

6

6

3

2

7

1

8

7

9

3

8

4

5

9

R

4

3

6

5

H

n

i

m

/

b

l

4

3

9

3

4

4

9

4

4

5

0

6

5

6

0

7

5

7

5

8

m

f

c

s

9

4

4

8

1

5

6

8

5

5

5

6

4

2

7

3

9

7

1

6

8

0

3

9

9

9

9

6

3

1

1

A

0

0

6

5

H

n

i

m

/

b

l

3

.

1

3

1

.

6

3

9

.

0

4

7

.

5

4

5

.

0

5

3

.

5

5

1

.

0

6

9

.

4

6

7

.

9

6

3

.

9

7

m

f

c

s

7

1

4

0

8

4

4

4

5

8

0

6

2

7

6

6

3

7

9

9

7

3

6

8

7

2

9

5

5

0

1

1

0

6

5

H

2

0

6

5

H

n

i

m

/

b

l

8

.

5

3

3

.

1

4

8

.

6

4

2

.

2

5

7

.

7

5

2

.

3

6

6

.

8

6

1

.

4

7

6

.

9

7

m

f

c

s

6

7

4

9

4

5

2

2

6

5

9

6

8

6

7

1

4

8

3

1

9

6

8

9

9

5

0

1

3

1

6

5

H

n

i

m

/

b

l

0

.

3

5

1

.

1

6

2

.

9

6

3

.

7

7

4

.

5

8

5

.

3

9

6

.

1

0

1

7

.

9

0

1

8

.

7

1

1

4

3

1

m

f

c

s

4

0

7

2

1

8

0

2

9

8

2

0

1

6

3

1

1

3

4

2

1

1

5

3

1

9

5

4

1

7

6

5

1

2

8

7

1

4

0

6

5

H

n

i

m

/

b

l

0

.

2

7

0

.

3

8

0

.

4

9

1

.

5

0

1

1

.

6

1

1

1

.

7

2

1

1

.

8

3

1

1

.

9

4

1

2

.

0

6

1

2

8

1

m

f

c

s

8

5

9

4

0

1

1

1

5

2

1

7

9

3

1

4

4

5

1

1

9

6

1

7

3

8

1

4

8

9

1

0

3

1

2

3

2

4

2

Important Note: These are atmospheric relief valves. Settings equal pressure above atmosphere when outlet is connected via 
proper piping to the atmosphere (outside). (scfm = Standard Cubic Feet per Minute)

INSTALLATION DIMENSIONS

O

N

T

A

C

S

N

O

I

T

C

E

N

N

O

C

D

E

D

A

E

R

H

T

T

P

N

A

(MM)

B

(MM)

C

(MM)

M

O

T

T

O

B

T (DN)

E

L

N

I

E

D

I

S

T (DN)

E

L

T

U

O

A

0

0

6

5

H

R

0

0

6

5

H

1

/

2

T (15)

P

F

"

3

/

4

T (20)

P

F

"

2.13"

(54)

2.75"

(70)

1.63"

(41)

3.00"

(76)

4.13"
(105)

2.25"

(57)

1

0

6

5

H

PT (25)

F

"

1

2

0

6

5

H

R

2

0

6

5

H

R

2

3

6

5

H

3

/

4

T (20)

P

F

"

PT (25)

F

"

1

1

3

1

6

5

H

R

3

3

6

5

H

T (25)

P

F

"

1

1

/

4

T (32)

P

F

"

1

1

/

2

T (40)

P

F

"

4

0

6

5

H

R

4

3

6

5

H

1

1

/

4

T (32)

P

F

"

H5600 “R” Series capacity valves have green installation 

date tags, while all others are blue.

A

B

C

PRESSURE-RELIEF VALVE CAPACITY RATINGS (NATIONAL BOARD CERTIFIED)

Отзывы: